| Plan Review Stops For Permit 01091004 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-12-05 |
|
|
Cont ID |
|
| Sent By |
lhatten |
Date |
2001-12-05 |
Time |
15:19 |
Rev Time |
1.00 |
| Received By |
lhatten |
Date |
2001-12-05 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2001-12-05 00:00:00 | LETTERS ON FILLING POOL WITH DIRT , | | | SOUTHSIDE RAMP & NORTHSIDE STAIRS | | | PER DETAILS OKED PER LOU HATTEN | | | SAME AS BELOW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-11-30 |
|
|
Cont ID |
|
| Sent By |
lhatten |
Date |
2001-11-30 |
Time |
15:10 |
Rev Time |
1.00 |
| Received By |
lhatten |
Date |
2001-11-30 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2001-12-05 00:00:00 | OK PER LOU HATTEN | | 2001-11-30 00:00:00 | STAIRWAY DETAILS AT REAR OF BUILDING | | | OK 11/30/2001 PER LOU HATTEN |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2001-10-18 |
|
|
Cont ID |
|
| Sent By |
lhatten |
Date |
2001-10-18 |
Time |
10:31 |
Rev Time |
2.00 |
| Received By |
lsmith |
Date |
2001-10-16 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2001-10-18 00:00:00 | REVIEW & STAMPED PLANS 10/16/2001 | | | OK PER PRELIM. MEETINGS 1ST PHASE ONLY | | | FOR 1ST FLOOR OCCUPANCY ONLY! --2ND | | | FLOOR TO REMAIN EMPTY UNTIL PLANS TO | | | CONVERT FLOOR TO CLASSROOMS AT A LATER | | | DATE! PER LOU HATTEN | | | SAME AS ABOVE 10/18/2001 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-12-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-04 |
Time |
18:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-04 |
Time |
18:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-10-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-09 |
Time |
20:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-09 |
Time |
20:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-09-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-09-24 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-09-24 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2001-09-24 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS NEED TO | | | BE SIGNED, DATED AND SEALED BY THE | | | ENGINEER OF RECORD. PER FS/FAC 471.025 | | | | | | 2)NOTE: PLEASE NOTE THAT PLANS SHOW SD`S | | | AS 120V INTERCONNECTED. PLANS ALSO SHOW | | | LV FIRE ALARM SYSTEM. PLEASE CLARIFY. | | | | | | 3)NOTE: PLEASE CLARFIY NEW/ EMERGENCY | | | LIGTHING? | | | | | | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED, | | | PLEASE NOTE THAT RATINGS WERE SUBMITTED | | | FOR PANELS BUT NOT FOR MAIN/METER PANEL. | | | PER 110-9. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-10-03 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-03 |
Time |
17:25 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-03 |
Time |
17:25 |
Sent To |
|
|
| Notes |
| 2001-10-03 00:00:00 | 1) THIS APPROVAL IS FOR THE FIRST | | | FLOOR ONLY. OCCUPANCY FOR THE SECOND | | | FLOOR WILL ONLY BE APPROVED AFTER | | | PLANS AND PERMITS ARE SUBMITTED FOR | | | THE SECOND FLOOR. THE EGRESS STAIR | | | FROM THE SECOND FLOOR WHEN PERMITTED | | | IS TO MEET ALL OF THE REQUIREMENTS FOR | | | OUTSIDE STAIRS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-09-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-09-25 |
Time |
12:09 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-09-25 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2001-09-25 00:00:00 | 1) PLEASE PROVIDE OCCUPANT LOAD | | | CLACULATIONS. | | | 2) PLEASE PROVIDE A LIFE SAFETY PLAN. | | | 3) PLEASE EXPLAIN NUMBER AND AGES OF | | | CHILDREN. PLEASE EXPLAIN HOURS OF | | | OPERATION. | | | 4) WHAT PROTECTION IS PROVIDED FOR THE | | | OPEN STAIRWAY. | | | 5) THE SPIRAL STAIR SHOWN ON PAGE A-2 | | | CANNOT BE USED TO EGRESS MORE THAN 5 | | | PERSONS. WHAT WILL THE OCCUPANT LOAD | | | FOR THIS STAIR BE. ARE THERE ANY WINDOWS | | | WITHIN 10 FEET OF THIS STAIR. | | | 6) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR REQUIRED FIRE ALARM SYSTEM. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2002-01-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-23 |
