| Plan Review Stops For Permit 01091150 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2002-04-09 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-04-09 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2002-03-27 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-03-27 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-27 00:00:00 | THE PLANS SUBMITTED 3/22/02 DO NOT | | | COMPLY WITH THE CODE.THE PLANS | | | IDENTIFIED AS 07286970 ON THE LISTING | | | AGENCY STAMP INDICATE THE FOLLOWING: | | | | | | SHEET 1 OF 4 WIND VELOCITY 130 MPH ASCE | | | 7-98.(AS NOTED PREVIOUSLY WPB IS IN | | | AN140 MPH ZONE) | | | | | | SHEET 2 OF 4 WIND VELOCITY 110 MPH | | | | | | SHEET 3 OF 4 WIND VELOCITY 130 MPH ASCE | | | 7-98 | | | | | | ALL OF THESE SHEETS ARE SIGNED AND | | | SEALED BY JOHN BODZIAK, ARCH. | | | | | | THERE IS NO SHEET NUMBERED 4 OF 4. | | | | | | ANOTHER SHEET SIGNED AND SEALED BY | | | BODZIAK DATED 3/19/02, PAGE 1 OF 1, | | | BEARING "APPROVAL NUMBER 001092" | | | CONTAINS SOME FOUNDATION INFORMATION. | | | | | | THIS SHEET DECLARES 140 MPH ASCE 7-98 | | | AND 2001 FBC. | | | | | | FOR THE CITY TO ACCEPT THIS STRUCTURE | | | IN ACCORDANCE WITH THE MANUFACTURED | | | BUILDING ACT OF 1979, THE PLANS MUST | | | MEET THE CRITERIA CONTAINED IN THAT | | | LEGISLATION AND THE FLORIDA | | | ADMINISTRATIVE CODE.TO DATE THE PLANS | | | SUBMITTED HAVE NOT.PLEASE PROVIDE | | | PLANS LISTED FOR USE IN THIS AREA. | | | INCLUDE A COPY OF THE DCA LISTING | | | RECOGNITION LETTER. | | | | | | COMPLETE CALCULATIONS FOR THE | | | FOUNDATION WERE REQUESTEED PREVIOUSLY | | | AND TO DATE THIS HAS NOT BEEN DONE. | | | I HAVE REVIEWED THE SLIDING AND | | | OVERTURNING ANALYSIS PREPARED BY | | | KENNETH GODFREY, PE.IN A PHONE | | | COVERSTION TODAY HE TOLD ME HE IS NOT | | | RESPONSIBLE FOR THE FOUNDATION DESIGN. | | | | | | PROVIDE A DCA APPROVAL LETTER PERTINENT | | | TO THESE PLANS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2002-03-11 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-03-11 |
Time |
08:08 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-11 00:00:00 | THE CITY OF WEST PALM BEACH IS LOCATED | | | IN THE 140 MPH WIND CONTOUR.SEE FIG. | | | 6-1B OF ASCE 7-98. | | | | | | STATE CLEARLY WHICH CODE THIS STRUCTURE | | | HAS BEEN DESIGNED TO.SBC 1997 SECTION | | | 1606 HAS DIFFERENT WIND DESIGN | | | REQUIREMENTS THAN ASCE7-98 AND CLEARLY | | | PROHIBITS THE MIXING OF WIND LOADS FROM | | | DIFFERENT SOURCES.SEE SBC 1606.1.2.1 | | | (1997) | | | | | | THE K.A. GODFREY, PE CALCULATIONS ARE | | | 130 MPH AND DECLARE EXPOSURES C AND D. | | | GIVENTHE PROPOSED SITING, PLEASE | | | CLARIFY THESE CHOICES AND THE | | | DIRECTIONS FROM WHICH THEY WILL BE | | | APPLIED. | | | | | | THE JA BODZIAK, ARCH FOUNDATION PLAN | | | DATED 2/4/02 MIXES WIND LOAD SOURCES | | | AND CODES.THE PIER CALCUALTION HAS | | | ONLY GRAVITY LOADS.SEE SBC 1609.1 | | | AND/OR ASCE 7-98 2.0 COMBINATION OF | | | LOADS. | | | | | | SHEET 4.3 OF THE GODFREY CALCULATIONS | | | HAS THE TIE DOWNS SPACED AT 6.19' MAX. | | | THE BODZIAK AT 7.5' | | | | | | THE BODZIAK FOUNDATION PLAN CALLS OUT | | | 2000 PSF SOIL BEARING CAPACITY. | | | | | | PLEASE REVIEW CHAPTER 61G15-30 | | | OF THE FLORIDA ADMINISTRATIVE CODE, | | | "RESPONSIBILITY RULES COMMON TO ALL | | | ENGINEERS" | | | | | | PROVIDE A BUILDING LISTED FOR USE IN | | | THIS AREA.1997 SBC 110 MPH (1606) OR | | | ASCE 7-95 (INVOKED BY THE 97 SBC) 140 | | | MPH. | | | | | | OR THE 2001 FBC 140 MPH WIND ZONE. | | | | | | PROVIDE A FOUNDATION DESIGN, WITH | | | COMPLETE CALCUALTIONS IN ACCORDANCE | | | WITH GOOD ENGINEERING PRACTICE. | | | | | | IF THIS BUILDING IS TO HAVE THE FLOOR | | | LEVEL SET AT THE SAME HEIGHT AS THE | | | SURROUNDING GRADE, HOW WILL THE 18" | | | CLEARANCE TO GRADE CALLED OUT ON THE | | | FOUNDATION SHEET BE ACCOMPLISHED?SEE | | | ALSO, SBC 2303.3 AND 2304.2.5. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-12-21 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-12-21 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-12-21 00:00:00 | SAME AS 10/5/01.NO CHANGE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-10-05 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-10-05 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-05 00:00:00 | PROVIDE A COPY OF THE DCA LETTER OF | | | ACCEPTANCE. | | | | | | SHOW THE ELEVATIONS FOR HC ACCESS, THE | | | PORCH CONSTRUCTION AND OVERALL SITE | | | ACCESSIBILITY. | | | | | | THE PIER LOAD / SOIL BEARING VALUE IS | | | NOT ACCEPTABLE.SEE SBC 1804.1 AND | | | PARTICULARLY SBC 1804.4. GIVEN THE | | | DECLARED 16" X 16" PAD SIZES THE TABLE | | | LOADS EXCEED THE SOIL BEARING VALUE. | | | PROVIDE SIGNED AND SEALED CALCULATIONS | | | FOR THE FOUNDATION SYSTEM, INCLUDING | | | UPLIFT INVESTIGATION. | | | | | | THE $5000.00 DECLARED PERMIT VALUATION | | | IS TOO LOW FOR THIS SCOPE OF WORK. | | | PROVIDE A DETAILED TAKEOFF WITH | | | EXTENSIONS FOR THE PARKING LOT AND THE | | | BUILDING SET UP. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-12-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-27 |
