Plan Review Details - Permit 01090882
Plan Review Stops For Permit 01090882
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-01 Cont ID  
Sent By dpalmer Date 2001-10-01 Time 16:52 Rev Time 0.00
Received By dpalmer Date 2001-10-01 Time 16:52 Sent To  
Notes
2001-10-01 00:00:00VALUE OF PERMIT STLL NEEDS TO BE UPED
 TO VALUE OF WORK BEING DONE. 104.7.5

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-09-26 Cont ID  
Sent By dpalmer Date 2001-09-26 Time 12:44 Rev Time 0.00
Received By dpalmer Date 2001-09-26 Time 12:44 Sent To  
Notes
2001-09-26 00:00:00********* UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT NO PLANS WERE
 SUBMITTED FOR REVIEW.
  
 2)NOTE: PLEASE SHOW RISER DIAGRAM ETC.
  
  
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-10-05 Cont ID  
Sent By pkrauss Date 2001-10-05 Time 14:43 Rev Time 0.30
Received By pkrauss Date 2001-10-05 Time 14:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-09-26 Cont ID  
Sent By pkrauss Date 2001-09-26 Time 12:31 Rev Time 0.30
Received By pkrauss Date 2001-09-26 Time 12:31 Sent To  
Notes
2001-09-26 00:00:00********************DENIED**************
  
  
 PLEASE PROVIDE MAKE, MODEL AND BTU'S
 FOREQUIPMENT.
  
 AS PER FLORIDA ENERGY CODE SECTION
 101.4.1.1, ENERGY CALCULATIONS AS PER
 CHAPTER6 SECTION 607.1.ABC.1, EQUIPMENT
 SIZING CLCULATION SHALL BE PERFORMED ON
 THE BUILDING AND SHALL BE ATTACHED TO
 FORM 600 SUBMITTED WITH APPLICATION.
 COOLING & HEATING DESIGN LOADS, FOR THE
 PURPOSE OF SIZING HVAC SYSTEMS, SHALL
 BE DETERMINED FOR EACH ZONE WITHIN A
 DWELLING IN ACCORDANCE WIHHT ACCA
 MANUAL J.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS 659-8096 EXT. 8388.