Plan Review Details - Permit 01090052
Plan Review Stops For Permit 01090052
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2002-11-15 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 06:17 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-11-15 00:00:00REVISION #9 DATED 11/12/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2002-10-28 Cont ID  
Sent By hpiskura Date 2002-10-28 Time 10:33 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-10-28 00:00:00RE: REVISIONS LABELED {7} AS BUILTS,
 DATED 9/30/02.
  
 PAGE ASI #002 "NEW 2X4 18 GA STEEL
 CHANELS ATTACHED WITH 1 5/8" SELF
 TAPPING SCREWS"
  
 WHAT ARE THEY ATTACHED TO? IT APPEARS
 THAT THEY ARE LAYING ON TOP OF A PIECE
 GYPSUM.WHAT IS THE SPACING?SPAN?
  
 ASI 003 AND 004, SAME.PLEASE PROVIDE
 SPECIFIC DESIGN INFORMATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2002-08-22 Cont ID  
Sent By hpiskura Date 2002-08-22 Time 09:20 Rev Time 0.00
Received By hpiskura Date 2002-08-22 Time 09:00 Sent To  
Notes
2002-08-22 00:00:00REVISION #6 DATED 7/31/02
  
 SHEET A2.1, THE DOOR SHOWN AS (204)
 SERVING MECHANICAL ROOM (206) DOES NOT
 COMPLY WITH FBC 1012.1.4.PLEASE REVISE
 AS NECESSARY.
  
 SHEET A5.1, SHOW SPECIFIC CONNECTION
 DETAILS FOR THE ATTACHMENT OF THE
 SOFFIT TO THE STRUCTURE ABOVE AND A
 FRAMING LAYOUT.SEE FBC 104.2.1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-06-25 Cont ID  
Sent By jwitmer Date 2002-06-25 Time 07:17 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-06-25 00:00:00REVISIONS 6/11/02JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2002-01-25 Cont ID  
Sent By hpiskura Date 2002-01-25 Time 11:32 Rev Time 0.00
Received By hpiskura Date 2002-01-25 Time 11:23 Sent To  
Notes
2002-01-25 00:00:00NO CHANGES FROM PREVIOUS REVIEW, SAME PL
 ANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-01-03 Cont ID  
Sent By jwitmer Date 2002-01-03 Time 13:06 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-11-20 Cont ID  
Sent By jwitmer Date 2001-11-20 Time 07:23 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-09-24 Cont ID  
Sent By jwitmer Date 2001-09-24 Time 06:49 Rev Time 5.00
Received By jwitmer Date 2001-09-24 Time 06:49 Sent To  
Notes
2001-09-24 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01090052
 314 CLEMATIS ST
 CONT : ITASCA CON
 (561) 241-4999
  
 TYPE V PROTECTED/SPRINKLERED
  
 COMMENT ON TENANT BUILDOUT!!! FUTURE
 TENANT BUILDOUT SPACE 210 IF SPACE IS
 SUBDIVIDED INTO SMALLER TENANT SPACES
 THERE MAYBE A PROBLEM, SBC 1020.1 SINGLE
 EXIT REQUIREMENTS, 75' MAXIMUM TRAVEL
 DISTANCE TO A SINGLE EXIT.
  
 1)- SHEET A2.1 DOORS 202,203,205,207&
 211 REQUIRE A RATING, NOT GIVEN?
 2)- DOOR 203 ELEVATOR MACHINE ROOM
 RATING?
 3)- STAIRWELL (201) REQUIRES A 1 HR EN-
 CLOSURE, IT IS A REQUIRED EXIT. BY DEFIN
 ITION, EXIT: THAT PORTION OF A MEANS OF
 EGRESS WHICH IS SEPERATED FROM ALL OTHER
 SPACES OF A BUILDING OR STRUCTURE BY
 CONSTRUCTION AND OPENING PROTECTIVES, AS
 REQUIRED FOR EXITS, TO PROVIDE A PROTECT
 ED WAY OF TRAVEL TO THE EXIT DISCHARGE.
 SBC 3003.1.4. ELEVATORS SHALL NOT BE IN
 A COMMON ENCLOSING SHAFT, AND THE PATH
 OF TRAVEL FROM ONE FLIGHT OF STAIRS TO
 THE NEXT SHALL NOT PASS DIRECTLY IN
 FRONT OF THE ELEVATOR DOORS.
 SEE 3003.1.5 ELEVATOR LOBBY EXCEPTION!
 4)-SHEET A2.1 WALL "A", A6.0 WALL SCHEDU
 LE INDICATES TEST UL: U-465 1 HR RATING
 S-2 INDICATES 18 GAUGE "FLEXIBLE" TOP &
 BOTTOM TRACK, DOES THE "FLEXIBLE TRACK"
 HAVE A UL RATING?
 5)- A2.2 DETAIL 3 RESTROOMS SEE ATTACHED
 DRAWINGS FOR NOTICE OF CHANGE TO THE
 FL ACCESSIBILITY CODE FOR HANDICAPPED
 RESTROOMS FIGURE 30(E).
 6)- SBC 1204.2 RESTROOMS FOR PUBLIC USE.
 THE WALLS & FLOORS OF ALL RESTROOMS
 (PUBLIC) SHALL BE LINED WITH NONABSORB-
 ANT MATERIALS TO A HEIGTH OF 4 FT ABOVE
 THE FLOOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X 8412

