Plan Review Details - Permit 01090320
Plan Review Stops For Permit 01090320
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-09-13 Cont ID  
Sent By pkrauss Date 2001-09-13 Time 12:22 Rev Time 0.40
Received By pkrauss Date 2001-09-13 Time 11:57 Sent To  
Notes
2001-09-13 00:00:00******************PROVISO***************
  
 AHU IN ATTIC SHALL COMPLY WITH 1997 SMC
 304.1.1,ACCESS OPENING SHALL BE NO
 LESS THAN 22" X 36" CONTINUOUS FROM THE
 OPENING TO THE EQUIPMENT AND ITS
 CONTROLS.
  
 EQUIPMENT IN THE ATTIC SHALL HAVE AN
 ACCESSIBLE DISCONNECT SWITCH AND A
 110-120 VOLT A/C GROUNDING TYPE
 CONVENIENCE OUTLET.A LIGHT ON THE
 SERVICE SIDE OF THE EQUIPMENT CONTROLED
 BY A SWITCH AT THE ACCESS OPENING.
  
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED FOR AHU AS PER 1997
 SMC 304.8.6.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.