Plan Review Details - Permit 01090497
| Plan Review Stops For Permit 01090497 |
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2001-10-16 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-10-16 |
Time |
09:45 |
Rev Time |
3.00 |
| Received By |
mamini |
Date |
2001-10-16 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2001-10-16 00:00:00 | PASSED: | | | 1. RESPONSES TO THE PREVIOUS REVIEW | | | COMMENTS DATED 8-08-01 SATISFACTORY AND | | | REVIEW COMMENTS IMPLEMENTED. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2001-09-18 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-09-18 |
Time |
15:30 |
Rev Time |
5.00 |
| Received By |
mamini |
Date |
2001-09-18 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2001-09-18 00:00:00 | FAILED: | | | 1. PLEASE PROVIDE STORM WATER CALC.. | | | 2. PLEASE PROVIDE PERVIOUS & IMPERVIOUS | | | CALC.. | | | 3. PLEASE PROVIDE R.W GATE VALVE AT | | | EVERY 1000' TO 1200' MAX. | | | 4. R.W GATE VALVE FOR HYDRANT CONNECTION | | | SHOULD BE INSTALLED AT 4' MAX. FROM | | | C/L OF HYDRANT, SEE STANDARD DETAILS. | | | 4. PLEASE VERIFY, M.H # 413, 414 ARE | | | DROP M.H?? | | | 5. PLEASE SHOW BACKFLOW PREVENTERS FOR | | | THE LIFT STATIONS. | | | 6. PLEASE SHOW ALL DIP SECTIONS @ | | | CONFLICT CROSSING ON SANITARY SEWER | | | PROFILE. | | | 7. PLEASE PROVIDE POLLUTION PREVENTION | | | PLAN, PLAN MUST BE INSTALLED IN FIELD | | | PRIOR TO ANY CONSTRUCTION. | | | 8. PLEASE PROVIDE SIGNING AND MARKING | | | PLANS. | | | 9. NOTE NO. 7 IN GENERAL NOTES, SHEET | | | 2 OF 7 REFERS TO 1982 SPECS., PLEASE | | | REVISE TO LATEST. | | | 10. INSTALLATION OF LIFT STATIONS AND | | | CONNECTIONS TO WATER, SEWER MAIN MUST BE | | | COORDINATED AND APPROVED BY PUBLIC | | | UTILITIES ENGINEERING SERVICES | | | DEPARTMENTS. | | | | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-10-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-16 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-16 |
Time |
10:52 |
Sent To |
|
|
| Notes |
| 2001-10-16 00:00:00 | VALVES FOR FIRE HYDRANTS ARE NOT TO | | | EXCEED FOUR FEET FROM HYDRANTS. PLEASE | | | SEE DETAIL ON PAGE 7 OF 14. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-09-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-09-20 |
Time |
12:45 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-09-20 |
Time |
12:45 |
Sent To |
|
|
| Notes |
| 2001-09-20 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | | TO,DURING AND AFTER CONSTRUCTION. | | | 2) VALVES FOR FIRE HYDRANTS SHALL NOT | | | EXCEED 4 FEET FROM THE FIRE HYDRANTS | | | AS SHOWN ON THE DETAIL DRAWINGS. | | | 3) IS THERE ONLY ONE PLANNED INGRESS | | | AND EGRESS ROAD TO THE REAR OF THE | | | PROPERTY. | | | 4) UNDERGOUND FIRE LINES AND | | | FIRE HYDRANTS ARE TO MEET UTILITY AND | | | FIRE RESCUE REQUIREMENTS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|