| Plan Review Stops For Permit 01090435 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2002-04-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-04-25 |
Time |
12:52 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-04-25 00:00:00 | REVISION DATED 4/10/02 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2002-01-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-25 |
Time |
09:47 |
Rev Time |
0.10 |
| Received By |
jwitmer |
Date |
2002-01-24 |
Time |
16:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2002-01-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-01-16 |
Time |
16:10 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2002-01-16 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2002-01-16 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT #01090435 | | | 1600 N FL MANGO | | | | | | 1)- QUESTION FROM PREVIOUS REVIEW, AREA | | | OVER OFFICE, IS TO BE CONSIDERED A | | | "STORAGE" AREA. THE FIRE SPRINKLER PLAN | | | INDICATES CLEARLY MEZZANINE. EITHER THE | | | DESIGN PROFESSIONAL SHALL INDICATE IN | | | LETTER FORM SIGNED & SEALED OR A NEW | | | DRAWING WITH THE MEZZANINE REMOVED. | | | OTHERWISE THE CITY SHALL REQUIRE | | | THE AFFADAVIT FROM THE DESIGN PROFESSION | | | AL INDICATING WHAT THE SAFE LOADING | | | WILL BE FOR THE MEZZANINE. | | | | | | THE CONTRACTOR SHALL HAVE THE PLAN REVIE | | | WED BY THE COUNTY FOR IMPACT FEES BEFORE | | | THE PLAN CAN BE ISSUED. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-01-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-01-02 |
Time |
16:15 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2002-01-02 |
Time |
16:15 |
Sent To |
|
|
| Notes |
| 2002-01-02 00:00:00 | BUILDING PLAN REVIEW | | | 1600 N FLORIDA MANGO ROAD | | | PERMIT # 01090435 | | | CONT: MCKINNEY COMMERCIAL | | | CELL: (321) 508-8024 CURT | | | | | | 1)- COMMENT FROM PREVIOUS PLAN REVIEW | | | ABOUT IS THE BUILDING AND ADDITION | | | FIRE SPRINKLERED? THE ANSWER WAS "YES" | | | WE SHALL REQUIRE THE FIRE SPRINKLER PLAN | | | (2) COPIES BEFORE ISSUANCE OF THE BUILD- | | | ING PERMIT. | | | | | | (2)- COMMENT FROM PREVIOUS REVIEW IN REF | | | RENCE TO STORAGE OVER THE OFFICE AND THE | | | REQUIRED AFFIDAVIT FROM THE DESIGN | | | PROFESSIONAL,NOT ADDRESSED. | | | SOMEONE HAS WRITTEN ON THE COMMENT SHEET | | | IN RED PENCIL NOTHING FROM THE ARCHETECT | | | SIGNED AND SEALED. | | | | | | (3)- THE STRUCTURAL PLANS AND LETTER | | | FOR THE STRUCTURE ARENOT SEALED. | | | FL S S 61G15-23.002 A PROFSSIONAL ENGIN- | | | EER SHALL SIGN HIS NAME AND AFFIX HIS | | | SEAL TO ALL PLANS, SPECIFICATIONS, | | | REPORTS OR OTHER DOCUMENTS PREPARED OR | | | ISSUED BY SAID REGISTRANT & BEING FILED | | | FOR PUBLIC RECORD. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-10-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-10-26 |
Time |
08:46 |
Rev Time |
3.50 |
| Received By |
jwitmer |
Date |
2001-10-26 |
Time |
06:58 |
Sent To |
|
|
| Notes |
| 2001-10-26 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01090435 | | | 1600 N. FLORID MANGO DOAD | | | CONT: MCKINNEY COMMERCIAL CONST.GR. | | | TEL: (321) 727-0059 | | | | | | SBC= 1997 STANDAED BUILDING CODE | | | SBC*= AMENDMENTS/ STANDARD BUILDING CODE | | | | | | 1)- SBC* 104.2.2 ADDITIONAL INFORMATION | | | REQUIRED, A CURRENT SURVEY. SBC 503.4.1 | | | /60' CLEAR AREA FOR AREA MODIFICATIONS. | | | | | | 2)- SBC* PLANS DO NOT INDICATE TYPE OF | | | BUILDING TYPE I- VI. IS THE CURRENT | | | BUILDINGS FULLY SPRINKLERED? WILL THE | | | ADDITION AS WELL AS THE OFFICE BE FULLY | | | SPRINKLERED? | | | | | | 3)- 8 1/2"X11" DETAIL SHEET, ALTERNATE | | | SECTIION, THIS DETAIL INDICATES 16" | | | FLOOR TRUSSES,AGAIN WHAT TYPE CONSTRUC- | | | TION ARE YOU USING? WHAT TYPE OCCUPANCY | | | WILL THE AREA ABOVE THE 16" FLOOR TRUSS- | | | ES BE USED FOR? STORAGE, ADMINISTTRATIVE | | | CODE 106.4.2 STORAGE & FACTORY OWNER, | | | AGENT