Time |
17:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-27 |
Time |
17:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-10-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-01 |
Time |
23:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-01 |
Time |
23:18 |
Sent To |
|
|
| Notes |
| 2001-10-01 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT ELECTRICAL | | | PLAN FOR TRAILER WAS SUBMITTED. PLEASE | | | NOTE THAT TRAILER IS EXEMPT FOR ELEC. | | | REVIEW. | | | PLEASE NOTE THAT WAS IS NEEDED IS AN | | | ELECTRICAL RISER DIAGRAM FOR SERVICE | | | AND TRAILER HOOK-UP. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2002-03-11 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2002-03-11 |
Time |
13:26 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2002-03-11 |
Time |
13:26 |
Sent To |
|
|
| Notes |
| 2002-03-11 00:00:00 | PASSED : | | | 1. RESPONSES TO THE PREVIOUS REVIEW | | | COMMENTS DATED 12-26-01 SATISFACTORY. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT.8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2001-12-26 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-12-26 |
Time |
09:01 |
Rev Time |
2.00 |
| Received By |
mamini |
Date |
2001-12-26 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2001-12-26 00:00:00 | FAILED : | | | 1. SEPARATE PERMITS FROM HEALTH | | | DEPARTMENT FOR THE PROPOSED STORAGE TANK | | | AND TEMPORARY WELL IS REQUIRED. | | | 2. ALL OFF-STREET PARKING MUST BE | | | PAINTED WITH DOUBLE 4" WHITE AND BLUE | | | FOR H.C PER CITY REQUIREMENT. | | | 3. THE COST OF SITE / UTILITIES WORKS | | | MUST BE INCLUDED IN PERMITTING FEE. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-12-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-28 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-28 |
Time |
12:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-10-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-01 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-01 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2001-10-01 00:00:00 | 1) PLEASE PROVIDE A LETTER INDICATING | | | HOW LONG THE TEMPORARY TRAILER WILL | | | BE ON SITE. | | | 2) PLEASE PROVIDE ADDRESS FOR TRAILER | | | IN THE EVENT OF AN EMERGENCY. | | | 3) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | | TO,DURING AND AFTER CONSTRUCTION. | | | 4) SMOKE DETECTORS REQUIRED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2002-03-14 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2002-03-14 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-03-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-03-07 |
Time |
10:09 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2002-03-07 |
Time |
10:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-12-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-12-19 |
Time |
13:46 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2001-12-19 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2001-12-19 00:00:00 | DENIED | | | | | | 1) APPROVAL AND PERMITS REQUIRED FROM | | | HEALTH DEPT BEFORE PLUMBING PLAN REVIEW. | | | LETTERS FROM HEALTH DEPT. SHALL ACCOMP- | | | ANY PLANS FOR PLUMBING APPROVAL. | | | | | | 2) UTILITY DEPT. APPROVAL REQUIRED. AS | | | SOON AS SEWER AND WATER ARE RELEASED FOR | | | USE THE TRAILER SHALL BE HOOKED UP TO | | | CITY UTILITIES. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-10-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-05 |
Time |
15:13 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-10-05 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2001-10-05 00:00:00 | DENIED | | | | | | 1) PLEASE INDICATE IF THERE IS SEWER | | | FACILITIES. IF NOT, A LETTER AND PERMIT | | | FROM THE HEALTH IS REQUIRED. | | | | | | 2) A RPZ BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE. PLSEAS INDICATE ON PLANS. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2002-03-14 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-03-14 |
Time |
08:22 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2002-01-03 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-01-03 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2002-03-12 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2002-01-03 00:00:00 | NEED TO HAS A SITE PLAN WITH THE | | | LANDSCAPING SHOWN |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2001-09-27 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-09-27 |
Time |
07:46 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|