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2002-11-15 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 06:17 Rev Time 0.50
Received By dpalmer Date 2002-11-15 Time 06:17 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-08-21 Cont ID  
Sent By dpalmer Date 2002-08-21 Time 19:59 Rev Time 0.00
Received By dpalmer Date 2002-08-21 Time 20:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-01-31 Cont ID  
Sent By dpalmer Date 2002-01-31 Time 16:16 Rev Time 0.00
Received By dpalmer Date 2002-01-31 Time 16:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-12-13 Cont ID  
Sent By dpalmer Date 2001-12-13 Time 12:46 Rev Time 0.00
Received By dpalmer Date 2001-12-13 Time 12:46 Sent To  
Notes
2001-12-13 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE TAPPING A TAP FROM
 MAIN GUTTER TO OTHER GUTTER. 240-21
  
 2)NOTE: PLEASE NOTE SIZECONDUCTORS
 IN MAIN GUTTER IS NOT SHOWN.
  
 3)NOTE: PLEASE STILL NEED TO CLARIFY
 HOW CONDUCTORSARE COMING IN FROM
 OUTSIDE? ROOM TENDS TO SIT BACK IN FROM
 OUTSIDE WALL AND NO MORE THAN 8' OF UN-
 -PROTECTEDPER LOCAL AMENDMENTS.
  
 4)NOTE: PLEASE NOTE THE SIZE OF GROUND-
 -ING ELECTRODE CONDUCTOR PER 250-66
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-11-07 Cont ID  
Sent By dpalmer Date 2001-11-07 Time 22:08 Rev Time 0.00
Received By dpalmer Date 2001-11-07 Time 22:08 Sent To  
Notes
2001-11-07 00:00:00******************** UNSAT ***********
  
 1)NOTE: PLEASE NOTE THAT THE RISER
 DIAGRAM SUBMITTED SHOWS AN OVERHEAD
 SERVICE? PLEASE CLARIFY? PLANS
 SHOW NEW SERVICE IN EXISTING ELECTRICAL
 ROOM UPSTAIRS, SHOW HOW SERVICE IS
 COMING IN THROUGH WALLS AND OTHER SPACE
 SHOWN BEHIND SERVICE WALL?
  
 2)NOTE: PLEASE NOTE THAT A NEW CAN ONLY
 BE ADDED IF ITEMS IN 230-2 ARE MET.
 PLANS DO NOT SHOW ENOUGH DETAIL FOR THIS
 ? THE EXSITING SERVICE SIZE IS NOT LARGE
 ENOUGH? DOES NOT SHOW VOLTAGE? PHASES?
 PLEASE NOTE I CANNOT FIND WHERE PLANS DE
 TAIL A 2HR SEPARATION BETWEEN EXSITING
 AND NEW AREA IN ORDER FOR IT TO BE
 CONSIDERED A SEPARTE BLDG FOR A NEW
 SERVICE.
  
 3)NOTE: PLEASE CALRIFY WHERE NEW METERS
 AND DISCONNECTS ARE? PLEASE SEE E-3
 ELEC ROOM ONLY SHOWS HOUSE PANEL?
  
 4)NOTE: PLEASE CLARIFY HOW CONDUITS ARE
 GOING TO RUN TO TENANTS 1&2. IF THROUGH
 STAIRS/EXIT CORRIDOR, THEN REQ`MENTS FOR
 FIRE PLAN REVIEW MUST BE SHOWN. PLEASE
 SEE FIRE REVIEW FOR THIS. EXT 8497
  
 5)NOTE: PLEASE CLARIFY LOAD FOR NEW
 ELEVATOR LOAD ON HOUSE PANEL? SHOWN AS
 1-POLE 20A 1KW LOAD ?
  
