Plan Review Details - Permit 01090435
Plan Review Stops For Permit 01090435
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-04-25 Cont ID  
Sent By jwitmer Date 2002-04-25 Time 12:52 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-04-25 00:00:00REVISION DATED 4/10/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-01-24 Cont ID  
Sent By pkrauss Date 2002-04-25 Time 09:47 Rev Time 0.10
Received By jwitmer Date 2002-01-24 Time 16:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2002-01-16 Cont ID  
Sent By jwitmer Date 2002-01-16 Time 16:10 Rev Time 1.50
Received By jwitmer Date 2002-01-16 Time 15:30 Sent To  
Notes
2002-01-16 00:00:00BUILDING PLAN REVIEW
 PERMIT #01090435
 1600 N FL MANGO
  
 1)- QUESTION FROM PREVIOUS REVIEW, AREA
 OVER OFFICE, IS TO BE CONSIDERED A
 "STORAGE" AREA. THE FIRE SPRINKLER PLAN
 INDICATES CLEARLY MEZZANINE. EITHER THE
 DESIGN PROFESSIONAL SHALL INDICATE IN
 LETTER FORM SIGNED & SEALED OR A NEW
 DRAWING WITH THE MEZZANINE REMOVED.
 OTHERWISE THE CITY SHALL REQUIRE
 THE AFFADAVIT FROM THE DESIGN PROFESSION
 AL INDICATING WHAT THE SAFE LOADING
 WILL BE FOR THE MEZZANINE.
  
 THE CONTRACTOR SHALL HAVE THE PLAN REVIE
 WED BY THE COUNTY FOR IMPACT FEES BEFORE
 THE PLAN CAN BE ISSUED.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-01-02 Cont ID  
Sent By jwitmer Date 2002-01-02 Time 16:15 Rev Time 1.50
Received By jwitmer Date 2002-01-02 Time 16:15 Sent To  
Notes
2002-01-02 00:00:00BUILDING PLAN REVIEW
 1600 N FLORIDA MANGO ROAD
 PERMIT # 01090435
 CONT: MCKINNEY COMMERCIAL
 CELL: (321) 508-8024 CURT
  
 1)- COMMENT FROM PREVIOUS PLAN REVIEW
 ABOUT IS THE BUILDING AND ADDITION
 FIRE SPRINKLERED? THE ANSWER WAS "YES"
 WE SHALL REQUIRE THE FIRE SPRINKLER PLAN
 (2) COPIES BEFORE ISSUANCE OF THE BUILD-
 ING PERMIT.
  
 (2)- COMMENT FROM PREVIOUS REVIEW IN REF
 RENCE TO STORAGE OVER THE OFFICE AND THE
 REQUIRED AFFIDAVIT FROM THE DESIGN
 PROFESSIONAL,NOT ADDRESSED.
 SOMEONE HAS WRITTEN ON THE COMMENT SHEET
 IN RED PENCIL NOTHING FROM THE ARCHETECT
 SIGNED AND SEALED.
  
 (3)- THE STRUCTURAL PLANS AND LETTER
 FOR THE STRUCTURE ARENOT SEALED.
 FL S S 61G15-23.002 A PROFSSIONAL ENGIN-
 EER SHALL SIGN HIS NAME AND AFFIX HIS
 SEAL TO ALL PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS PREPARED OR
 ISSUED BY SAID REGISTRANT & BEING FILED
 FOR PUBLIC RECORD.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-10-26 Cont ID  
Sent By jwitmer Date 2001-10-26 Time 08:46 Rev Time 3.50
Received By jwitmer Date 2001-10-26 Time 06:58 Sent To  
Notes
2001-10-26 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01090435
 1600 N. FLORID MANGO DOAD
 CONT: MCKINNEY COMMERCIAL CONST.GR.
 TEL: (321) 727-0059
  
 SBC= 1997 STANDAED BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- SBC* 104.2.2 ADDITIONAL INFORMATION
 REQUIRED, A CURRENT SURVEY. SBC 503.4.1
 /60' CLEAR AREA FOR AREA MODIFICATIONS.
  
