Plan Review Details - Permit 01090294
Plan Review Stops For Permit 01090294
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-10-30 Cont ID  
Sent By jwitmer Date 2001-10-30 Time 17:18 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-10-30 00:00:00PROVISO
 PERMIT # 01090294
 1649 FORUM PLACE
 BUILDING ASSOCIATES
 CELL 744-6741 - RICHARD PARKMAN
 PROVIDE PRODUCT APPROVAL FOR NEW GLASS
 / ALUM STOREFRONTJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-09-24 Cont ID  
Sent By jwitmer Date 2001-09-24 Time 10:12 Rev Time 0.00
Received By jwitmer Date 2001-09-24 Time 10:11 Sent To  
Notes
2001-09-24 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01090294
 1649 FORUM PLACE
 CONT: BUILDING ASSOCIATES INC
 TEL: (561) 746-3421
 CEL: (561) 310-5429
  
 SBC = STANDARD BUILDING CODE
  
 1)- SHEET A1 INDICATES EXTERIOR DOORS
 # 4,5 & 8. THERE IS NO PLOT PLAN, THE
 KEY PLAN DOESN'T INDICATE WHERE THE PROP
 ERTY LINE IS IN RELATIONSHIP WITH THESE
 OPENINGS. SBC 705 1.1.2. PROTECTION OF
 EXTERIOR WALL OPENINGS, EVERY EXTERIOR
 WALL OPENING WITHIN 15' OF THE PROPERTY
 LINE SHALL BE EQUIPPED WITH APPROVED
 OPENING PROTECTIVES.
  
 2)- SHEET A1 INDICATES THAT THERE WAS A
 DOORWAY BLOCKED IN AT APPROXIMATELY
 DOOR #5, IS DOORWAY #5 A NEW OPENING RE-
 QUIRING THE LINTEL? IF SO DO THE BLOCK
 CELLS ON EITHER SIDE OF THE DOORWAY
 REQUIRE REINFORCING?
  
 3)- SHEET A1 ALSO INDICATES THAT DOOR
 #4 IS TO BE REPLACED, WILL THE DOOR JAMB
 ALSO BE REPLACED?
  
 4)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 EXTERIOR DOOR ASSEMBLIES (DOOR & JAMBS)
 THAT ARE REPLACED SHALL COMPLY WITH
 WIND ZONE TESTING REQUIREMENT TESTING.
 110 MPH WIND ZONE. THE CITY ACCEPTS
 DADE COUNTY OR SBCCI TEST REPORTS,
 (2 COPIES).
  
 5)- SBC 1205 RODENT PROOFING, EXTERIOR
 WALL OPENINGS TO COMPLY WITH THIS SEC-
 TION OF THE CODE.
  
 6)- SHEET A1 INDICATES THAT THERE WILL
 BE NEW GLAZING (WINDOW) THE CITY SHALL
 REQUIRE PRODUCT TESTING REPORTS,THE TEST
 ING REPORT WILL NEED ONLY SHOW TESTING
 FOR WIND, SINCE LESS THAN 50% OF THE
 GLAZED OPENINGS ARE NOT BEING REPLACED
 THIS STRUCTURE DOES NOT REQUIRE NEED TO
 MEET THE REQUIREMENTS FOR LARGE MISSLE
 IMPACT GLAZING. SBC 1606.4/1707/4/1.
 CITY OFFICIAL INTERPRETATION (4).
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-25 Cont ID  
Sent By dpalmer Date 2001-10-25 Time 07:29 Rev Time 0.00
Received By dpalmer Date 2001-10-25 Time 07:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-10-02 Cont ID  
Sent By dpalmer Date 2001-10-02 Time 11:42 Rev Time 0.00
Received By dpalmer Date 2001-10-02 Time 11:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-10-16 Cont ID  
Sent By mcarsill Date 2001-10-16 Time 12:38 Rev Time 0.00
Received By mcarsill Date 2001-10-16 Time 12:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-09-10 Cont ID  
Sent By mcarsill Date 2001-09-10 Time 14:48 Rev Time 0.00
Received By mcarsill Date 2001-09-10 Time 14:48 Sent To  
Notes
2001-09-10 00:00:001) PLANS DO NOT INDICATE ANY WAITING
 SPACES. ARE ANY PLANNED AND IF SO WHERE
 WILL THIS LOCATION BE.
 2) PLEASE PROVIDE OCCUPANT LOAD
 CALCULATIONS TO INCLUDE THE NECESSARY
 STAFF NEEDED TO RUN ESTABLISHMENT.
 3) DOOR # 1 REQUIRED TO HAVE SIGNAGE
 "THESE DOORS TO REMAIN UNLOCKED DURING
 BUSINESS HOURS" WITH ONE INCH LETTERING
 ON A CONTRASTING BACKGROUND.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-04-24 Cont ID  
Sent By pkrauss Date 2002-04-24 Time 09:43 Rev Time 0.35
Received By pkrauss Date 2002-04-24 Time 09:17 Sent To  
Notes
2002-04-24 00:00:00MECHANICAL PERMIT 01121518
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION, & WALKIN COOLER/FREEZER
  
 TEST AND BALANCE REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.
  
