Plan Review Details - Permit 01091150
Plan Review Stops For Permit 01091150
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-04-09 Cont ID  
Sent By hpiskura Date 2002-04-09 Time 09:43 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2002-03-27 Cont ID  
Sent By hpiskura Date 2002-03-27 Time 10:21 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-03-27 00:00:00THE PLANS SUBMITTED 3/22/02 DO NOT
 COMPLY WITH THE CODE.THE PLANS
 IDENTIFIED AS 07286970 ON THE LISTING
 AGENCY STAMP INDICATE THE FOLLOWING:
  
 SHEET 1 OF 4 WIND VELOCITY 130 MPH ASCE
 7-98.(AS NOTED PREVIOUSLY WPB IS IN
 AN140 MPH ZONE)
  
 SHEET 2 OF 4 WIND VELOCITY 110 MPH
  
 SHEET 3 OF 4 WIND VELOCITY 130 MPH ASCE
 7-98
  
 ALL OF THESE SHEETS ARE SIGNED AND
 SEALED BY JOHN BODZIAK, ARCH.
  
 THERE IS NO SHEET NUMBERED 4 OF 4.
  
 ANOTHER SHEET SIGNED AND SEALED BY
 BODZIAK DATED 3/19/02, PAGE 1 OF 1,
 BEARING "APPROVAL NUMBER 001092"
 CONTAINS SOME FOUNDATION INFORMATION.
  
 THIS SHEET DECLARES 140 MPH ASCE 7-98
 AND 2001 FBC.
  
 FOR THE CITY TO ACCEPT THIS STRUCTURE
 IN ACCORDANCE WITH THE MANUFACTURED
 BUILDING ACT OF 1979, THE PLANS MUST
 MEET THE CRITERIA CONTAINED IN THAT
 LEGISLATION AND THE FLORIDA
 ADMINISTRATIVE CODE.TO DATE THE PLANS
 SUBMITTED HAVE NOT.PLEASE PROVIDE
 PLANS LISTED FOR USE IN THIS AREA.
 INCLUDE A COPY OF THE DCA LISTING
 RECOGNITION LETTER.
  
 COMPLETE CALCULATIONS FOR THE
 FOUNDATION WERE REQUESTEED PREVIOUSLY
 AND TO DATE THIS HAS NOT BEEN DONE.
 I HAVE REVIEWED THE SLIDING AND
 OVERTURNING ANALYSIS PREPARED BY
 KENNETH GODFREY, PE.IN A PHONE
 COVERSTION TODAY HE TOLD ME HE IS NOT
 RESPONSIBLE FOR THE FOUNDATION DESIGN.
  
 PROVIDE A DCA APPROVAL LETTER PERTINENT
 TO THESE PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2002-03-11 Cont ID  
Sent By hpiskura Date 2002-03-11 Time 08:08 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-03-11 00:00:00THE CITY OF WEST PALM BEACH IS LOCATED
 IN THE 140 MPH WIND CONTOUR.SEE FIG.
 6-1B OF ASCE 7-98.
  
 STATE CLEARLY WHICH CODE THIS STRUCTURE
 HAS BEEN DESIGNED TO.SBC 1997 SECTION
 1606 HAS DIFFERENT WIND DESIGN
 REQUIREMENTS THAN ASCE7-98 AND CLEARLY
 PROHIBITS THE MIXING OF WIND LOADS FROM
 DIFFERENT SOURCES.SEE SBC 1606.1.2.1
 (1997)
  
 THE K.A. GODFREY, PE CALCULATIONS ARE
 130 MPH AND DECLARE EXPOSURES C AND D.
 GIVENTHE PROPOSED SITING, PLEASE
 CLARIFY THESE CHOICES AND THE
 DIRECTIONS FROM WHICH THEY WILL BE
 APPLIED.
  
