Plan Review Details - Permit 01090466
Plan Review Stops For Permit 01090466
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-10-22 Cont ID  
Sent By jwitmer Date 2001-10-22 Time 15:01 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-09-28 Cont ID  
Sent By jwitmer Date 2001-09-28 Time 13:06 Rev Time 1.22
Received By jwitmer Date 2001-09-28 Time 13:06 Sent To  
Notes
2001-09-28 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01090466
 1801 PALM BEACH LAKES # 198
 HMD ENTERPRISES INC.
 (407) 805-0809
  
 1)-SBC 413.8 COVERED MALLS, REQUIRE
 FIRE SPRINKLERS, THE EXISTING ROOMS ARE
 MISSING THE SPRINKLER LOCATIONS.
  
 2)- 413.7 OCCUPANCY SEPERATION, THE PLAN
 DOES NOT INDICATE THE TYPE OF OCCUPANCY
 ON EITHER SIDE? 413.7.2 1 HR SEPERATION
 BETWEEN DIFFERENT OCCUPANCIES.
  
 3)- SBC TABLE 803.3 MINIMUM INTERIOR
 FINISH CLASSIFICATION NOT GIVEN
  
 4)- FL ACCESSIBILITY CODE 4.5.1 FLOOR
 SURFACES ALONG ACCESSIBLE ROUTE & IN
 ACCESSIBLE ROOMS AND SPACES INCLUDING
 FLOORS, WALKS, RAMPS, & STAIRS.A STATIC
 COEFFICIENT OF 0.6 IS RECOMMENDED FOR
 ACCESSIBLE ROUTES & 0.8 FOR RAMPS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-22 Cont ID  
Sent By dpalmer Date 2001-10-22 Time 22:26 Rev Time 0.00
Received By dpalmer Date 2001-10-22 Time 22:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-09-19 Cont ID  
Sent By dpalmer Date 2001-09-19 Time 22:48 Rev Time 0.00
Received By dpalmer Date 2001-09-19 Time 22:48 Sent To  
Notes
2001-09-19 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANS THAT CORRELATE WITH A
 SUBMITTED PANEL SCHEDULE.
  
 2)NOTE: PLEASE CALRIFY EXSITING/NEW
 SHOW WINDOW OUTLET(S) PER 210-62
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-10-22 Cont ID  
Sent By jwitmer Date 2001-10-22 Time 15:00 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-10-22 00:00:00FIRE OK PER MEC 10/18/01 SEE PLAN &
 RESUB SHEETJW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-09-18 Cont ID  
Sent By mcarsill Date 2001-09-18 Time 09:14 Rev Time 0.00
Received By mcarsill Date 2001-09-18 Time 09:14 Sent To  
Notes
2001-09-18 00:00:001) REMODELING REFLECTED CEILING PLAN
 DISPLAYS NO FIRE SPRINKLER HEADS IN
 REAR ROOM. PLEASE SHOW EXISTING
 SPRINKLER HEADS IN REAR ROOM.
 2) PLEASE INDICATE INTERIOR FINISH
 INFORMATION FOR WALLS AND CEILINGS.
 3) PLEASE INDICATE LOCATIONS OF FIRE
 EXTINGUISHERS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-11-19 Cont ID  
Sent By pkrauss Date 2001-11-19 Time 13:55 Rev Time 0.45
Received By pkrauss Date 2001-11-19 Time 13:55 Sent To  
Notes
2001-11-19 00:00:00 
  
 NO MAKE-UP AIR INDICATED ON PLAN FOR
 THE RESTROOM OR OFFICE AREA.PLEASE
 SUBMIT REVISED PLAN INDICATING DUCT
 SIZE, GRILL SIZE AND CFM DISTRIBUTION
 TO THESE AREAS.
  