SHALL EMPLOY A COMPETENT ARCHITECT | | | OR ENGINEER IN COMPUTING THE SAFE FLOOR | | | LOAD CAPACITY. ALL SUCH COMPUTATIONS | | | SHALL BE ACCOMPANIED BY AN AFFIDAVIT | | | FROM THE DESIGN PROFESSIONAL STATING THE | | | SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR | | | IN POUNDS PER SQUARE FOOTUNIFORMLY | | | DISTRIBUTED.THE COMPUTATIONS & AFFIDAVIT | | | SHALL BE FILED AS A PERMANENT RECORD OF | | | THE BUILDING DEPARTMENT. | | | | | | 4)- SBC 411.1.1 HIGH RACK STORAGE, | | | PLEASE PROVIDE INFORMATION ON STORAGE | | | COMPONENTS? | | | | | | 5)- NEW ADDITION, WILL PRODUCT APPROVAL | | | FOR THE SWING DOORS, OVERHEAD DOORS AS | | | WELL AS THEROOFING BE SUBMITTED WITH | | | SHOP DRAWINGS? | | | | | | 6)- THE DESIGN PROFESSIONALS ARE TO | | | ADDRESS THE DESIGN DIFFERERENCIAL OF THE | | | OLD STRUCTURE, THE ABILITY OF THE EXIST | | | ING STRUCTURE (DESIGNED UNDER PREVIOUS | | | CODES) TO WITHSTAND THE WIND LOADS AND | | | DESIGN PRESSURES OF TODAYS CODE? | | | | | | 7)- OFFICE SPACE: FL.ACC CODE 4.1.6(2) | | | PLEASE INDICATE THE HANDICAPPED EGRESS | | | INTO THE OFFICES. | | | | | | 8)- MENS RESTROOM :FL ACC CODE 4.17.5 | | | DOORS SHALL NOT SWING INTO THE CLEAR | | | FLOOR SPACE OF ANY FIXTURE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2002-04-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-04-24 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-04-24 |
Time |
13:34 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-01-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-01-14 |
Time |
17:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-01-14 |
Time |
17:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-12-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-11 |
Time |
21:22 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-11 |
Time |
21:22 |
Sent To |
|
|
| Notes |
| 2001-12-11 00:00:00 | *************** UNSAT ************** | | | | | | PLEASE NOTE THAT NOTE#1&2 FROM FIRST | | | REVIEW IS NOT SHOWN ON PLANS. | | | PLEASE NOTE THAT LOAD CALCUALTIONS, | | | NEED TO BE SHOWN AS ON FIRST SET OF | | | NOTES. PLEASE SEE 215-5,220-3, 220-3-B9, | | | 215-2,215-3,230-42,,,,PLEASE CLARIFY | | | WHERE 125% IS SHOWN? | | | PLEASE NOTE IF METHOD OF EQUIPMENT | | | GRONDING IS A METAL CONDUIT THEN PLEASE | | | SHOW ON PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-10-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-24 |
Time |
20:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-24 |
Time |
20:29 |
Sent To |
|
|
| Notes |
| 2001-10-24 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT LOAD CALCALAT- | | | -IONS NEED TO BE SHOWN!!215-5 | | | ALL CONTINOUS LOADS AT 125% | | | PLEASE NOTE PLANS SHOW CONNECTED LOADS | | | W/NO WATTS PER SQ FT, OUTLETS ETC | | | | | | 2)NOTE: PLEASE CLARIFY EQUIPMENT | | | GROUNDING BETWEEN FIRST MEANS OF DISC | | | AND PANELS?? 250-122 | | | | | | | | | 3)NOTE: PLEASE NOTE THAT ALL PLANS MUST | | | CONTAIN AN ORIGINAL SIGNATURE FROM THE | | | ARCH/ENGINEER OF RECORD PER FS/FAC | | | 471.025/481.221 | | | PLEASE NOTE THAT PLANSHAVE A STAMP FOR | | | SIGNATURE? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2002-01-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-24 |
Time |
16:07 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2002-01-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-01-25 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-01-25 |
Time |
11:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2002-01-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-01-10 |
Time |