  
 6)NOTE: PLEASE CLARIFY EQUIPMENT GROUND-
 ING CONDUCTOR BETWEEN MAINS AND PANELS.
 250-122
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW, IF THERE ARE ANY QUESTIONS,OR
 IF A MEETING WOULD LIKE TO BE SET UP TO
 GO OVER ANY ITEMS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-09-18 Cont ID  
Sent By dpalmer Date 2001-09-18 Time 18:12 Rev Time 0.00
Received By dpalmer Date 2001-09-18 Time 18:11 Sent To  
Notes
2001-09-18 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE CLARIFY SERVICE ENTRANCE
 CONDUCTORS? RISER SHOWS OH SERV AND
 SERVICE BEING INSIDE? SERVICE IS SHOWN
 ON SECOND FLOOR IN ROOM.? PLEASE CALRIFY
 PLEASE ALSO CLARIFY 2HR MEANS OF
 SEPARATION REQ`D FOR ADDITIONAL SERVICE
 UNDER 230-2. PIPE SHOWN GOING THROUGH
 EXISTING SEPARATE BLDG. 230-3.
  
 2)NOTE: PLEASE NOTE THAT ELECTRICAL ROOM
 WOULD REQ` 2HR SEPARATION FROM EXISTING
 SPACE FOR NEW SERVICE BEING ADDED.
 BLDG CODE AND FIRE CODE
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2002-08-29 Cont ID  
Sent By mcarsill Date 2002-08-29 Time 17:12 Rev Time 0.00
Received By mcarsill Date 2002-08-29 Time 17:12 Sent To  
Notes
2002-08-29 00:00:001) MECHANICAL DOOR SWINGS TOO FAR INTO
 THE EXIT CORRIDOR. PLEASE REVISE
 AS NECESSARY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-02-06 Cont ID  
Sent By mcarsill Date 2002-02-06 Time 13:56 Rev Time 0.00
Received By mcarsill Date 2002-02-06 Time 13:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-12-12 Cont ID  
Sent By mcarsill Date 2001-12-12 Time 14:55 Rev Time 0.00
Received By mcarsill Date 2001-12-12 Time 14:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-11-14 Cont ID  
Sent By mcarsill Date 2001-11-14 Time 11:33 Rev Time 0.00
Received By mcarsill Date 2001-11-14 Time 11:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-09-05 Cont ID  
Sent By mcarsill Date 2001-09-05 Time 12:22 Rev Time 0.00
Received By mcarsill Date 2001-09-05 Time 12:22 Sent To  
Notes
2001-09-05 00:00:001) PLEASE EXPLAIN HOW STOREFRONT DOORS
 WILL MEET THE REQUIREMENTS FOR AT
 LEAST 20 MINUTE FIRE RATINGS.
 2) STAIRS PROVIDING EXITING SHALL BE
 ENCLOSED BY AT LEAST A ONE HOUR
 FIRE SEPARATION.
 3) NO INTERIOR FINISH CLASSIFICATION
 INFORMATION PROVIDED FOR WALLS AND
 CEILINGS.
 4) EXITS FOR PROPOSED TENANT SPACE #1
 ARE NOT PROPERLY SEPARATED FROM ONE
 ANOTHER BY DISTANCE AS REQUIRED BY
 FIRE CODE REQUIREMENTS.
 5) WILL THE SECOND FLOOR HAVE A SINGLE
 OR MULTIPLE TENANTS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2002-08-22 Cont ID  
Sent By pkrauss Date 2002-08-22 Time 12:45 Rev Time 0.45
Received By pkrauss Date 2002-08-22 Time 10:16 Sent To  
Notes
2002-08-22 00:00:00AS BUILT REVISIONS

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-02-01 Cont ID  
Sent By pkrauss Date 2002-02-01 Time 11:24 Rev Time 0.45
Received By pkrauss Date 2002-02-01 Time 10:57 Sent To  
Notes
2002-02-01 00:00:00 
 PROVISO: (MECHANICAL PERMIT 01090064)
  
 PROVIDE MANUFACTURER SUBMITTAL DATA FOR
 THE CONDENSATE PUMP PRIOR TO INSPECTION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2001-12-14 Cont ID  
Sent By pkrauss Date 2001-12-14 Time 15:40 Rev Time 0.35
Received By pkrauss Date 2001-12-14 Time 15:39 Sent To  
Notes
2001-12-14 00:00:00*******************DENIED***************
  