 2)- SBC* PLANS DO NOT INDICATE TYPE OF
 BUILDING TYPE I- VI. IS THE CURRENT
 BUILDINGS FULLY SPRINKLERED? WILL THE
 ADDITION AS WELL AS THE OFFICE BE FULLY
 SPRINKLERED?
  
 3)- 8 1/2"X11" DETAIL SHEET, ALTERNATE
 SECTIION, THIS DETAIL INDICATES 16"
 FLOOR TRUSSES,AGAIN WHAT TYPE CONSTRUC-
 TION ARE YOU USING? WHAT TYPE OCCUPANCY
 WILL THE AREA ABOVE THE 16" FLOOR TRUSS-
 ES BE USED FOR? STORAGE, ADMINISTTRATIVE
 CODE 106.4.2 STORAGE & FACTORY OWNER,
 AGENT SHALL EMPLOY A COMPETENT ARCHITECT
 OR ENGINEER IN COMPUTING THE SAFE FLOOR
 LOAD CAPACITY. ALL SUCH COMPUTATIONS
 SHALL BE ACCOMPANIED BY AN AFFIDAVIT
 FROM THE DESIGN PROFESSIONAL STATING THE
 SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR
 IN POUNDS PER SQUARE FOOTUNIFORMLY
 DISTRIBUTED.THE COMPUTATIONS & AFFIDAVIT
 SHALL BE FILED AS A PERMANENT RECORD OF
 THE BUILDING DEPARTMENT.
  
 4)- SBC 411.1.1 HIGH RACK STORAGE,
 PLEASE PROVIDE INFORMATION ON STORAGE
 COMPONENTS?
  
 5)- NEW ADDITION, WILL PRODUCT APPROVAL
 FOR THE SWING DOORS, OVERHEAD DOORS AS
 WELL AS THEROOFING BE SUBMITTED WITH
 SHOP DRAWINGS?
  
 6)- THE DESIGN PROFESSIONALS ARE TO
 ADDRESS THE DESIGN DIFFERERENCIAL OF THE
 OLD STRUCTURE, THE ABILITY OF THE EXIST
 ING STRUCTURE (DESIGNED UNDER PREVIOUS
 CODES) TO WITHSTAND THE WIND LOADS AND
 DESIGN PRESSURES OF TODAYS CODE?
  
 7)- OFFICE SPACE: FL.ACC CODE 4.1.6(2)
 PLEASE INDICATE THE HANDICAPPED EGRESS
 INTO THE OFFICES.
  
 8)- MENS RESTROOM :FL ACC CODE 4.17.5
 DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE OF ANY FIXTURE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-04-24 Cont ID  
Sent By btrobaug Date 2002-04-24 Time 13:56 Rev Time 0.00
Received By btrobaug Date 2002-04-24 Time 13:34 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-01-14 Cont ID  
Sent By dpalmer Date 2002-01-14 Time 17:19 Rev Time 0.00
Received By dpalmer Date 2002-01-14 Time 17:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-12-11 Cont ID  
Sent By dpalmer Date 2001-12-11 Time 21:22 Rev Time 0.00
Received By dpalmer Date 2001-12-11 Time 21:22 Sent To  
Notes
2001-12-11 00:00:00*************** UNSAT **************
  
