Plan Review Details - Permit 01090761
Plan Review Stops For Permit 01090761
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-11-13 Cont ID  
Sent By dpalmer Date 2001-11-13 Time 16:39 Rev Time 0.00
Received By dpalmer Date 2001-11-13 Time 16:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-10-30 Cont ID  
Sent By dpalmer Date 2001-10-30 Time 21:29 Rev Time 0.00
Received By dpalmer Date 2001-10-30 Time 21:29 Sent To  
Notes
2001-10-30 00:00:00**************** UNSAT*****************
  
 1)NOTE: PLEASE NOTE #1 FROM FIRST
 REVIEW,3-2/0`S FOR SINGLE PHASE
 SERVICE?PLEASE NOTE PLANS STILL SHOW A
 #1 CONDUCTOR? FOR ?
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3)NOTE: PLEASE NOTETHAT PLANS THAT
 ARE BACK IN MUST BE SIGNED,DATED AND
 SEALED BY THE ENGINEER OF RECORD.
 471.025 OF
 THE FS/FAC
  
 4) NOTE: PLEASE SHOW GROUNDING
 ELECTRODE GOING TO BUILDING STEEL AND
 COLD WATER PER 250-50.
  
 PLEASE NOTE :IS COLD WATER METAL? CPVC?
 PLEASE NOTE PER 250-50 .
  
 PLEASE NOTE MOST NOTES FROM FIRST
 REVIEW WERE ADDRESSED BUT STILL NEEDS
 SOME OTHERS DONE.
 PLEASE SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-09-28 Cont ID  
Sent By dpalmer Date 2001-09-28 Time 16:20 Rev Time 0.00
Received By dpalmer Date 2001-09-28 Time 16:20 Sent To  
Notes
2001-09-28 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE NOTE SERVICE ENTRANCE
 CONDUCTORS? PLEASE NOTE 3-2/0`S AND 1,#1
 PLEASE CALRIFY?
  
 2)NOTE: PLEASE INDICATE200A MAIN PANEL
 AS MCB. SHOWN AS MLO
  
 3)NOTE: PLEASE INCLUDE CWP WITH GROUND-
 -ING ELECTRODE SYSTEM (IF METAL) 250-50
  
 4)NOTE: PLEASE NOTEGARAGE OUTLET TO BE
 SHOWN AS GFI.210-8
  
 5)NOTE:PLEASENOTE THAT ALL BATH OUTLET
 -S ARE ALSO TO BE SHOWN AS GFI/GFI
 PROTECTED PER 210-8
  
 6)NOTE: PLEASE NOTE THAT PANEL SCHEDULES
 SHOW MOETHAN ONE AHU AND CU FOR A/C??
 BUT LOAD CALCULATIONS ONLY SHOW ONE FOR
 HEAT AND PLANS ONLY SHOW ONE CU AND NO
 AHU`S??? PLEASE SHOW ALL AHU`S AND LIGHT
 -S AND RECEPTS IN ATTIC.210-70,210-63
 440-11.
  
 7) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 8)NOTE: PLEASE NOTE CLEARENCES FOR A/C
 CU`S PER 110-26
  
 9)NOTE: PLEASE NOTE THAT LAUNDRY CIRCUIT
 IS SHOWN AT 1200 AND DISHWASHER AT 1500
 THESE COULD BE A MISPRINT AND NEED TO
 BE SWAPPED PER 210-11-C-2
  
 10)NOTE: PLEASE NOTE MISSING OUTLET FOR
 BATH OFF BEDROOM #4, PER 210-52D
  
 11)NOTE: PLEASE NOTE MISSING OUTLET IN
 BEDROOM #4 210-52
  
 12)NOTE: PLEASE NOTE THAT MAIN SHOWN IN
 200A PANEL IS SHOWN AS 180AMPS?? PLEASE
 NOTE THAT THIS NEEDS TO CORRELATE WITH
 ART; 240-6
  
 13)PLEASE NOTE THAT SD FOR MASTER NEEDS
 TO BE MOVED INTO MASTER BEDROOM.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-01-28 Cont ID  
Sent By pkrauss Date 2002-01-28 Time 15:15 Rev Time 0.40
Received By pkrauss Date   Time   Sent To  
Notes
2002-01-28 00:00:00MECH REV 02010559

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-09-26 Cont ID  
Sent By hmoser Date 2001-09-26 Time 18:05 Rev Time 0.50
Received By hmoser Date 2001-09-26 Time 18:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-05-08 Cont ID  
Sent By kstevens Date 2002-05-08 Time 14:27 Rev Time 0.00
Received By kstevens Date 2002-05-08 Time 14:27 Sent To  
Notes
2002-05-08 00:00:00REVISION OK - SINK ADDED TO SANT RISER.