 2001 FLORIDA BUILDING CODE, MECHANICAL
  
 PROVIDE AIR DUCT PATHWAYS OR AIR
 TRANSFER PATHWAYS FROM HIGH ZONES TO
 LOW ZONE. (BEDROOMS TO HALL).
 2001 FBC(M) 601.4, BALANCED AIR RETURN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-10-24 Cont ID  
Sent By pkrauss Date 2001-10-24 Time 13:06 Rev Time 0.35
Received By pkrauss Date 2001-10-24 Time 12:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-09-28 Cont ID  
Sent By pkrauss Date 2001-09-28 Time 11:15 Rev Time 1.00
Received By pkrauss Date 2001-09-28 Time 11:15 Sent To  
Notes
2001-09-28 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.PROVIDE AIR BALANCE SCHEDULE TO
 SHOW COMPLIANCE WITH 1997 SMC 501.2.
  
 2.PROVIDE DETAIL OF 6" GAS FLUE WITH
 TERMINATION LOCATION AT ROOF.
  
 ADDITIONAL PERMIT REQUIRED FOR HOOD,
 FIRE SUPRESSION AND WALK-IN COOLER.
 PLEASE PROVIDE PLANS AND MANUFACTUERER
 SUBMITTAL DATA/PRODUCT APPROVALS WITH
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-06-15 Cont ID  
Sent By kstevens Date 2002-06-15 Time 16:52 Rev Time 0.00
Received By kstevens Date 2002-06-15 Time 16:52 Sent To  
Notes
2002-06-15 00:00:00REVISION OK - SANT. RISER DIAGRAM - ADD
 FLOOR SINK FOR COND. FROM COOLER

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-10-28 Cont ID  
Sent By pschmitz Date 2001-10-28 Time 15:07 Rev Time 2.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-10-28 00:00:00PLUMBING PLAN REVIEW,RESUB PROVISO.
 SEE SHT A5.1 SEPERATE GAS PERMIT,ALSO
 GAS PIPE SIZE 2", WERE SHOWN.2" PVC
 SLEEVE IN FLR, 1/2"CSST TUBING, NO JOINT
 IN SLAB OR SLEEVE.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-02 Cont ID  
Sent By kstevens Date 2001-10-02 Time 10:35 Rev Time 1.25
Received By kstevens Date 2001-10-02 Time 10:35 Sent To  
Notes
2001-10-02 00:00:00DENIED
 REFERENCE: SPC-94 - SGC-97 - FACBC-97
  
 1) PAGE A5, SANITARY RISER VENT REQUIRED
 BEFORE 1ST WAIT STATION. (SHOWN ON FLAT
 DRAWING) SPC SEC 921.4.2
 2) PAGE A5, COMBINATION WASTE AND VENT
 FOR FLOOR SINKS AND HAND SINK AT BAR
 AREA TO COMPLY WITH SEC 421.4. PIPE SIZE
 TO BE AT LEAST 4" FOR MAIN HORIZONTAL
 WASTE LINE.
 3) PAGE A5, WATER RISER, MAXIMUM FIX-
 TURES ON 1/2" COLD WATER IS 2. SPC-94
 COUNTYWIDE AMENDMENTS SEC 607.7
 4) PAGE A5, FLOOR DRAINS IN PUBLIC REST
 ROOMS SHALL HAVE TRAP PRIMERS. SPC 94
 SEC 409.4.1.1
 5) PAGE A5, UNIT #19 4 WELL STEAM TABLE
 SHALL DRAIN INTO A FLOOR SINK NOT A
 FLOOR DRAIN AS SHOWN ON GREASE RISER &
 FLAT DRAWING. SPC-94 SEC 804.1 804.5
 6) PAGE A1, SHOW DETAIL ON HDCP URNAL.
 CLEAR FLOOR SPACE & HEIGHT PER FACBC-97
 SEC 4.18.2 & 4.18.3
 7) PAGES C1 & A5, GREASE TRAP TO BE
 SIZED BY UTILITY DEPT.PLEASE CONTACT
 R. COMPO AT (561) 837-4074.
 8) PAGE A5, SEPARATE PERMIT REQUIRED FOR
 GAS. SEE ATTACHED SHEET FOR INFORMATION
 REQUIRED WITH PERMIT APPLICATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377