Plan Review Details - Permit 01091257
| Plan Review Stops For Permit 01091257 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2001-10-17 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-10-17 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-10-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-10 |
Time |
18:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-10 |
Time |
18:50 |
Sent To |
|
|
| Notes |
| 2001-10-10 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS NEED | | | CLARIFICATION. PLANS ARE BEING SUBMITTED | | | FOR COMMERCIAL OFFICES/SPACE AND PLANS | | | LOAD CALCULATIONS ARE SHOWN FOR RESIDENT | | | -IAL??? PLEASE CLARIFY. | | | | | | 2)NOTE: PLEASE NOTE THAT ALL BRANCH | | | CIRCUIT #`S NEED TO BE SHOWN ON PLANS | | | FOR COMM SPACE. NEED TO CORRELATE WITH | | | PANEL SCHEDULE. 215-5 | | | | | | 3)NOTE: PLEASE NOTE MISSING OUTLET FOR | | | A/C CU. 309.1 AND 210-63 | | | | | | 4)NOTE: PLEASE NOTE NO LIGHTING SHOWN? | | | EGRESS? EMERGENCY? EXIT? | | | | | | PLEASE CALRIFY AND SUBMIT THE ABOVE | | | INFORMATION FOR REVIEW.IF THERE ARE | | | ANY QUESTIONS, PLEASE CALL. | | | NOTE: CHANGE OF USE TO OFFICE, ALL | | | WIRING METHODS EXISTING AND NEW WILL BE | | | REQ`D TO MEET COMM WIRING METHODS. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-10-18 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-18 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-18 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2001-10-18 00:00:00 | 1) PLEASE INDICATE WHAT THE EXISTING | | | USE FOR THE BUILDING WAS. WAS IT | | | RESIDENTIAL OR BUSINESS. IF IT WAS | | | RESIDENTIAL AND NOW IT APPEARS THAT | | | THE BUILDING WILL BE USED FOR BUSINESS | | | THEN IT WILL BE CONSIDERED A CHANGE | | | OF USE. | | | 2) NO EXIT SIGNS OR EMERGENCY LIGTING | | | EQUIPMENT SHOWN. | | | 3) PLEASE EXPLAIN EXITING ARRANGEMENT. | | | TWO EXITS ARE REQUIRED FROM THE | | | SECOND FLOOR. THE CODE DOES ALLOW FOR | | | A SINGLE MEANS OF EGRESS FROM THE | | | SECOND FLOOR BUT IT APPEARS THAT THE | | | EXCEPTIONS TO THIS CODE DOES NOT EXIST. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-10-15 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-10-15 |
Time |
11:10 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2001-10-15 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2001-10-15 00:00:00 | DENIED | | | 1. PROVIDE DUCT SIZES | | | 2. PROVIDE INFORMATION ON AIR FROM FIRST | | | TO SECOND FLOOR AND DUCT PENETRATION TO | | | CRAWL SPACE BELOW FIRST FLOOR. | | | NOTE: DUCTS TO BE MINIMUM 4" ABOVE | | | GROUND AT GRADE LEVEL. | | | 3. BATHROOMS WITHOUT MINIMUM 3 SQ FT | | | CLEAR OPENING WINDOWS REQUIRE EXHAUST | | | FANS. | | | 4. NO CFM SHOWN AT DROP INTO PASTOR'S | | | OFFICE. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-10-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-11 |
Time |
15:35 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-10-11 |
Time |
15:35 |
Sent To |
|
|
| Notes |
| 2001-10-11 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) SANITARY RISER DIAGRAM REQUIRED PER | | | SPC SEC 104.2.1 | | | | | | 2) PAGE A1, TOILET FACILITIES SHALL BE | | | ADAPTABLE PER FACBC-97 SEC 4.1.3(11) | | | ADAPTABLE TOILET FACILITIES SHALL HAVE | | | PROPER BACKING FOR W/C, AND SHOWER. | | | SHOWER SIZE SHALL COMPLY WITH FIGURE 35 | | | (A) OR (B). PLEASE SHOW CLEAR FLOOR | | | SPACE FOR W/C AND LAV. DOORS CAN NOT | | | OPEN INTO THE CLEAR FLOOR SPACE OF A | | | FIXTURE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|