| Plan Review Stops For Permit 01090437 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-09-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-14 |
Time |
09:58 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-09-14 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2001-09-14 00:00:00 | PROVISO - ATTIC ACCESS FOR AHU SHALL BE | | | NO LESS THAT 22" X 36"CONTINUOUS TO | | | EQUIPMENT, DISCONNECT, CONVENIENCE | | | OUTLET, AND LIGHT ON EQUIPMENT SIDE | | | COTROLLED BY A SWITCH AT ACCESS | | | OPENING. AUXILIARY DRAIN PAN WITH | | | OVERFLOW PROTECTION.ALL THE ABOVED | | | ITEMS REQUIRED FOR ATTIC INSTALLATION. | | | | | | EXHAUST FANS NOT INIDICATED ON PLAN. | | | SHOW COMPLIANCE WITH 1997 SMC 503.3.1, | | | SHALL BE MECHANICALLY EXHAUSTED TO THE | | | OUTDOORS OR HAVE WINDOWS WITH NO LESS | | | THAN 3 SQ FT OF OPEN SPACE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|
|
|