Plan Review Details - Permit 01090539
Plan Review Stops For Permit 01090539
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-10-03 Cont ID  
Sent By dpalmer Date 2001-10-03 Time 22:48 Rev Time 0.00
Received By dpalmer Date 2001-10-03 Time 22:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-01-04 Cont ID  
Sent By pkrauss Date 2002-01-04 Time 14:08 Rev Time 0.35
Received By pkrauss Date 2002-01-04 Time 14:08 Sent To  
Notes
2002-01-04 00:00:00MECH REV PERMIT 01110863

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-11-28 Cont ID  
Sent By pkrauss Date 2001-11-28 Time 11:04 Rev Time 0.45
Received By pkrauss Date 2001-11-28 Time 11:04 Sent To  
Notes
2001-11-28 00:00:00THIS IS NOT A REVISION -
 CHANGE OF CONTRACTOR REQUIRED.
 NEW MECH PERMIT 01110863

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-09-29 Cont ID  
Sent By tmoore Date 2001-09-29 Time 10:37 Rev Time 0.33
Received By rmcdouga Date 2001-09-29 Time 10:37 Sent To  
Notes
2001-10-19 00:00:00OK PER H MOSER 9-29-01

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-09-26 Cont ID  
Sent By kstevens Date 2001-09-26 Time 19:06 Rev Time 0.33
Received By kstevens Date 2001-09-26 Time 19:06 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-10-19 Cont ID  
Sent By rmcdouga Date 2001-10-19 Time 15:54 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-10-09 Cont ID  
Sent By rmcdouga Date 2001-10-09 Time 09:35 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-10-09 00:00:00*************BUILDING UNSAT*************
  
 1) THE ENERGY FORM INCORRECTLY LISTS THE
 EXTERIOR WALL TYPE AS WOOD FRAME WITH AN
 R VALUE OF 3.0. THE EXTERIOR WALLS ARE
 ACTUALLY CONCRETE BLOCK. PLEASE CORRECT.
  
 2) THE ROOF SHEATHING AT GABLE ENDS IS
 REQUIRED TO BE NAILED WITH 8D COMMON
 NAILS AT 4" O.C. AT THE EDGES AND 6"O.C.
 INTERMEDIATE WITHIN 5' OF THE ROOF EDGE
 INCLUDING OVERHANG. SEC.2306 CITY OF
 W.P.B. AMENDMENTS TO THE 97 S.B.C.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-09-24 Cont ID  
Sent By sgraham Date 2001-09-24 Time 12:38 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***