Plan Review Details - Permit 01091004
Plan Review Stops For Permit 01091004
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-12-05 Cont ID  
Sent By lhatten Date 2001-12-05 Time 15:19 Rev Time 1.00
Received By lhatten Date 2001-12-05 Time 15:12 Sent To  
Notes
2001-12-05 00:00:00LETTERS ON FILLING POOL WITH DIRT ,
 SOUTHSIDE RAMP & NORTHSIDE STAIRS
 PER DETAILS OKED PER LOU HATTEN
 SAME AS BELOW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-11-30 Cont ID  
Sent By lhatten Date 2001-11-30 Time 15:10 Rev Time 1.00
Received By lhatten Date 2001-11-30 Time 13:28 Sent To  
Notes
2001-12-05 00:00:00OK PER LOU HATTEN
2001-11-30 00:00:00STAIRWAY DETAILS AT REAR OF BUILDING
 OK 11/30/2001 PER LOU HATTEN

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-10-18 Cont ID  
Sent By lhatten Date 2001-10-18 Time 10:31 Rev Time 2.00
Received By lsmith Date 2001-10-16 Time 10:26 Sent To  
Notes
2001-10-18 00:00:00REVIEW & STAMPED PLANS 10/16/2001
 OK PER PRELIM. MEETINGS 1ST PHASE ONLY
 FOR 1ST FLOOR OCCUPANCY ONLY! --2ND
 FLOOR TO REMAIN EMPTY UNTIL PLANS TO
 CONVERT FLOOR TO CLASSROOMS AT A LATER
 DATE! PER LOU HATTEN
 SAME AS ABOVE 10/18/2001

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-12-04 Cont ID  
Sent By dpalmer Date 2001-12-04 Time 18:55 Rev Time 0.00
Received By dpalmer Date 2001-12-04 Time 18:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-09 Cont ID  
Sent By dpalmer Date 2001-10-09 Time 20:19 Rev Time 0.00
Received By dpalmer Date 2001-10-09 Time 20:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-09-24 Cont ID  
Sent By dpalmer Date 2001-09-24 Time 15:45 Rev Time 0.00
Received By dpalmer Date 2001-09-24 Time 15:45 Sent To  
Notes
2001-09-24 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PLANS NEED TO
 BE SIGNED, DATED AND SEALED BY THE
 ENGINEER OF RECORD. PER FS/FAC 471.025
  
 2)NOTE: PLEASE NOTE THAT PLANS SHOW SD`S
 AS 120V INTERCONNECTED. PLANS ALSO SHOW
 LV FIRE ALARM SYSTEM. PLEASE CLARIFY.
  
 3)NOTE: PLEASE CLARFIY NEW/ EMERGENCY
 LIGTHING?
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED,
 PLEASE NOTE THAT RATINGS WERE SUBMITTED
 FOR PANELS BUT NOT FOR MAIN/METER PANEL.
 PER 110-9.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-10-03 Cont ID  
Sent By mcarsill Date 2001-10-03 Time 17:25 Rev Time 0.00
Received By mcarsill Date 2001-10-03 Time 17:25 Sent To  
Notes
2001-10-03 00:00:001) THIS APPROVAL IS FOR THE FIRST
 FLOOR ONLY. OCCUPANCY FOR THE SECOND
 FLOOR WILL ONLY BE APPROVED AFTER
 PLANS AND PERMITS ARE SUBMITTED FOR
 THE SECOND FLOOR. THE EGRESS STAIR
 FROM THE SECOND FLOOR WHEN PERMITTED
 IS TO MEET ALL OF THE REQUIREMENTS FOR
 OUTSIDE STAIRS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-09-25 Cont ID  
Sent By mcarsill Date 2001-09-25 Time 12:09 Rev Time 0.00
Received By mcarsill Date 2001-09-25 Time 12:09 Sent To  
Notes
2001-09-25 00:00:001) PLEASE PROVIDE OCCUPANT LOAD
 CLACULATIONS.
 2) PLEASE PROVIDE A LIFE SAFETY PLAN.
 3) PLEASE EXPLAIN NUMBER AND AGES OF
 CHILDREN. PLEASE EXPLAIN HOURS OF
 OPERATION.
 4) WHAT PROTECTION IS PROVIDED FOR THE
 OPEN STAIRWAY.
 5) THE SPIRAL STAIR SHOWN ON PAGE A-2
 CANNOT BE USED TO EGRESS MORE THAN 5
 PERSONS. WHAT WILL THE OCCUPANT LOAD
 FOR THIS STAIR BE. ARE THERE ANY WINDOWS
 WITHIN 10 FEET OF THIS STAIR.
 6) SEPARATE PLANS AND PERMITS REQUIRED
 FOR REQUIRED FIRE ALARM SYSTEM.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-01-23 Cont ID  
Sent By pkrauss Date 2002-01-23 Time 15:43 Rev Time 0.50
Received By pkrauss Date 2002-01-23 Time 15:32 Sent To  
Notes
2002-01-23 00:00:00 
 PROVISO:
  