 PLEASE NOTE THAT NOTE#1&2 FROM FIRST
 REVIEW IS NOT SHOWN ON PLANS.
 PLEASE NOTE THAT LOAD CALCUALTIONS,
 NEED TO BE SHOWN AS ON FIRST SET OF
 NOTES. PLEASE SEE 215-5,220-3, 220-3-B9,
 215-2,215-3,230-42,,,,PLEASE CLARIFY
 WHERE 125% IS SHOWN?
 PLEASE NOTE IF METHOD OF EQUIPMENT
 GRONDING IS A METAL CONDUIT THEN PLEASE
 SHOW ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-24 Cont ID  
Sent By dpalmer Date 2001-10-24 Time 20:33 Rev Time 0.00
Received By dpalmer Date 2001-10-24 Time 20:29 Sent To  
Notes
2001-10-24 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT LOAD CALCALAT-
 -IONS NEED TO BE SHOWN!!215-5
 ALL CONTINOUS LOADS AT 125%
 PLEASE NOTE PLANS SHOW CONNECTED LOADS
 W/NO WATTS PER SQ FT, OUTLETS ETC
  
 2)NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING BETWEEN FIRST MEANS OF DISC
 AND PANELS?? 250-122
  
  
 3)NOTE: PLEASE NOTE THAT ALL PLANS MUST
 CONTAIN AN ORIGINAL SIGNATURE FROM THE
 ARCH/ENGINEER OF RECORD PER FS/FAC
 471.025/481.221
 PLEASE NOTE THAT PLANSHAVE A STAMP FOR
 SIGNATURE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-01-24 Cont ID  
Sent By kstevens Date 2002-01-24 Time 16:07 Rev Time 1.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-01-25 Cont ID  
Sent By mcarsill Date 2002-01-25 Time 11:30 Rev Time 0.00
Received By mcarsill Date 2002-01-25 Time 11:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2002-01-10 Cont ID  
Sent By mcarsill Date 2002-01-10 Time 17:00 Rev Time 0.00
Received By mcarsill Date 2002-01-10 Time 17:00 Sent To  
Notes
2002-01-10 00:00:001) A REVIEW OF THE FIRE SPRINKLER
 DRAWINGS INDICATE THAT THE NORTH
 BUILDING INCLUDING THE NEW ADDITION
 WILL EXCEED THE 40,000 SQUARE FEET
 PROTECTION AREA LIMITATIONS INDICATED
 IN NFPA 13. ACCORDING TO NFPA 13,
 STORAGE OCCUPANCIES CANNOT EXCEED
 40,000 SQUARE FEET SUPPLIED BY A SINGLE
 RISER A SITE VISIT WAS PERFORMED ON
 1.10.02 BY CITY STAFF. IT IS BELIEVED
 THAT THE EXISTING 1000 GALLON FIRE
 PUMP IS SUPPLIED BY AN EXISTING 6"
 WATER LINE WHICH SHOULD BE AT LEAST
 AN 8" LINE. HIGH-PILED STORAGE WAS
 OBSERVED INSIDE AT LEAST ONE OF THE
 BUILDINGS. IT IS THE OPINION OF CITY
 STAFF THAT A COMPLETE REPORT BE
 PREPARED BY A LICENSED FIRE PROTECTION
 ENGINEER WITH REGARDS TO EXISTING
 FIRE PROTECTION FOR THE BUILDINGS AND
 THE FUTURE FIRE PROTECTION SYSTEM
 PLANNED FOR THE NEW ADDITION. THE
 NEW ADDITION CANNOT BE CONNECTED TO
 THE EXISTING SYSTEM AS IT WOULD EXCEED
 AREA LIMITATIONS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-12-10 Cont ID  
Sent By mcarsill Date 2001-12-10 Time 13:56 Rev Time 0.00
Received By mcarsill Date 2001-12-10 Time 13:56 Sent To  
Notes
2001-12-10 00:00:001) NO FIRE SPRINKLER DRAWINGS OR
 CALCULATIONS PROVIDED WITH PLANS FOR
 NEW FIRE SPRINKLER SYSTEM PLANNED FOR
 NEW BUILDING.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-10-23 Cont ID  
Sent By mcarsill Date 2001-10-23 Time 13:48 Rev Time 0.00
Received By mcarsill Date 2001-10-23 Time 13:48 Sent To  
Notes
2001-10-23 00:00:001) IT IS NOTED ON THE PLANS A FIRE
 PUMP ROOM AND AN EXISTING SIAMESE
 CONNECTION. WHICH PORTIONS OF THE
 BUILDING ARE FIRE SPRINKLER PROTECTED.
 2) ARE ANY RACK STORAGE UNITS PLANNED
 FOR USE WITHIN THE PROPOSED WAREHOUSE.
 3) WILL THE NEW OFFICE BE SPRINKLERED
 ON NON-SPRINKLERED.
 4) NO INTERIOR FINISH INFORMATION
 PROVIDED FOR WALLS AND CEILINGS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2002-04-25 Cont ID  
Sent By btrobaug Date 2002-04-24 Time 13:56 Rev Time 0.35
Received By pkrauss Date 2002-04-25 Time 09:39 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-03-08 Cont ID  
Sent By pkrauss Date 2002-03-08 Time 13:10 Rev Time 0.40
Received By pkrauss Date 2002-03-08 Time 07:50 Sent To  
Notes
2002-03-08 00:00:00 
 MECH REV PERMIT 02020569