  
 PROVSIOUS COMMENTS NEVER ADDRESSED.
 SEE COMMENTS DATED FROM 9-24-01.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-11-16 Cont ID  
Sent By pkrauss Date 2001-11-16 Time 10:24 Rev Time 0.40
Received By pkrauss Date 2001-11-16 Time 10:24 Sent To  
Notes
2001-11-16 00:00:00*******************DENIED***************
  
  
 SEE COMMENTS FROM REVIEW DATED 9/24/01

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-09-24 Cont ID  
Sent By pkrauss Date 2001-09-24 Time 13:57 Rev Time 1.00
Received By pkrauss Date 2001-09-24 Time 13:13 Sent To  
Notes
2001-09-24 00:00:00********************DENIED**************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.FIRE DAMPERS ARE REQUIRED FOR DUCTS
 THAT PENETRATE A WALL OR PARTITION
 WITH A FIRE RESISTANCE RATING OF 1
 HOUR OR MORE.
  
 2.FIRE DAMPERS ARE ALSO REQUIRED FOR
 DUCTS PENETRATING ONLY ONE FLOOR OF
 A BUILDING REQUIRING THE PROTECTION
 OF VERTICAL OPENINGS WHEN THE DUCT
 IS NOT PROTECTED BY A SHAFT
 ENCLOSURE.
  
 3.FIRE DAMPER LOCATIONS SHALL BE
 IDENTIFIED ON THE PLAN.
  
 4.FIRE DAMPERS SHALL COMPLY WITH THE
 REQUIREMENTS OF UL 555 AND SHALL
 BEAR THE LABEL OF AN APPROVED
 TESTING AGENCY.
  
 5.PLEASE PROVIDE A DETAIL OF FIRE
 DAMPER INSTALLATION.
  
 6.PLEASE IDENTIFY CONDENSATE ON PLAN.
 AS PER AMENDED 1994 SPC 804.3, UNITS
 LARGER THAN 3 TONS SHALL TERMINATE
 INTO STORM DRAIN OR AN APPROVED
 DRYWELL.
  
 NOTE:FAN SHUTDOWN BY DUCT SMOKE
 DETECTOR SHALL HAVE NOTIFICATION
 TO ALARM/STROBE IN NORMALLY
 OCCUPIED AREAS. NFPA 90A 4-4.4.3.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop P PLUMBING
Rev No 7 Status P Date 2002-10-23 Cont ID  
Sent By pschmitz Date 2002-10-23 Time 07:54 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-10-23 00:00:00REVISION FOR F/D IN WOMENS REST RM, PES

Review Stop P PLUMBING
Rev No 6 Status F Date 2002-08-26 Cont ID  
Sent By kstevens Date 2002-08-26 Time 08:17 Rev Time 0.00
Received By kstevens Date 2002-08-26 Time 08:12 Sent To  
Notes
2002-08-26 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) FLOOR DRAIN IN WOMENS TOILET ROOM NOT
 VENTED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 5 Status P Date 2002-02-08 Cont ID  
Sent By kstevens Date 2002-02-08 Time 14:01 Rev Time 1.50
Received By kstevens Date 2002-02-08 Time 14:01 Sent To  
Notes
2002-02-08 00:00:00PROVISO: WATER HAMMER ARRESTORS SHALL BE
 LOCATED NEAR FIXTURES NOT AT TOP OF DROP

Review Stop P PLUMBING
Rev No 4 Status F Date 2002-01-31 Cont ID  
Sent By kstevens Date 2002-01-31 Time 18:58 Rev Time 1.00
Received By kstevens Date 2002-01-31 Time 18:58 Sent To  
Notes
2002-01-31 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT P-2 WATER RISER DIAGRAM, AIR
 CHAMBER DETAIL NOT SHOWN AS REQUSTED IN
 LAST REVIEW. SEE SHEET PROVIDED AND GIVE
 DETAILS ON PLANS FOR VALVES IN AIR
 CHAMBERS.
 2) SHT P-2 PREVIOUS COMMENTS NOT ADDRESS
 ED PROPERLY. VENT FOR DOUBLE LAV IS
 STILL GOING UP AND THEN BACK DOWN. THIS
 IS NOT ACCEPTABLE.
 3) SHT P-2 WATER HEATER EMERGENCY PAN
 DRAIN SHALL BE 1" NOT 3/4" AS SHOWN.
 SPC SEC 507.8.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-01-07 Cont ID  
Sent By kstevens Date 2002-01-07 Time 18:15 Rev Time 1.00
Received By kstevens Date 2002-01-07 Time 18:15 Sent To  
Notes
2002-01-07 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) PER PREVIOUS REVIEW SHT P-2 AIR
 CHAMBERS SHALL BE ACCESSIBLE AND RECHARG
 EABLE PER WH-PDI 201 SPC SEC 607.8.3.
 SEE ATTACHED SHEET FOR APPROVED AIR
 CHAMBERS. SHOW DETAIL ON PLANS IF USING
 AIR CHAMBERS.
  
