Plan Review Details - Permit 01090497
Plan Review Stops For Permit 01090497
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-10-16 Cont ID  
Sent By mamini Date 2001-10-16 Time 09:45 Rev Time 3.00
Received By mamini Date 2001-10-16 Time 09:44 Sent To  
Notes
2001-10-16 00:00:00PASSED:
 1. RESPONSES TO THE PREVIOUS REVIEW
 COMMENTS DATED 8-08-01 SATISFACTORY AND
 REVIEW COMMENTS IMPLEMENTED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-09-18 Cont ID  
Sent By mamini Date 2001-09-18 Time 15:30 Rev Time 5.00
Received By mamini Date 2001-09-18 Time 15:29 Sent To  
Notes
2001-09-18 00:00:00FAILED:
 1. PLEASE PROVIDE STORM WATER CALC..
 2. PLEASE PROVIDE PERVIOUS & IMPERVIOUS
 CALC..
 3. PLEASE PROVIDE R.W GATE VALVE AT
 EVERY 1000' TO 1200' MAX.
 4. R.W GATE VALVE FOR HYDRANT CONNECTION
 SHOULD BE INSTALLED AT 4' MAX. FROM
 C/L OF HYDRANT, SEE STANDARD DETAILS.
 4. PLEASE VERIFY, M.H # 413, 414 ARE
 DROP M.H??
 5. PLEASE SHOW BACKFLOW PREVENTERS FOR
 THE LIFT STATIONS.
 6. PLEASE SHOW ALL DIP SECTIONS @
 CONFLICT CROSSING ON SANITARY SEWER
 PROFILE.
 7. PLEASE PROVIDE POLLUTION PREVENTION
 PLAN, PLAN MUST BE INSTALLED IN FIELD
 PRIOR TO ANY CONSTRUCTION.
 8. PLEASE PROVIDE SIGNING AND MARKING
 PLANS.
 9. NOTE NO. 7 IN GENERAL NOTES, SHEET
 2 OF 7 REFERS TO 1982 SPECS., PLEASE
 REVISE TO LATEST.
 10. INSTALLATION OF LIFT STATIONS AND
 CONNECTIONS TO WATER, SEWER MAIN MUST BE
 COORDINATED AND APPROVED BY PUBLIC
 UTILITIES ENGINEERING SERVICES
 DEPARTMENTS.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-10-16 Cont ID  
Sent By mcarsill Date 2001-10-16 Time 10:52 Rev Time 0.00
Received By mcarsill Date 2001-10-16 Time 10:52 Sent To  
Notes
2001-10-16 00:00:00VALVES FOR FIRE HYDRANTS ARE NOT TO
 EXCEED FOUR FEET FROM HYDRANTS. PLEASE
 SEE DETAIL ON PAGE 7 OF 14.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-09-20 Cont ID  
Sent By mcarsill Date 2001-09-20 Time 12:45 Rev Time 0.00
Received By mcarsill Date 2001-09-20 Time 12:45 Sent To  
Notes
2001-09-20 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING AND AFTER CONSTRUCTION.
 2) VALVES FOR FIRE HYDRANTS SHALL NOT
 EXCEED 4 FEET FROM THE FIRE HYDRANTS
 AS SHOWN ON THE DETAIL DRAWINGS.
 3) IS THERE ONLY ONE PLANNED INGRESS
 AND EGRESS ROAD TO THE REAR OF THE
 PROPERTY.
 4) UNDERGOUND FIRE LINES AND
 FIRE HYDRANTS ARE TO MEET UTILITY AND
 FIRE RESCUE REQUIREMENTS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910