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-01-11 Cont ID  
Sent By pkrauss Date 2002-01-11 Time 09:39 Rev Time 0.40
Received By pkrauss Date 2002-01-11 Time 09:15 Sent To  
Notes
2002-01-11 00:00:00 
 MECHANICAL PERMIT 02020569
  
 PROVISO:
  
 FRESH AIR INTAKE SHALL BE SCREENEDAND
 LOCATED A MIMINUM OF 10 FT FROM ANY VENT
 OUTLET OR SANITARY SEWER VENT OUTLET,
 UNLESS SUCH A VENT OUTLET IS NOT LESS
 THAN 24 INCHES ABOVE THE FRESH AIR
 INLET.1997 SMC 405
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-12-14 Cont ID  
Sent By pkrauss Date 2001-12-14 Time 09:56 Rev Time 1.00
Received By pkrauss Date 2001-12-14 Time 09:41 Sent To  
Notes
2001-12-14 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE OUTSIDE ARE
 CALCULATIONS AS PER ASHRAE 62-89.
 INDICATE CALCULATION ON THE PLAN.
  
 PLEASE INDICATE PROTECTION FOR AHU #1,
 NOTE INDICATES A VERTICAL UNIT BELOW
 FUTURE STR (STORE?).WILL THIS BE THE
 SAME OCCUPANT AS THE OFFICE SPACE?
  
 PLEASE NOTE AS PER 1997 SMC 609.1.1, NO
 COMBUSTIBLES SHALL BE ABOVE THE CEILING
 IN THE RETURN AIR PLENUM.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR IS
 REQUIRED AS PER 1997 SMC 406.1. WITH
 NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS (NFPA 90A
 4-4.4.3).
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-10-24 Cont ID  
Sent By pkrauss Date 2001-10-24 Time 10:05 Rev Time 1.00
Received By pkrauss Date 2001-10-24 Time 09:58 Sent To  
Notes
2001-10-24 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
  
 2.PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 3.PROVIDE TOTAL BTU'S FOR AIR HANDLER
 UNITS.
  
 4.INDICATE CFM DISTRIBUTION FOR EACH
 DROP.
  
 5.INDICATE ACCESS FOR SERVICE,
 MAINTENANCE AND REPLACEMENT FOR
 AHU #2.
  