 THE JA BODZIAK, ARCH FOUNDATION PLAN
 DATED 2/4/02 MIXES WIND LOAD SOURCES
 AND CODES.THE PIER CALCUALTION HAS
 ONLY GRAVITY LOADS.SEE SBC 1609.1
 AND/OR ASCE 7-98 2.0 COMBINATION OF
 LOADS.
  
 SHEET 4.3 OF THE GODFREY CALCULATIONS
 HAS THE TIE DOWNS SPACED AT 6.19' MAX.
 THE BODZIAK AT 7.5'
  
 THE BODZIAK FOUNDATION PLAN CALLS OUT
 2000 PSF SOIL BEARING CAPACITY.
  
 PLEASE REVIEW CHAPTER 61G15-30
 OF THE FLORIDA ADMINISTRATIVE CODE,
 "RESPONSIBILITY RULES COMMON TO ALL
 ENGINEERS"
  
 PROVIDE A BUILDING LISTED FOR USE IN
 THIS AREA.1997 SBC 110 MPH (1606) OR
 ASCE 7-95 (INVOKED BY THE 97 SBC) 140
 MPH.
  
 OR THE 2001 FBC 140 MPH WIND ZONE.
  
 PROVIDE A FOUNDATION DESIGN, WITH
 COMPLETE CALCUALTIONS IN ACCORDANCE
 WITH GOOD ENGINEERING PRACTICE.
  
 IF THIS BUILDING IS TO HAVE THE FLOOR
 LEVEL SET AT THE SAME HEIGHT AS THE
 SURROUNDING GRADE, HOW WILL THE 18"
 CLEARANCE TO GRADE CALLED OUT ON THE
 FOUNDATION SHEET BE ACCOMPLISHED?SEE
 ALSO, SBC 2303.3 AND 2304.2.5.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-12-21 Cont ID  
Sent By hpiskura Date 2001-12-21 Time 13:42 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-12-21 00:00:00SAME AS 10/5/01.NO CHANGE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-10-05 Cont ID  
Sent By hpiskura Date 2001-10-05 Time 14:30 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-10-05 00:00:00PROVIDE A COPY OF THE DCA LETTER OF
 ACCEPTANCE.
  
 SHOW THE ELEVATIONS FOR HC ACCESS, THE
 PORCH CONSTRUCTION AND OVERALL SITE
 ACCESSIBILITY.
  
 THE PIER LOAD / SOIL BEARING VALUE IS
 NOT ACCEPTABLE.SEE SBC 1804.1 AND
 PARTICULARLY SBC 1804.4. GIVEN THE
 DECLARED 16" X 16" PAD SIZES THE TABLE
 LOADS EXCEED THE SOIL BEARING VALUE.
 PROVIDE SIGNED AND SEALED CALCULATIONS
 FOR THE FOUNDATION SYSTEM, INCLUDING
 UPLIFT INVESTIGATION.
  