 PLEASE PROVIDE INFORMATION OF EXISTING
 RTU (TONNAGE & O.A.).AIR BALANCE
 SCHEDULE INDICATES 1050 CFM SUPPLY AIR
 AND PLAN INDICATES 2200 CFM BEING
 DISTRIBUTED.
  
 PROVISO -
  
 1.NO COMBUSTIBLES ABOVE THE CEILING IN
 THE RETURN AIR PLENUM.
 1997 SMC 609.1.1.
  
 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-10-31 Cont ID  
Sent By pkrauss Date 2001-10-31 Time 08:20 Rev Time 0.50
Received By pkrauss Date 2001-10-31 Time 07:50 Sent To  
Notes
2001-10-31 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89.
  
 SHOW COMPLIANCE WITH ASHRAE 62-1989
 SECTION 5.7, CONTAMINANTS FROM
 STATIONARY LOCAL SOURCES WITHIN THE
 SPACE SHALL BE CONTROLLED BY COLLECTION
 AND REMOVAL AS CLOSE TO THE SOURCE AS
 PRACTICABLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-09-28 Cont ID  
Sent By pkrauss Date 2001-09-28 Time 14:25 Rev Time 0.30
Received By pkrauss Date 2001-09-28 Time 14:24 Sent To  
Notes
2001-09-28 00:00:00 
  
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-11-09 Cont ID  
Sent By pschmitz Date 2001-11-09 Time 18:52 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-11-09 00:00:00PROVISO, FOR FLR SINKS ADDRESSED IN
 NOTES SHOWN AS FLR DRAINS ON PLANS.
 END OF COMENTSPAUL SCHMITZX 8233

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-10-28 Cont ID  
Sent By pschmitz Date 2001-10-28 Time 06:44 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-10-28 00:00:00PLUMBING PLAN REVIEW,DENIED
 (1) SHT-2 PUBLIC REST RM IN STORAGE
 AREA.
 STD PLBG. CODE-94, SEC 407.2.2 REQUIRED
 FACILITIES SHALL BE DIRECTLY ACCESSIBLE
 TO THE PUBLIC THRU DIRECT OPENINGS OR
 CORRIDORS FROM THE AREA THEY ARE
 INTENDED TO SERVE.
 (2A) SHT-MEP-1 2" PIPE RECEPTOR, ALL
 INDIRECT WASTE SHALL TERMINATE TO A
 FLOOR SINK, SEC 802.
 (2B) PEDICURE UNIT, WATER SUPPLY TO BE
 PROTECTED WITH A APPROVED BACK FLOW
 PREVENTER SEC 606.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-01 Cont ID  
Sent By jleech Date 2001-10-01 Time 08:27 Rev Time 2.00
Received By jleech Date 2001-10-01 Time 08:27 Sent To  
Notes
2001-10-01 00:00:00DENIED;
 1.WATER HEATER SHALL BE READILY
 ACCESSIBLE. INSTALL ON FLOOR OR
 INSTALL A SHIPS LADDER.
 2.T & P LINE TO DRAIN TO A FLOOR SINK
 WITH A TRAP PRIMER.
 3.SHOW COMPLIANCE TO TABLE 407, MINIMUM
 PLUMBING FIXTURES.
 4.WATER DIAGRAM, PLEASE SIZE .
 5.WATER HAMMER ARRESTORS SHALL BE
 INSTALLED PER MANUFACTORS INSTRUCTIONS
 6.H/C BATHROOM;
 A.DOOR NOT PERMITED TO SWING INTO
 CLEAR FLOOR SPACE OF LAV. FACBC
 SEC. 4.19.3.
 B.SHOW GRAB BARS ON FLOOR PLAN.
 C.REVISE NOTE ABOVE H/C BATH DRAWING
 HOT WATER LINES AND TRAP WILL BE
 INSULATED PER 4.19.4 TEMP. NOT IN
 HANDICAP CODE.
 7.SANITARY DIAGRAM NOT CORRECT. LAVITORY
 NEXT TO PEDICURE SINK IS NOT SHOWN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved