| Plan Review Stops For Permit 01090294 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-10-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-10-30 |
Time |
17:18 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-30 00:00:00 | PROVISO | | | PERMIT # 01090294 | | | 1649 FORUM PLACE | | | BUILDING ASSOCIATES | | | CELL 744-6741 - RICHARD PARKMAN | | | PROVIDE PRODUCT APPROVAL FOR NEW GLASS | | | / ALUM STOREFRONTJW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-09-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-09-24 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-09-24 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2001-09-24 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01090294 | | | 1649 FORUM PLACE | | | CONT: BUILDING ASSOCIATES INC | | | TEL: (561) 746-3421 | | | CEL: (561) 310-5429 | | | | | | SBC = STANDARD BUILDING CODE | | | | | | 1)- SHEET A1 INDICATES EXTERIOR DOORS | | | # 4,5 & 8. THERE IS NO PLOT PLAN, THE | | | KEY PLAN DOESN'T INDICATE WHERE THE PROP | | | ERTY LINE IS IN RELATIONSHIP WITH THESE | | | OPENINGS. SBC 705 1.1.2. PROTECTION OF | | | EXTERIOR WALL OPENINGS, EVERY EXTERIOR | | | WALL OPENING WITHIN 15' OF THE PROPERTY | | | LINE SHALL BE EQUIPPED WITH APPROVED | | | OPENING PROTECTIVES. | | | | | | 2)- SHEET A1 INDICATES THAT THERE WAS A | | | DOORWAY BLOCKED IN AT APPROXIMATELY | | | DOOR #5, IS DOORWAY #5 A NEW OPENING RE- | | | QUIRING THE LINTEL? IF SO DO THE BLOCK | | | CELLS ON EITHER SIDE OF THE DOORWAY | | | REQUIRE REINFORCING? | | | | | | 3)- SHEET A1 ALSO INDICATES THAT DOOR | | | #4 IS TO BE REPLACED, WILL THE DOOR JAMB | | | ALSO BE REPLACED? | | | | | | 4)- SBC 1606.2.6.2 COMPONENTS & CLADDING | | | EXTERIOR DOOR ASSEMBLIES (DOOR & JAMBS) | | | THAT ARE REPLACED SHALL COMPLY WITH | | | WIND ZONE TESTING REQUIREMENT TESTING. | | | 110 MPH WIND ZONE. THE CITY ACCEPTS | | | DADE COUNTY OR SBCCI TEST REPORTS, | | | (2 COPIES). | | | | | | 5)- SBC 1205 RODENT PROOFING, EXTERIOR | | | WALL OPENINGS TO COMPLY WITH THIS SEC- | | | TION OF THE CODE. | | | | | | 6)- SHEET A1 INDICATES THAT THERE WILL | | | BE NEW GLAZING (WINDOW) THE CITY SHALL | | | REQUIRE PRODUCT TESTING REPORTS,THE TEST | | | ING REPORT WILL NEED ONLY SHOW TESTING | | | FOR WIND, SINCE LESS THAN 50% OF THE | | | GLAZED OPENINGS ARE NOT BEING REPLACED | | | THIS STRUCTURE DOES NOT REQUIRE NEED TO | | | MEET THE REQUIREMENTS FOR LARGE MISSLE | | | IMPACT GLAZING. SBC 1606.4/1707/4/1. | | | CITY OFFICIAL INTERPRETATION (4). | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-10-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-25 |
Time |
07:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-25 |
Time |
07:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-10-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-02 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-02 |
Time |
11:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-10-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-16 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-16 |
Time |
12:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-09-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-09-10 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-09-10 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2001-09-10 00:00:00 | 1) PLANS DO NOT INDICATE ANY WAITING | | | SPACES. ARE ANY PLANNED AND IF SO WHERE | | | WILL THIS LOCATION BE. | | | 2) PLEASE PROVIDE OCCUPANT LOAD | | | CALCULATIONS TO INCLUDE THE NECESSARY | | | STAFF NEEDED TO RUN ESTABLISHMENT. | | | 3) DOOR # 1 REQUIRED TO HAVE SIGNAGE | | | "THESE DOORS TO REMAIN UNLOCKED DURING | | | BUSINESS HOURS" WITH ONE INCH LETTERING | | | ON A CONTRASTING BACKGROUND. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-04-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-24 |
Time |
09:43 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-04-24 |
Time |
09:17 |
Sent To |
|
|
| Notes |
| 2002-04-24 00:00:00 | MECHANICAL PERMIT 01121518 | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPRESSION, & WALKIN COOLER/FREEZER | | | | | | TEST AND BALANCE REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. | | | | | | 2001 FLORIDA BUILDING CODE, MECHANICAL | | | | | | PROVIDE AIR DUCT PATHWAYS OR AIR | | | TRANSFER PATHWAYS FROM HIGH ZONES TO | | | LOW ZONE. (BEDROOMS TO HALL). | | | 2001 FBC(M) 601.4, BALANCED AIR RETURN. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-10-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-24 |
Time |
13:06 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-10-24 |
Time |
12:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-09-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-28 |
Time |
11:15 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2001-09-28 |
Time |
11:15 |
Sent To |
|
|
| Notes |
| 2001-09-28 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | 1.PROVIDE AIR BALANCE SCHEDULE TO | | | SHOW COMPLIANCE WITH 1997 SMC 501.2. | | | | | | 2.PROVIDE DETAIL OF 6" GAS FLUE WITH | | | TERMINATION LOCATION AT ROOF. | | | | | | ADDITIONAL PERMIT REQUIRED FOR HOOD, | | | FIRE SUPRESSION AND WALK-IN COOLER. | | | PLEASE PROVIDE PLANS AND MANUFACTUERER | | | SUBMITTAL DATA/PRODUCT APPROVALS WITH | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-06-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-06-15 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-06-15 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2002-06-15 00:00:00 | REVISION OK - SANT. RISER DIAGRAM - ADD | | | FLOOR SINK FOR COND. FROM COOLER |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-10-28 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-10-28 |
Time |
15:07 |
Rev Time |
2.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-28 00:00:00 | PLUMBING PLAN REVIEW,RESUB PROVISO. | | | SEE SHT A5.1 SEPERATE GAS PERMIT,ALSO | | | GAS PIPE SIZE 2", WERE SHOWN.2" PVC | | | SLEEVE IN FLR, 1/2"CSST TUBING, NO JOINT | | | IN SLAB OR SLEEVE. | | | END OF COMMENTS PAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-10-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-02 |
Time |
10:35 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2001-10-02 |
Time |
10:35 |
Sent To |
|
|
| Notes |
| 2001-10-02 00:00:00 | DENIED | | | REFERENCE: SPC-94 - SGC-97 - FACBC-97 | | | | | | 1) PAGE A5, SANITARY RISER VENT REQUIRED | | | BEFORE 1ST WAIT STATION. (SHOWN ON FLAT | | | DRAWING) SPC SEC 921.4.2 | | | 2) PAGE A5, COMBINATION WASTE AND VENT | | | FOR FLOOR SINKS AND HAND SINK AT BAR | | | AREA TO COMPLY WITH SEC 421.4. PIPE SIZE | | | TO BE AT LEAST 4" FOR MAIN HORIZONTAL | | | WASTE LINE. | | | 3) PAGE A5, WATER RISER, MAXIMUM FIX- | | | TURES ON 1/2" COLD WATER IS 2. SPC-94 | | | COUNTYWIDE AMENDMENTS SEC 607.7 | | | 4) PAGE A5, FLOOR DRAINS IN PUBLIC REST | | | ROOMS SHALL HAVE TRAP PRIMERS. SPC 94 | | | SEC 409.4.1.1 | | | 5) PAGE A5, UNIT #19 4 WELL STEAM TABLE | | | SHALL DRAIN INTO A FLOOR SINK NOT A | | | FLOOR DRAIN AS SHOWN ON GREASE RISER & | | | FLAT DRAWING. SPC-94 SEC 804.1 804.5 | | | 6) PAGE A1, SHOW DETAIL ON HDCP URNAL. | | | CLEAR FLOOR SPACE & HEIGHT PER FACBC-97 | | | SEC 4.18.2 & 4.18.3 | | | 7) PAGES C1 & A5, GREASE TRAP TO BE | | | SIZED BY UTILITY DEPT.PLEASE CONTACT | | | R. COMPO AT (561) 837-4074. | | | 8) PAGE A5, SEPARATE PERMIT REQUIRED FOR | | | GAS. SEE ATTACHED SHEET FOR INFORMATION | | | REQUIRED WITH PERMIT APPLICATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|