 THE $5000.00 DECLARED PERMIT VALUATION
 IS TOO LOW FOR THIS SCOPE OF WORK.
 PROVIDE A DETAILED TAKEOFF WITH
 EXTENSIONS FOR THE PARKING LOT AND THE
 BUILDING SET UP.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-12-27 Cont ID  
Sent By dpalmer Date 2001-12-27 Time 17:24 Rev Time 0.00
Received By dpalmer Date 2001-12-27 Time 17:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-01 Cont ID  
Sent By dpalmer Date 2001-10-01 Time 23:19 Rev Time 0.00
Received By dpalmer Date 2001-10-01 Time 23:18 Sent To  
Notes
2001-10-01 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT ELECTRICAL
 PLAN FOR TRAILER WAS SUBMITTED. PLEASE
 NOTE THAT TRAILER IS EXEMPT FOR ELEC.
 REVIEW.
 PLEASE NOTE THAT WAS IS NEEDED IS AN
 ELECTRICAL RISER DIAGRAM FOR SERVICE
 AND TRAILER HOOK-UP.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2002-03-11 Cont ID  
Sent By mamini Date 2002-03-11 Time 13:26 Rev Time 1.00
Received By mamini Date 2002-03-11 Time 13:26 Sent To  
Notes
2002-03-11 00:00:00PASSED :
 1. RESPONSES TO THE PREVIOUS REVIEW
 COMMENTS DATED 12-26-01 SATISFACTORY.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT.8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-12-26 Cont ID  
Sent By mamini Date 2001-12-26 Time 09:01 Rev Time 2.00
Received By mamini Date 2001-12-26 Time 09:01 Sent To  
Notes
2001-12-26 00:00:00FAILED :
 1. SEPARATE PERMITS FROM HEALTH
 DEPARTMENT FOR THE PROPOSED STORAGE TANK
 AND TEMPORARY WELL IS REQUIRED.
 2. ALL OFF-STREET PARKING MUST BE
 PAINTED WITH DOUBLE 4" WHITE AND BLUE
 FOR H.C PER CITY REQUIREMENT.
 3. THE COST OF SITE / UTILITIES WORKS
 MUST BE INCLUDED IN PERMITTING FEE.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-12-28 Cont ID  
Sent By mcarsill Date 2001-12-28 Time 12:55 Rev Time 0.00
Received By mcarsill Date 2001-12-28 Time 12:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-10-01 Cont ID  
Sent By mcarsill Date 2001-10-01 Time 16:01 Rev Time 0.00
Received By mcarsill Date 2001-10-01 Time 16:01 Sent To  
Notes
2001-10-01 00:00:001) PLEASE PROVIDE A LETTER INDICATING
 HOW LONG THE TEMPORARY TRAILER WILL
 BE ON SITE.
 2) PLEASE PROVIDE ADDRESS FOR TRAILER
 IN THE EVENT OF AN EMERGENCY.
 3) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING AND AFTER CONSTRUCTION.
 4) SMOKE DETECTORS REQUIRED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-03-14 Cont ID  
Sent By drunnels Date 2002-03-14 Time 14:41 Rev Time 0.00
Received By drunnels Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-03-07 Cont ID  
Sent By kstevens Date 2002-03-07 Time 10:09 Rev Time 0.33
Received By kstevens Date 2002-03-07 Time 10:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-12-19 Cont ID  
Sent By kstevens Date 2001-12-19 Time 13:46 Rev Time 1.00
Received By kstevens Date 2001-12-19 Time 13:46 Sent To  
Notes
2001-12-19 00:00:00DENIED
  
 1) APPROVAL AND PERMITS REQUIRED FROM
 HEALTH DEPT BEFORE PLUMBING PLAN REVIEW.
 LETTERS FROM HEALTH DEPT. SHALL ACCOMP-
 ANY PLANS FOR PLUMBING APPROVAL.
  
 2) UTILITY DEPT. APPROVAL REQUIRED. AS
 SOON AS SEWER AND WATER ARE RELEASED FOR
 USE THE TRAILER SHALL BE HOOKED UP TO
 CITY UTILITIES.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-05 Cont ID  
Sent By kstevens Date 2001-10-05 Time 15:13 Rev Time 0.50
Received By kstevens Date 2001-10-05 Time 15:13 Sent To  
Notes
2001-10-05 00:00:00DENIED
  
 1) PLEASE INDICATE IF THERE IS SEWER
 FACILITIES. IF NOT, A LETTER AND PERMIT
 FROM THE HEALTH IS REQUIRED.
  
 2) A RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. PLSEAS INDICATE ON PLANS.
  
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 3 Status P Date 2002-03-14 Cont ID  
Sent By sgraham Date 2002-03-14 Time 08:22 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2002-01-03 Cont ID  
Sent By sgraham Date 2002-01-03 Time 11:19 Rev Time 0.00
Received By sgraham Date 2002-03-12 Time 14:45 Sent To  
Notes
2002-01-03 00:00:00NEED TO HAS A SITE PLAN WITH THE
 LANDSCAPING SHOWN

Review Stop Z ZONING
Rev No 1 Status F Date 2001-09-27 Cont ID  
Sent By sgraham Date 2001-09-27 Time 07:46 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***