17:00 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-01-10 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2002-01-10 00:00:00 | 1) A REVIEW OF THE FIRE SPRINKLER | | | DRAWINGS INDICATE THAT THE NORTH | | | BUILDING INCLUDING THE NEW ADDITION | | | WILL EXCEED THE 40,000 SQUARE FEET | | | PROTECTION AREA LIMITATIONS INDICATED | | | IN NFPA 13. ACCORDING TO NFPA 13, | | | STORAGE OCCUPANCIES CANNOT EXCEED | | | 40,000 SQUARE FEET SUPPLIED BY A SINGLE | | | RISER A SITE VISIT WAS PERFORMED ON | | | 1.10.02 BY CITY STAFF. IT IS BELIEVED | | | THAT THE EXISTING 1000 GALLON FIRE | | | PUMP IS SUPPLIED BY AN EXISTING 6" | | | WATER LINE WHICH SHOULD BE AT LEAST | | | AN 8" LINE. HIGH-PILED STORAGE WAS | | | OBSERVED INSIDE AT LEAST ONE OF THE | | | BUILDINGS. IT IS THE OPINION OF CITY | | | STAFF THAT A COMPLETE REPORT BE | | | PREPARED BY A LICENSED FIRE PROTECTION | | | ENGINEER WITH REGARDS TO EXISTING | | | FIRE PROTECTION FOR THE BUILDINGS AND | | | THE FUTURE FIRE PROTECTION SYSTEM | | | PLANNED FOR THE NEW ADDITION. THE | | | NEW ADDITION CANNOT BE CONNECTED TO | | | THE EXISTING SYSTEM AS IT WOULD EXCEED | | | AREA LIMITATIONS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-12-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-10 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-10 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2001-12-10 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS OR | | | CALCULATIONS PROVIDED WITH PLANS FOR | | | NEW FIRE SPRINKLER SYSTEM PLANNED FOR | | | NEW BUILDING. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-10-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-23 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-23 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2001-10-23 00:00:00 | 1) IT IS NOTED ON THE PLANS A FIRE | | | PUMP ROOM AND AN EXISTING SIAMESE | | | CONNECTION. WHICH PORTIONS OF THE | | | BUILDING ARE FIRE SPRINKLER PROTECTED. | | | 2) ARE ANY RACK STORAGE UNITS PLANNED | | | FOR USE WITHIN THE PROPOSED WAREHOUSE. | | | 3) WILL THE NEW OFFICE BE SPRINKLERED | | | ON NON-SPRINKLERED. | | | 4) NO INTERIOR FINISH INFORMATION | | | PROVIDED FOR WALLS AND CEILINGS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2002-04-25 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-04-24 |
Time |
13:56 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-04-25 |
Time |
09:39 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2002-03-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-08 |
Time |
13:10 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-03-08 |
Time |
07:50 |
Sent To |
|
|
| Notes |
| 2002-03-08 00:00:00 | | | | MECH REV PERMIT 02020569 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-01-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-11 |
Time |
09:39 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-01-11 |
Time |
09:15 |
Sent To |
|
|
| Notes |
| 2002-01-11 00:00:00 | | | | MECHANICAL PERMIT 02020569 | | | | | | PROVISO: | | | | | | FRESH AIR INTAKE SHALL BE SCREENEDAND | | | LOCATED A MIMINUM OF 10 FT FROM ANY VENT | | | OUTLET OR SANITARY SEWER VENT OUTLET, | | | UNLESS SUCH A VENT OUTLET IS NOT LESS | | | THAN 24 INCHES ABOVE THE FRESH AIR | | | INLET.1997 SMC 405 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-12-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-14 |
Time |
09:56 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2001-12-14 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2001-12-14 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE OUTSIDE ARE | | | CALCULATIONS AS PER ASHRAE 62-89. | | | INDICATE CALCULATION ON THE PLAN. | | | | | | PLEASE INDICATE PROTECTION FOR AHU #1, | | | NOTE INDICATES A VERTICAL UNIT BELOW | | | FUTURE STR (STORE?).WILL THIS BE THE | | | SAME OCCUPANT AS THE OFFICE SPACE? | | | | | | PLEASE NOTE AS PER 1997 SMC 609.1.1, NO | | | COMBUSTIBLES SHALL BE ABOVE THE CEILING | | | IN THE RETURN AIR PLENUM. | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR IS | | | REQUIRED AS PER 1997 SMC 406.1. WITH | | | NOTIFICATION TO ALARM/STROBE IN | | | NORMALLY OCCUPIED AREAS (NFPA 90A | | | 4-4.4.3). | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-10-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-24 |
