Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-10-22 Cont ID  
Sent By jwitmer Date 2001-10-22 Time 16:02 Rev Time 1.50
Received By jwitmer Date 2001-10-22 Time 16:02 Sent To  
Notes
2001-10-22 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01090448
 814 N ROSEMARY AV
 CONT. CATALFUMO
 TEL 624-9697 X 256
  
 SBC= STANDARD BUILDING CODE 1997
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- SBC 3203 DOORS/ WINDOWS SHALL NOT
 OPEN OR PROJECT UPON PUBLIC PROPERTY.
  
 2)- FL. ACCES. CODE, 4.13.6 MANEUVERING
 CLEARENCES AT DOORS, SEE DOOR # 3 & 8.
 18" IS REQUIRED ON THE PULL SIDE & A
 MINIMUM OF 12 ON THE PUSH SIDE OF DOOR,
 AT LATCH.
  
 3)- SHEET A-2 DETAILS 1&2 INDICATE THAT
 SUSPENDED CEILINGS WILL BE HUNG FROM THE
 EXISTING PRECAST T'S, HOW ARE THE #9
 HANGING WIRE TO BE ATTACHED TO THE
 PRE-CAST T'S?
  
 4)- SBC 104.1.1 AWNINGS REQUIRE A SSEPER
 ATE PERMIT.
  
 5)- SBC 3204.2 CLOTH AWNNINGS REQUIRE
 FIRE RESITANCE CERTIFICATE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-10-23 Cont ID  
Sent By dpalmer Date 2001-10-23 Time 22:05 Rev Time 0.00
Received By dpalmer Date 2001-10-23 Time 22:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-10-16 Cont ID  
Sent By mcarsill Date 2001-10-16 Time 08:47 Rev Time 0.00
Received By mcarsill Date 2001-10-16 Time 08:47 Sent To  
Notes
2001-10-16 00:00:001) IT APPEARS THAT THIS BUILDING IS
 LOCATED IN THE CITY FIRE LIMITS.
 CERTAIN BUILDING AND FIRE CODE
 REGULATIONS APPLY TO BUILDINGS LOCATED
 IN THESE LIMITS. PLEASE SEE APPENDIX F
 STANDARD BUILDING CODE AND CHAPTER 11
 OF THE CITY CODE.
 2) NO INTERIOR FINISH INFORMATION
 PROVIDED. CLASS A OR B REQUIRED IN
 EXITS, AND CLASS A,B,OR C IN OTHER
 AREAS.
  
 APPROVED PROVISO:
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status C Date 2001-10-23 Cont ID  
Sent By ndenmark Date 2001-10-23 Time 10:30 Rev Time 0.33
Received By ndenmark Date 2001-10-23 Time 10:30 Sent To  
Notes
2001-10-23 00:00:00PROVISO:
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-21 Cont ID  
Sent By pschmitz Date 2001-10-21 Time 13:35 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-10-21 00:00:00PLUMBING PLAN REVIEW. DENIED.
 (1A) SHT A-1 TOILET RM'S #1,#2 COMPLY
 WITH FACBC-97 SEC 4.22, LOCATION OF W/C,
 LAV, GRAB BARS, CLEAR FLR SPACE, DOOR
 SWING AND TOILET ACCESSORIES.
 (B) BREAK ROOM SINK COMPLY W/ SEC 4.24
 HGTH 34"AFF, KNEE CLEARANCE 19",CLEAR
 FLOOR SPACE 30"X 48".
 (C) DRINKING FOUNTAIN REQUIRED, TAB 407
 FACBC-97 SEC 4.1.3(10)(A) CLEAR FLOOR
 SPACE, PEOPLE WHO HAVE TROUBLE BENDING.
 (D) TOILET ROOMS TO BE DIRECTLY ACCES-
 SIBLE TO THE PUBLIC, SEC 407.2.2
 (2)SHT M-1 PROVIDE A ISOMETRIC DRAWING
 OF THE DWV AND WATER PIPING, WITH PIPE
 SIZES, SEC 104.3
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop Z ZONING
Rev No 1 Status F Date 2001-09-28 Cont ID  
Sent By sgraham Date 2001-09-28 Time 11:42 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-09-28 00:00:00FAILED URBAN DESIGN