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-05-02 Cont ID  
Sent By kstevens Date 2002-05-02 Time 18:24 Rev Time 0.00
Received By kstevens Date 2002-05-02 Time 18:24 Sent To  
Notes
2002-05-02 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) SHT 5A SANITARY RISER DIAGRAM DOES
 NOT REFLECT FLOOR PLAN. "ODK" SHOULD BE
 TAKEN OFF BY POOL BATH AS ON FLOOR PLAN,
 NOT BY THE WASH MACHINE/LAUNDRY SINK AS
 SHOWN.
 2) WHAT IS "ODK" ?- WHAT IS "SW" LOOP
 BY DRAIN ADDED ON REVISION?
 3) SHT 5A BATH #3 SHOWER. ALL SHOWER
 COMPARTMENTS SHALL HAVE A MINIMUM OF 900
 SQUARE INCHES OF INTERIOR CROSS-SECTION-
 AL AREA. SHOWER COMPARTMENTS SHALL NOT
 BE LESS THAN 30 INCHES IN MINIMUM DIMEN-
 SION MEASURED FROM THE FINISHED INTERIOR
 DIMENSION OF THE COMPARTMENT.THE MINIMUM
 DIMENSION SHALL BE MEASURED AS THE SIDE
 OF A RECTANGLE, ALTITUDE OF A TRIANGLE,
 OR DIAMETER OF A CIRCLE.
  
 `EVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-10-29 Cont ID  
Sent By kstevens Date 2001-10-26 Time 19:20 Rev Time 0.33
Received By kstevens Date 2001-10-26 Time 19:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-09-25 Cont ID  
Sent By jleech Date 2001-09-25 Time 18:07 Rev Time 0.33
Received By jleech Date 2001-09-25 Time 18:07 Sent To  
Notes
2001-09-25 00:00:00DENIED;
 RISER DIAGRAM DOES NOT REFLECT FLOOR
 PLAN ON SECOND FLOOR. FLOOR PLAN SHOWS
 A FULL BATHROOM, RISER DIA SHOWS 1/2
 BATH.
 MASTER BATHROOM LAV. AND SHOWER ARE
 UNVENTED.

Review Stop R ROOF PLAN REVIEW
Rev No 6 Status P Date 2002-05-15 Cont ID  
Sent By jgomez Date 2002-05-15 Time 13:29 Rev Time 0.25
Received By jgomez Date 2002-05-15 Time 13:29 Sent To  
Notes
2002-05-15 00:00:00TRUSS DRAWINGS REVIEW.

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status F Date 2002-05-14 Cont ID  
Sent By jgomez Date 2002-05-14 Time 13:53 Rev Time 0.25
Received By jgomez Date 2002-05-14 Time 13:53 Sent To  
Notes
2002-05-14 00:00:001-REVISED TRUSS DRAWINGS WERE NOT
 REVIEWED BY ENGINEER OF RECORD AS
 REQUIRED BY CHAPTER 471 OF FLORIDA
 STATUTES. USE STANDARD REVIEW STAMP
 OR OTHER ACCEPTABLE METHOD THAT
 IDENTIFIES THE ENGINEER OF RECORD WHO
 DESIGNED THE BUILDING AND REVIEWED
 THE TRUSSES.
 2-PROVIDE TWO SETS OF TRUSSES AND TRUSS
 LAYOUTS. AT LEAST ONE OF THEM TO BE
 ORIGINAL WITH SEALS AND SIGNATURES FOR
 PUBLIC RECORDS AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTES.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2002-05-10 Cont ID  
Sent By jgomez Date 2002-05-10 Time 13:35 Rev Time 0.50
Received By jgomez Date 2002-05-10 Time 13:35 Sent To  
Notes
2002-05-10 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-TRUSS LAYOUT TO HAVE ENGINEER'S
 ORIGINAL SIGNATURE AS REQUIRED BY
 CHAPTER 471 OF FLORIDA STATUTES.
 **ALSO, ENGINEER TO INCLUDE ALL HIS
 INFORMATION AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTES.
 2-ENGINEERED TRUSSES:
 A)ENGINEER TO HAVE ORIGINAL SIGNATURE,
 EMBOSSED SEAL AND DATE AS REQUIRED BY
 CHAPTER 471 OF FLORIDA STATUTES.
 B)ENGINEERED TRUSS TO HAVE SPECIFIC
 YEAR OF THE CODE USED FOR DESIGN.
 C)ENGINEER TO SIGN, SEAL AND DATE LETTER
 FOR LATERAL BRACING AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.
 D)REVISE/UPDATE ALL GENERAL TRUSS
 DETAILS. USE SBC (WITH SPECIFIC YEAR)
 FOR 110MPH OR ASCE 7-95 FOR 140MPH,
 NOT ASCE 7-93 FOR 110MPH.(SEE PACKAGE)
 E)ENGINEER TO SIGN, SEAL AND DATE ALL
 GENERAL TRUSS DETAILS AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.
 **NOTE: COPY OF GENERAL TRUSS DETAILS
 HAS THE SEAL OF ANOTHER ENGINEER.
 CLARIFY WHO IS RESPONSIBLE FOR THE
 DESIGN AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES.
 SEE COMMENTS ON GENERAL TRUSS DETAILS.
 3-ENGINEER OF RECORD TO REVIEW ALL
 TRUSS DRAWINGS AFTER CORRECTIONS ARE
 DONE TO THEM. USE STANDARD REVIEW
 STAMP OR ACCEPTABLE METHOD IDENTIFYING
 ENGINEER WHO REVIEW THE TRUSSES AS
 REQUIRED BY CHAPTER 471 FL. STATUTES.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2002-05-01 Cont ID  
Sent By jgomez Date 2002-05-01 Time 16:44 Rev Time 0.50
Received By jgomez Date 2002-05-01 Time 16:44 Sent To  
Notes
2002-05-01 00:00:00CHECKLIST:
 1-DRAWINGS STILL SHOW ENTRY DOOR TO BE
 2880. THIS DOOR SIZE DOESN'T COMPLY
 WITH TABLE 1004 SBC 1997. NEED 32"MIN.
 CLEAR OPENING.
 2-ALL PRODUCT APPROVAL INFORMATION
 REQUESTED ON PROVISO DATED 11-06-01
 WAS NEVER SUBMITTED. NEED ALL PRODUCT
 APPROVALS FOR ALL TYPES OF DOORS AND
 WINDOWS TO BE INSTALLED. INCLUDING
 PREODUCT APPROVAL FOR GARAGE DOORS.
 3-ENGINEERED TRUSS DRAWINGS WERE NEVER
 SUBMITTED TO THIS OFFICE.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-11-06 Cont ID  
Sent By jgomez Date 2001-11-06 Time 08:38 Rev Time 3.50
Received By jgomez Date 2001-11-06 Time 08:37 Sent To  
Notes
2001-11-05 00:00:00APPROVED WITH PROVISO:
 1-ENTRY DOOR TO HAVE 32" MINIMUM CLEAR
 OPENING AS REQUIRED BY TABLE 1004 OF
 SBC 1997.
 -NOTE: 2880 DOOR DOESN'T HAVE THE 32".
 REVISE AND INSTALL SIZE AS REQUIRED.
 2-PRODUCT APPROVALS:
 A)NORANDEX PRODUCT APPROVALS: ENGINEER
 OF RECORD TO PROVIDE HIS INFORMATION
 AND DATE AS REQUIRED BY CHAPTER 471 OF
 FLORIDA STATUTES.
 -ALSO, BE SPECIFIC ON JOB/SITE LOCATION
 B)WINDOW SILL ENGINEERED CALCULATIONS TO
 BE SIGNED, SEALED AND DATED AS REQ'D
 BY CHAPTER 471 OF FLORIDA STATUTES
 WHEN SUBMITTING INFORMATION FOR PUBLIC
 RECORDS.
 C)SINCE GARAGE DOORS ARE IN THE PROCESS
 OF GETTING THE PRODUCT APPROVAL, THEN,
 RESPONSIBLE ENGINEER TO SIGN, SEAL &
 DATE ALL INFORMATION SUBMITTED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-10-05 Cont ID  
Sent By jgomez Date 2001-10-05 Time 16:13 Rev Time 3.50
Received By jgomez Date 2001-10-06 Time 11:59 Sent To  
Notes
2001-10-05 00:00:00CHECKLIST:
 1-PROVIDE COMPLETE DETAIL/SECTION THRU
 STAIRWAY. SECTION 104.2.2OF CITY
 AMENDMENTS TO SBC 1997.
 2-PROVIDE ATTIC ACCESS.SEC 2309.6 SBC/97
 3-ENTRY DOOR TO HAVE 32" MIN. CLEAR
 OPENING. TABLE 1004 SBC 1997.
 4-SPECIFY FIREBLOCKING WHERE REQUIRED BY
 SEC. 2305 SBC/97.ALSO, SEE WALL SECT'N
 5-TRUSS COMPANY IS NOT LISTED IN THE
 PREFABRICATED WOOD COMPONENTS/TRUSS
 COMPLIANCE REPORT REPORTED TO THE
 BUILDING CODE ADVISORY BOARD OF PALM
 BEACH COUNTY. THEREFORE, TRUSSES WILL
 NOT BE APPROVED IN THIS COUNTY.
 6-REVISE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM. THE
 MEAN ROOF HEIGHT IS +/- 19'-0". THE
 MEAN ROOF HEIGHT IS TAKEN FROM THE
 FINISH GRADE, NOT FINISH FLOOR, TO THE
 AVERAGE POINT OF THE HIGHEST ROOF.
 7-SOIL TEST REPORT TO HAVE ENGINEER'S
 ORIGINAL SIGNATURE AS REQUIRED BY FL.
 STATUTES CHAPTER 471 WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS.
 8-REVISE ENERGY CALCULATIONS SEE
 COMMENTS ON FIRST PAGE OF FORM 600A-97
 9-PROVIDE CURRENT SBCCI OR DADE COUNTY
 PRODUCT APPROVALS FOR:
 A)EXTERIOR DOORS AND WINDOWS. IF USING
 NORANDEX PRODUCTS, THEN THEY MUST BE
 SITE SPECIFIC AND SIGNED, SEALED AND
 DATED BY THE MANUFACTURER'S ENGINEER
 AND BY THE ENGINEER OF RECORD FOR THIS
 HOUSE.
 -CLEARLY INDICATE ON DRAWINGS THE
 FASTENERS TO BE USED FOR EACH WINDOW
 AND DOOR COMPLETE ASSEMBLY AS SHOWN ON
 ARCHITECTURAL PLANS ACCORDING TO THE
 DESIGN PRESSURES CALCULATED FOR THIS
 PROJECT.
 -SLIDING GLASS DOORS DON'T SHOW TEST
 PERFORMED AS PER ASTM E-330.
 B)WINDOW SILL ACTUAL PRODUCT APPROVAL.
 C)PRECAST LINTEL PRODUCT APPROVAL WAS
 DELETED BY SBCCI. NEED UPDATED ONE.
 D)GARAGE DOORS PRODUCT APPROVAL WAS
 DELETED BY SBCCI.
 E)ENTRY DOORS WITH SIDELITES AND TRANSOM
 ABOVE COMPLETE ASSEMBLY AS SHOWN ON
 ARCHITECTURAL PLANS.
  
 10-PROVIDE COMPLETE INFORMATION FOR
 STORM PANELS:
 -NEED KEY PLAN & COMPLETE INSTALLATION
 SCHEDULE, SEE CITY SAMPLE ATTACHED.
 -CLEARLY INDICATE ON STORM PANELS DWGS
 SPECIFIC MOUNTING CONDITIONS & ANCHORS
 TO BE USED ACCORDING TO THE MEAN ROOF
 HEIGHT, DESIGN PRESSURES, PANEL SPAN,
 EDGE DISTANCE, CONNECTION TYPE AND
 STRUCTURE TO BE ATTACHED TO (MASONRY
 OR WOOD).
 11-PROVIDE SURVEY OR SITE PLAN SHOWING
 THE LAYOUT OF THE DRIVEWAY AND WALKWAY
 12-CONTRACTOR NEEDS TO UPDATE INSURANCE
 AND WORKER'S COMPENSATION.
 13-OWES $602.77 FOR UPDATED CONSTRUCTION
 VALUE AND RADON FEES. PLEASE PAY
 ATTACHED RECEIPT.
 14-SEE ADDITIONAL COMMENTS ON PLANS,
 INCLUDING COMMENTS BY OTHER TRADES.
 PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO THE ORIGINAL
 PLANS IN ORDER TO EXPEDITE THE REVIEW
 PROCESS.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-09-21 Cont ID  
Sent By sgraham Date 2001-09-21 Time 06:45 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***