Time |
10:05 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2001-10-24 |
Time |
09:58 |
Sent To |
|
|
| Notes |
| 2001-10-24 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | | ASHRAE 62-89. | | | | | | 2.PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2. | | | | | | 3.PROVIDE TOTAL BTU'S FOR AIR HANDLER | | | UNITS. | | | | | | 4.INDICATE CFM DISTRIBUTION FOR EACH | | | DROP. | | | | | | 5.INDICATE ACCESS FOR SERVICE, | | | MAINTENANCE AND REPLACEMENT FOR | | | AHU #2. | | | | | | PLEASE NOTE AS PER FLORIDA STATUE | | | 481.221 (1) (A), PLANS SHALL BEAR THE | | | SIGNATURE AND SEAL OF THE REGISTERED | | | ARCHITECT WHO PREPARED OR APPROVED THE | | | DOCUMENT AND THE DATE ON WHICH THEY | | | WERE SEALED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2002-04-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-04-24 |
Time |
09:19 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-04-24 |
Time |
09:19 |
Sent To |
|
|
| Notes |
| 2002-04-24 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) REVISION SHALL SHOW PROPER LOCATION | | | OF WATER HAMMER ARRESTORS. THEY SHALL BE | | | LOCATED CLOSE TO FIXTURE IN AN EFFECTIVE | | | RANGE NOT AT TOP OF DROP AS SHOWN. THESE | | | WERE RED LINED FOR PERMIT AND NEED TO BE | | | CORRECTED ON THE REVISION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-01-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-22 |
Time |
19:32 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-01-22 |
Time |
19:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-01-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-04 |
Time |
15:28 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2002-01-04 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2002-01-04 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SHT 2, TOILET ROOM TO BE ACCESSIBLE | | | AND DESIGNATED UNISEX HDCP TOILET ROOM. | | | TABLE 407 REQUIRES 2 W/C'S AND 2 LAVS | | | FOR WOMEN. | | | | | | 2) SHT 5, WATER RISER DIAGRAM, AIR CHAM- | | | BERS TO BE ACCESSIBLE AND RECHARGEABLE | | | PER PDI-WH 201 AND SPC SEC 607.8.3. | | | WATER HAMMER ARRESTORS DO NOT REQUIRE | | | ACCESS AND SHALL BE LOCATED CLOSE TO | | | SOURCE OF SHOCK. | | | | | | 3) SHT 2, DOOR SHALL NOT SWING INTO | | | CLEAR FLOOR SPACE OF FIXTURES 4.22.2. | | | | | | 4) SHT 2, PLEASE SHOW DETAILS FOR SINK | | | COMPLIANCE SEC 4.24 | | | | | | 5) SHT 5, NOTE #12 REMOVE REFERENCE TO | | | AIR CHAMBERS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-10-27 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-10-27 |
Time |
07:00 |
Rev Time |
2.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-27 00:00:00 | PLUMBING PLAN REVIEW,DENIED | | | CODE REFERENCE, SPC-94, FACBC-97 | | | (1) TAB 407 MINIMUM FACILITIES, WOMEN'S | | | REST RM, REQUIRED 2-W/C, 2-LAV'S. | | | (2) SHT-2,FACBC SEC 4.1 MIN. REQUIRMENTS | | | ALL AREAS OF NEWELY DESIGNED OR CONSTRU- | | | CTED BUILDINGSAND FACILITIES REQUIRED | | | TO BE ACCESSIBLE, SHALL COMPLY WITH 4.16 | | | ALTERATIONS TO EXISTING BUILDINGS. | | | PROVIDE DETAILS OF H/C FIXTURES,SEE FIGS | | | PAGES 102 THRU 109 FACBC-97. | | | SHOW CLEAR FLOOR SPACE FOR EA FIXTURE. | | | DOORS SHALL NOT SWING INTO CLEAR FLOOR | | | SPACE REQUIRED FOR ANY FIXTURE 4.22.2 | | | BREAK RM SINK, SEC 4.24 SINKS. | | | (3) SHT-5,DWV ISOMETRIC, D/F, URINAL | | | NOT VENTED. | | | (4A) SHT-5, PROVIDE ISOMETRIC FOR WATER | | | PIPING,PIPE SIZES,SHOW LOCATION OF WATER | | | HEATER,BACK FLOW PREVENTER. | | | (B) NOTE #12 REFERENCE TO AIR CHAMBERS, | | | SEC 607.8.3 ACCESSIBLE, RECHARGEABLE. | | | SPECIFY TYPE AND LOCATION OF WATER SHOCK | | | ARRESTOR.PDI-WH201, ASSE 1010. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-10-11 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-10-11 |
Time |
13:39 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|