Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-10-03 Cont ID  
Sent By mcarsill Date 2001-10-03 Time 15:36 Rev Time 0.00
Received By mcarsill Date 2001-10-03 Time 15:36 Sent To  
Notes
2001-10-03 00:00:001) PLEASE DELETE "WALK DOWN TO YOUR
 ASSIGNED RE-ENTRY FLOOR" FROM ALARM
 NOTIFICATION OPERATION MESSAGE.
 2) EXISTING SINGLE STATION SMOKE
 DETECTORS ARE TO REMAIN IN THE SLEEPING
 ROOMS, SINCE A COMPLETE SMOKE DETECTION
 SYSTEM WILL NOT BE PROVIDED.
 3) RECALL OF ELEVATORS NOT NECESSARY ON
 ALL INITIATING DEVICES, THE ELEVATOR
 LOBBY SMOKE DETECTOR CAN BE THE ONLY
 DEVICE TO RECALL THE ELEVATORS.
  
 CAPTAIN MIKE CARSILLO
 659-8096 EXT. 8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-09-17 Cont ID  
Sent By mcarsill Date 2001-09-17 Time 09:10 Rev Time 0.00
Received By mcarsill Date 2001-09-17 Time 09:10 Sent To  
Notes
2001-09-17 00:00:001) OPERATIONAL MATRIX DOES NOT INDICATE
 THAT ALL INITIATING DEVICES WILL SOUND
 THE FIRE ALARM SYSTEM EVACUATION
 FEATURE OF THE FIRE ALARM SYSTEM. PLEASE
 CORRECT OPERATIONAL MATRIX.
 2) OPERATIONAL MATRIX INDICATES THE
 UNLOCKING OF DOORS. WHAT DOORS ARE
 LOCKED.
 3) ELEVATOR EQUIPMENT ROOM M1-47 DOES
 NOT HAVE A HEAT DETECTOR SHOWN.
 4) PLEASE INDICATE ON THE PLANS WHAT
 THE EVACUATION MESSAGE WILL STATE.
 5) PLEASE NOTE ON THE PLANS WHAT
 DEVICES WILL ACTIVATE THE STAIRWELL
 PRESSURIZATION FANS.
 6) PLEASE BE ADVISED THAT SINGLE STATION
 SMOKE DETECTORS ARE REQUIRED IN
 EACH SLEEPING ROOM.
 7) PLEASE INDICATE ON THE PLANS THAT
 SMOKE DETECTORS WILL BE INSTALLED A
 MINIMUM OF THREE FEET FROM HVAC
 DIFFUSERS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910