 REFERENCE PLAN SHEET M-2, FIRE DAMPER
 WILL BE REQUIRED WHERE DUCT PENETRATES
 FLOOR.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-12-04 Cont ID  
Sent By pkrauss Date 2001-12-04 Time 13:24 Rev Time 0.50
Received By pkrauss Date 2001-12-04 Time 13:24 Sent To  
Notes
2001-12-04 00:00:00 
  
 PLEASE CLARIFY PLAN SHEEET M-3, OUTSIDE
 AIR SCHEMATIC.FIRE DAMPERS INSTALLED
 AT THE FIRST FLOOR CEILING, LOOKS LIKE
 A CRAWL SPACE BETWEEN 1ST FL CEILING
 AND THE FLOOR AT 2ND FLOOR.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-10-08 Cont ID  
Sent By pkrauss Date 2001-10-08 Time 08:51 Rev Time 0.35
Received By pkrauss Date 2001-10-08 Time 08:51 Sent To  
Notes
2001-10-08 00:00:00*******************PROVISO**************
  
 FIRE DAMPERS REQUIRED AT EXHAUST DUCTS
 PENETRATING FLOOR SHOULD MECH CHASE NOT
 BE A FIRE RATED CHASE.ACCESS DOORS
 REQUIRED FOR MAINTENANCE AND RESETTING
 OF EACH FIRE DAMPER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-09-25 Cont ID  
Sent By pkrauss Date 2001-09-25 Time 13:24 Rev Time 1.30
Received By pkrauss Date 2001-09-25 Time 12:43 Sent To  
Notes
2001-09-25 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.PLAN INDICATES CU-1A, CU-1B, CU-2A,
 CU-2B, AHU #1 AND #2.THE UNIT
 SCHEDULE INDICATES TWO AHU #1 AND
 TWO CU #1.IF SOME OF THE EQUIPMENT
 IS EXISTING PLEASE DISTINGUISH WHAT
 IS NEW AND WHAT MAY BE EXISTING.
  
 2.DUCTS PENETRATING ONLY ONE FLOOR
 SHALL BE PROTECTED BY EITHER A SHAFT
 ENCLOSURE OF BY INSTALLING A LISTED
 FIRE DAMPER WHERE FLOOR IS PIERCED
 IN LIEU OF THE ENCLOSURE.1997 SMC
 610.4.PLEASE INDICATE LOCATION OF
 FIRE DAMPERS AND ACCESS ON PLAN.
  
 3.CONDENSATE LINES AND TERMINATION
 NEEDS TO BE ADDRESSED ON PLAN.
 NOTE, UNITS LARGER THAN 3 TON SHALL
 TERMINATE INTO STORM DRAIN OF TO AN
 APPROVED DRYWELL. AMENDED 1994 SPC
 804.3 #2 AND 3.
  
 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS AS PER
 NFPA 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-10-12 Cont ID  
Sent By kstevens Date 2001-10-12 Time 10:42 Rev Time 0.33
Received By kstevens Date 2001-10-12 Time 10:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-09-26 Cont ID  
Sent By kstevens Date 2001-09-26 Time 15:41 Rev Time 1.25
Received By kstevens Date 2001-09-26 Time 15:41 Sent To  
Notes
2001-09-26 00:00:00DENIED
 REFERENCE SPC-94 - FACBC-97
  
 1) PLEASE NOTE THAT PLANS NEED TO BE
 SIGNED, DATED AND SEALED BY THE ENGINEER
 OF RECORD PER FS/FAC 471.025
 2) PAGE A-1, PLEASE PROVIDE CALCULATIONS
 FOR MINIMUM FACILITIES PER SPC-94 TABLE
 407.
 3) PAGE A-1, EXISTING BATHROOM SHOWER
 DOES NOT MEET FACBC-97 SECTION 4.21 REQ-
 UIREMENTS.
 4) PAGE A-1, COMMONS AREA, SINK TO COM-
 PLY WITH FACBC-97 SECTION 4.24.
 5) PAGE A-1, WATER HEATER TO BE READILY
 ACCESSIBLE. PROVIDE DETAILS.
 6) PAGE A-1, PLEASE PROVIDE SANITARY
 RISER DIAGRAM FOR NEW HDCP BATHROOMS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-10-18 Cont ID  
Sent By pschmitz Date 2001-10-18 Time 14:50 Rev Time 0.00
Received By lhatten Date   Time   Sent To  
Notes
2001-10-18 00:00:00ZONING NOT NEEDED!


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved