Plan Review Details - Permit 01090308
Plan Review Stops For Permit 01090308
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-11-06 Cont ID  
Sent By jwitmer Date 2001-11-06 Time 10:43 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-09-20 Cont ID  
Sent By jwitmer Date 2001-09-20 Time 15:28 Rev Time 2.00
Received By jwitmer Date 2001-09-20 Time 15:28 Sent To  
Notes
2001-09-20 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01090308
 1920 PALM BEACH LAKES BLVD #108
 CONT : DOUGLAS M PISARSKI
 TEL: (561) 832-9984
 FAX: (561) 662-3820
  
 1)- CONFRENCE DOOR FL ACCES CODE 4.13.6.
 MANEUVERING CLEARENCES AT DOORS
  
 2)- SBC TABLE 803.3 MINIMUM INTERIOR
 FINISH CLASSIFICATION MISSING, CLASSIFI-
 CATION 803.2.
  
 3)- 1 HR TENANT SEPERATION WALLS INDI-
 CATE METHOD OF COMPLIANCE WITH SBC 705.5
 PENETRATIONS OF FIRE RATED WALLS.
  
 4)- SBC 1204.2 ALL RESTROOM FLOORS AND
 WALLS ARE TO BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-03-18 Cont ID  
Sent By btrobaug Date 2002-03-18 Time 13:22 Rev Time 0.00
Received By btrobaug Date 2002-03-18 Time 08:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-11-05 Cont ID  
Sent By dpalmer Date 2001-11-05 Time 21:33 Rev Time 0.00
Received By dpalmer Date 2001-11-05 Time 21:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-09-18 Cont ID  
Sent By dpalmer Date 2001-09-18 Time 17:34 Rev Time 0.00
Received By dpalmer Date 2001-09-18 Time 17:23 Sent To  
Notes
2001-09-18 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS ARE TO BE SHOWN AT 125%. PLEASE
 NOTE THAT PLANS WERE COMING BACK FOR
 FIRE COMMENTS. PER 230-42/215-2-3.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-11-06 Cont ID  
Sent By jwitmer Date 2001-11-06 Time 10:41 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-11-06 00:00:00MIKE CARSELLO REVIEWED 10/29/01 OK

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-09-10 Cont ID  
Sent By mcarsill Date 2001-09-10 Time 16:36 Rev Time 0.00
Received By mcarsill Date 2001-09-10 Time 16:35 Sent To  
Notes
2001-09-10 00:00:001) PLEASE EXPLAIN ELECTRONIC LOCK (EDL)
 SHOWN ON EXIT DOOR NEAR WAITING AREA.
 IS FREE EGRESS PROVIDED AT ALL TIMES
 FROM THE TENANT SIDE OF THE TENANT
 SPACE.
 2) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION NOTED ON THE PLANS FOR
 WALLS AND CEILINGS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-11-13 Cont ID  
Sent By pkrauss Date 2001-11-13 Time 11:06 Rev Time 0.45
Received By pkrauss Date 2001-11-13 Time 10:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-09-25 Cont ID  
Sent By pkrauss Date 2001-09-25 Time 11:09 Rev Time 1.00
Received By pkrauss Date 2001-09-25 Time 11:04 Sent To  
Notes
2001-09-25 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.EXHAUST FAN 2 IS NOT INDICATED ON
 PLAN.
  
 2.PROVIDE AIR BALANCE SCHEDULE TO
 SHOW COMPLAINCE WITH 1997 SMC 501.2.
  
 3.AHU SHALL HAVE SUFFICIENT CLEARANCE
 FOR ACCESSIBILITY FOR SERVICE AND
 REPLACEMENT OF FILTERS, BLOWERS,
 MOTORS, COILS, CONTROLS AND VENT
 CONNECTIONS.
  
 4.PLEASE EXPLAIN THE 4" X 8" GRILL
 IS IT PULLING MAKE-UP AIR FROM
 THE INTERIOR SPACE?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-10-14 Cont ID  
Sent By pschmitz Date 2001-10-14 Time 14:34 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-10-14 00:00:00PLUMBING PLAN REVIEW, PROVISO
 (1)SEPERATE PERMIT FOR DENTAL VACUM,WAGD
 COMPRESSED AIR, PLUMBING CONTRACTOR TO
 COMPLY WITH NFPA-99C,LEVEL 3.
 CERTIFICATE REQUIRED AT TIME OF PERMIT.
 (2) SHT P-2 BACK FLOW PREVENTER ON WATER
 SERVICE, LOCAL ORD# 2853-95.
 BACK FLOW PREVENTERS REQUIRED ON ALL
 DENTAL EQUIPMENT SPC 94, SEC 601.6
 (3) SHT P-2 AIR CHAMBERS TO COMPLY WITH
 SEC 607.8.3 ACCESSIBLE & RECHARGEABLE.
 (4) SHT P-3 CO'S ON VACUM SYSTEM REQUIRE
 NFPA 99C SEC 4-5.2.2.3
 (5)SHT M-2 TERMINATION OF A/C CONDENSATE
 TO A DRY WELL, PLANTER, STORM DRAIN OUT
 SIDE OF BUILDING.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 561-659-8096X8233

Review Stop Z ZONING
Rev No 1 Status N Date 2001-11-09 Cont ID  
Sent By lsmith Date 2001-11-09 Time 11:55 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***