Plan Review Details - Permit 01091257
Plan Review Stops For Permit 01091257
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-10-17 Cont ID  
Sent By hpiskura Date 2001-10-17 Time 11:55 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-10 Cont ID  
Sent By dpalmer Date 2001-10-10 Time 18:50 Rev Time 0.00
Received By dpalmer Date 2001-10-10 Time 18:50 Sent To  
Notes
2001-10-10 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PLANS NEED
 CLARIFICATION. PLANS ARE BEING SUBMITTED
 FOR COMMERCIAL OFFICES/SPACE AND PLANS
 LOAD CALCULATIONS ARE SHOWN FOR RESIDENT
 -IAL??? PLEASE CLARIFY.
  
 2)NOTE: PLEASE NOTE THAT ALL BRANCH
 CIRCUIT #`S NEED TO BE SHOWN ON PLANS
 FOR COMM SPACE. NEED TO CORRELATE WITH
 PANEL SCHEDULE. 215-5
  
 3)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C CU. 309.1 AND 210-63
  
 4)NOTE: PLEASE NOTE NO LIGHTING SHOWN?
 EGRESS? EMERGENCY? EXIT?
  
 PLEASE CALRIFY AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW.IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
 NOTE: CHANGE OF USE TO OFFICE, ALL
 WIRING METHODS EXISTING AND NEW WILL BE
 REQ`D TO MEET COMM WIRING METHODS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-10-18 Cont ID  
Sent By mcarsill Date 2001-10-18 Time 10:31 Rev Time 0.00
Received By mcarsill Date 2001-10-18 Time 10:31 Sent To  
Notes
2001-10-18 00:00:001) PLEASE INDICATE WHAT THE EXISTING
 USE FOR THE BUILDING WAS. WAS IT
 RESIDENTIAL OR BUSINESS. IF IT WAS
 RESIDENTIAL AND NOW IT APPEARS THAT
 THE BUILDING WILL BE USED FOR BUSINESS
 THEN IT WILL BE CONSIDERED A CHANGE
 OF USE.
 2) NO EXIT SIGNS OR EMERGENCY LIGTING
 EQUIPMENT SHOWN.
 3) PLEASE EXPLAIN EXITING ARRANGEMENT.
 TWO EXITS ARE REQUIRED FROM THE
 SECOND FLOOR. THE CODE DOES ALLOW FOR
 A SINGLE MEANS OF EGRESS FROM THE
 SECOND FLOOR BUT IT APPEARS THAT THE
 EXCEPTIONS TO THIS CODE DOES NOT EXIST.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-10-15 Cont ID  
Sent By ndenmark Date 2001-10-15 Time 11:10 Rev Time 0.33
Received By ndenmark Date 2001-10-15 Time 11:10 Sent To  
Notes
2001-10-15 00:00:00DENIED
 1. PROVIDE DUCT SIZES
 2. PROVIDE INFORMATION ON AIR FROM FIRST
 TO SECOND FLOOR AND DUCT PENETRATION TO
 CRAWL SPACE BELOW FIRST FLOOR.
 NOTE: DUCTS TO BE MINIMUM 4" ABOVE
 GROUND AT GRADE LEVEL.
 3. BATHROOMS WITHOUT MINIMUM 3 SQ FT
 CLEAR OPENING WINDOWS REQUIRE EXHAUST
 FANS.
 4. NO CFM SHOWN AT DROP INTO PASTOR'S
 OFFICE.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-11 Cont ID  
Sent By kstevens Date 2001-10-11 Time 15:35 Rev Time 0.50
Received By kstevens Date 2001-10-11 Time 15:35 Sent To  
Notes
2001-10-11 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SANITARY RISER DIAGRAM REQUIRED PER
 SPC SEC 104.2.1
  
 2) PAGE A1, TOILET FACILITIES SHALL BE
 ADAPTABLE PER FACBC-97 SEC 4.1.3(11)
 ADAPTABLE TOILET FACILITIES SHALL HAVE
 PROPER BACKING FOR W/C, AND SHOWER.
 SHOWER SIZE SHALL COMPLY WITH FIGURE 35
 (A) OR (B). PLEASE SHOW CLEAR FLOOR
 SPACE FOR W/C AND LAV. DOORS CAN NOT
 OPEN INTO THE CLEAR FLOOR SPACE OF A
 FIXTURE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***