Time |
15:43 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2002-01-23 |
Time |
15:32 |
Sent To |
|
|
| Notes |
| 2002-01-23 00:00:00 | | | | PROVISO: | | | | | | REFERENCE PLAN SHEET M-2, FIRE DAMPER | | | WILL BE REQUIRED WHERE DUCT PENETRATES | | | FLOOR. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-12-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-04 |
Time |
13:24 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-12-04 |
Time |
13:24 |
Sent To |
|
|
| Notes |
| 2001-12-04 00:00:00 | | | | | | | PLEASE CLARIFY PLAN SHEEET M-3, OUTSIDE | | | AIR SCHEMATIC.FIRE DAMPERS INSTALLED | | | AT THE FIRST FLOOR CEILING, LOOKS LIKE | | | A CRAWL SPACE BETWEEN 1ST FL CEILING | | | AND THE FLOOR AT 2ND FLOOR. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-10-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-08 |
Time |
08:51 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-10-08 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2001-10-08 00:00:00 | *******************PROVISO************** | | | | | | FIRE DAMPERS REQUIRED AT EXHAUST DUCTS | | | PENETRATING FLOOR SHOULD MECH CHASE NOT | | | BE A FIRE RATED CHASE.ACCESS DOORS | | | REQUIRED FOR MAINTENANCE AND RESETTING | | | OF EACH FIRE DAMPER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-09-25 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-25 |
Time |
13:24 |
Rev Time |
1.30 |
| Received By |
pkrauss |
Date |
2001-09-25 |
Time |
12:43 |
Sent To |
|
|
| Notes |
| 2001-09-25 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | 1.PLAN INDICATES CU-1A, CU-1B, CU-2A, | | | CU-2B, AHU #1 AND #2.THE UNIT | | | SCHEDULE INDICATES TWO AHU #1 AND | | | TWO CU #1.IF SOME OF THE EQUIPMENT | | | IS EXISTING PLEASE DISTINGUISH WHAT | | | IS NEW AND WHAT MAY BE EXISTING. | | | | | | 2.DUCTS PENETRATING ONLY ONE FLOOR | | | SHALL BE PROTECTED BY EITHER A SHAFT | | | ENCLOSURE OF BY INSTALLING A LISTED | | | FIRE DAMPER WHERE FLOOR IS PIERCED | | | IN LIEU OF THE ENCLOSURE.1997 SMC | | | 610.4.PLEASE INDICATE LOCATION OF | | | FIRE DAMPERS AND ACCESS ON PLAN. | | | | | | 3.CONDENSATE LINES AND TERMINATION | | | NEEDS TO BE ADDRESSED ON PLAN. | | | NOTE, UNITS LARGER THAN 3 TON SHALL | | | TERMINATE INTO STORM DRAIN OF TO AN | | | APPROVED DRYWELL. AMENDED 1994 SPC | | | 804.3 #2 AND 3. | | | | | | 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | WITH NOTIFICATION TO ALARM/STROBE IN | | | NORMALLY OCCUPIED AREAS AS PER | | | NFPA 90A 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-10-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-12 |
Time |
10:42 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-10-12 |
Time |
10:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-09-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-26 |
Time |
15:41 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2001-09-26 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2001-09-26 00:00:00 | DENIED | | | REFERENCE SPC-94 - FACBC-97 | | | | | | 1) PLEASE NOTE THAT PLANS NEED TO BE | | | SIGNED, DATED AND SEALED BY THE ENGINEER | | | OF RECORD PER FS/FAC 471.025 | | | 2) PAGE A-1, PLEASE PROVIDE CALCULATIONS | | | FOR MINIMUM FACILITIES PER SPC-94 TABLE | | | 407. | | | 3) PAGE A-1, EXISTING BATHROOM SHOWER | | | DOES NOT MEET FACBC-97 SECTION 4.21 REQ- | | | UIREMENTS. | | | 4) PAGE A-1, COMMONS AREA, SINK TO COM- | | | PLY WITH FACBC-97 SECTION 4.24. | | | 5) PAGE A-1, WATER HEATER TO BE READILY | | | ACCESSIBLE. PROVIDE DETAILS. | | | 6) PAGE A-1, PLEASE PROVIDE SANITARY | | | RISER DIAGRAM FOR NEW HDCP BATHROOMS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-10-18 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-10-18 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
lhatten |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-18 00:00:00 | ZONING NOT NEEDED! |
|
|