 PLEASE NOTE AS PER FLORIDA STATUE
 481.221 (1) (A), PLANS SHALL BEAR THE
 SIGNATURE AND SEAL OF THE REGISTERED
 ARCHITECT WHO PREPARED OR APPROVED THE
 DOCUMENT AND THE DATE ON WHICH THEY
 WERE SEALED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status F Date 2002-04-24 Cont ID  
Sent By kstevens Date 2002-04-24 Time 09:19 Rev Time 0.00
Received By kstevens Date 2002-04-24 Time 09:19 Sent To  
Notes
2002-04-24 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) REVISION SHALL SHOW PROPER LOCATION
 OF WATER HAMMER ARRESTORS. THEY SHALL BE
 LOCATED CLOSE TO FIXTURE IN AN EFFECTIVE
 RANGE NOT AT TOP OF DROP AS SHOWN. THESE
 WERE RED LINED FOR PERMIT AND NEED TO BE
 CORRECTED ON THE REVISION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-01-22 Cont ID  
Sent By kstevens Date 2002-01-22 Time 19:32 Rev Time 0.50
Received By kstevens Date 2002-01-22 Time 19:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-01-04 Cont ID  
Sent By kstevens Date 2002-01-04 Time 15:28 Rev Time 1.50
Received By kstevens Date 2002-01-04 Time 15:28 Sent To  
Notes
2002-01-04 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT 2, TOILET ROOM TO BE ACCESSIBLE
 AND DESIGNATED UNISEX HDCP TOILET ROOM.
 TABLE 407 REQUIRES 2 W/C'S AND 2 LAVS
 FOR WOMEN.
  
 2) SHT 5, WATER RISER DIAGRAM, AIR CHAM-
 BERS TO BE ACCESSIBLE AND RECHARGEABLE
 PER PDI-WH 201 AND SPC SEC 607.8.3.
 WATER HAMMER ARRESTORS DO NOT REQUIRE
 ACCESS AND SHALL BE LOCATED CLOSE TO
 SOURCE OF SHOCK.
  
 3) SHT 2, DOOR SHALL NOT SWING INTO
 CLEAR FLOOR SPACE OF FIXTURES 4.22.2.
  
 4) SHT 2, PLEASE SHOW DETAILS FOR SINK
 COMPLIANCE SEC 4.24
  
 5) SHT 5, NOTE #12 REMOVE REFERENCE TO
 AIR CHAMBERS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-27 Cont ID  
Sent By pschmitz Date 2001-10-27 Time 07:00 Rev Time 2.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-10-27 00:00:00PLUMBING PLAN REVIEW,DENIED
 CODE REFERENCE, SPC-94, FACBC-97
 (1) TAB 407 MINIMUM FACILITIES, WOMEN'S
 REST RM, REQUIRED 2-W/C, 2-LAV'S.
 (2) SHT-2,FACBC SEC 4.1 MIN. REQUIRMENTS
 ALL AREAS OF NEWELY DESIGNED OR CONSTRU-
 CTED BUILDINGSAND FACILITIES REQUIRED
 TO BE ACCESSIBLE, SHALL COMPLY WITH 4.16
 ALTERATIONS TO EXISTING BUILDINGS.
 PROVIDE DETAILS OF H/C FIXTURES,SEE FIGS
 PAGES 102 THRU 109 FACBC-97.
 SHOW CLEAR FLOOR SPACE FOR EA FIXTURE.
 DOORS SHALL NOT SWING INTO CLEAR FLOOR
 SPACE REQUIRED FOR ANY FIXTURE 4.22.2
 BREAK RM SINK, SEC 4.24 SINKS.
 (3) SHT-5,DWV ISOMETRIC, D/F, URINAL
 NOT VENTED.
 (4A) SHT-5, PROVIDE ISOMETRIC FOR WATER
 PIPING,PIPE SIZES,SHOW LOCATION OF WATER
 HEATER,BACK FLOW PREVENTER.
 (B) NOTE #12 REFERENCE TO AIR CHAMBERS,
 SEC 607.8.3 ACCESSIBLE, RECHARGEABLE.
 SPECIFY TYPE AND LOCATION OF WATER SHOCK
 ARRESTOR.PDI-WH201, ASSE 1010.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop Z ZONING
Rev No 1 Status P Date 2001-10-11 Cont ID  
Sent By sgraham Date 2001-10-11 Time 13:39 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***