Plan Review Details - Permit 01090276
| Plan Review Stops For Permit 01090276 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-12-31 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-31 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-31 |
Time |
09:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-12-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-17 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-18 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2001-12-18 00:00:00 | SEE MECHANICAL NOTES. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-09-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-09-12 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-09-12 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2001-09-12 00:00:00 | 1) WALL TERMINATIONS OF EXHAUST FANS | | | SHALL BE AT LEAST 10 FEET FROM ADJACENT | | | BUILDINGS, PROPERTY LINES, GRADE LEVELS, | | | COMBUSTIBLE CONSTRUCTION, ELECTRICAL | | | EQUIPMENT OR LINES, DOORS OR WINDOWS. | | | PER NFPA 96, WALL TERMINATIONS | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-12-31 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-31 |
Time |
10:48 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-12-31 |
Time |
10:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-12-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-12 |
Time |
10:09 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-12-12 |
Time |
09:59 |
Sent To |
FIRE |
|
| Notes |
| 2001-12-12 00:00:00 | ********************DENIED************** | | | | | | | | | 1.DUCT SYSTEM SHALL BE DESIGNED AND | | | INSTALLED IN A MANNER TO PROVIDE AN | | | AIR VELOCITY WITHIN THE DUCT SYSTEM | | | OF NOT LESS THAN 1,500 FT PER | | | MINUTE. | | | | | | PLAN SHEET 1 OF 2 INDICATES 1,489 | | | FPM. | | | | | | AS PER 1997 SMC 505.5.4, DUCTWORK | | | CONNECTED TO BOTH SIDES OF THE FAN SHALL | | | HAVE ACCESS FOR INSPECTION AND CLEANING | | | WITHIN 3 FT ON EACH SIDE OF THE FAN. | | | | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-09-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-12 |
Time |
08:44 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-09-12 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2001-09-12 00:00:00 | *******************PROVISO************** | | | | | | | | | EF-1 SHALL TERMINATE A MINIMUM OF 10' | | | ABOVE ADJOINING GRADE LEVEL, 10' FROM | | | ANY ADJACENT BUILDING, PARKING AREA, | | | PROPERTY LINE, WINDOW, DOOR, OR AIR | | | INTAKE. 1997 SMC 506.1. | | | | | | NFPA 96 4-8.3.1, THE CLOSET POINT OF ANY | | | WINDOW ABOVE EXHAUST SHALL BE A MINIMUM | | | OF 10' DISTANT, PLUS 0.25 FOR EACH ONE | | | DEGREE FROM HORIZONTAL, ANGLE BEING | | | MEASURED FROM THE CENTER OF THE EXHAUST | | | TERMINATION TO THE CENTER OF THE WINDOW. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
|