 2) PER PREVIOUS REVIEW SHT P-2 VENT NOT
 APPROVED. VENT FOR DOUBLE LAV IN WOMENS
 RESTROOM RISES AND THEN DROPS DOWN INTO
 VENT HEADER. THIS IS NOT A LEGAL VENT.
  
 3) PER PREVIOUS REVIEW SHT P-2 PAN DRAIN
 NOT SHOWN. PLUMBING NOTES #27 NOT APPRO-
 VED. SPC SEC 507.8.3 - 507.8.4 RELIEF
 LINE AND PAN DRAIN LINE TO BE PIPED FULL
 SIZE SEPARATELY AND TERMINATE NO LESS
 THAN 6" ABOVE GROUND.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-11-13 Cont ID  
Sent By kstevens Date 2001-11-13 Time 15:55 Rev Time 0.75
Received By kstevens Date 2001-11-13 Time 15:55 Sent To  
Notes
2001-11-13 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PAGE P-2, SANT RISER DIAGRAM. URNAL
 SHALL BE WALL MOUNT NOT FLOOR MOUNT AS
 SHOWN ON RISER. DRINKING FOUNTAIN SHOWN
 ON MENS SIDE OF ALCOVE ON FLOOR PLAN AND
 ON WOMENS SIDE ON RISER. PLEASE CLARIFY.
 2) PAGE P-2, WATER RISER DIAGRAM. DOUBLE
 LAV SHOWN IN MENS ROOM AND DRINKING
 FOUNTAIN SHOWN ON WOMENS SIDE. AIR CHAM-
 BERS ARE QUICK FIX AND REQUIRE ACCESS &
 SHALL BE RECHARGEABLE PER SPC SEC 607.8.
 3. AND PER PDI-WH 201. IF WATER HAMMER
 ARRESTORS ARE USED THEY SHALL BE SIZED &
 LOCATED PER MANUFACTURE INSTALLATION IN-
 STRUCTIONS AND PDI-WH 201. NOT LOCATED
 ON TOP OF DROP AS SHOWN.
 4) PAGE P-2 VENT ON SANT. RISER DIAGRAM
 SHALL NOT GO UP - OVER - & DOWN AS SHOWN
 FOR LAV IN WOMENS ROOM.
 5) PAGE P-2 PLEASE INDICATE WHERE AND
 HOW THE PAN DRAIN AND T&P TERMINATE FROM
 WATER HEATER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-09-12 Cont ID  
Sent By kstevens Date 2001-09-12 Time 16:40 Rev Time 1.75
Received By kstevens Date 2001-09-12 Time 16:39 Sent To  
Notes
2001-09-12 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PAGES A2.0 & A2.2 DETAIL 3 RESTROOM
 PLAN. 3 LAVS REQUIRED IN WOMEN'S REST-
 ROOM PER SPC-94 TABLE 407.
 2) PAGE A2.2 DETAIL 3 RESTROOM PLAN.
 HDCP STALL NOT WIDE ENOUGH. SHOWS 6'0"
 AND IT SHOULD BE 7'0" PER FACBC-97, FIG.
 30(E).
 3) PAGE A2.2 DETAIL 7 RESTROOM ELEVATION
 URNAL TO COMPLY WITH FACBC-97 SECTIONS
 4.22.5 & 4.18.2. 17" TO LIP ECT.
 4) PAGE A2.2 DETAIL 4 RESTROOM ENTRANCE
 ELEVATION. 1 DRINKING FOUNTAIN SHALL
 COMPLY WITH FACBC-97 SECT. 4.15, AND 1
 DRINKING FOUNTAIN SHALL COMPLY WITH
 FACBC-97 SECT. 4.1.3(10).
 5) PAGE P2 SANITARY RISER DIAGRAM. URNAL
 NOT SHOWN ON RISER DIAGRAM.
 6) PAGE P2 WATER RISER DIAGRAM AND PLUMB
 ING NOTES #13. AIR CHAMBERS TO COMPLY
 WITH SPC-94 SECT. 607.8.2 & 607.8.3.
 ACCESSABLE AND RECHARGABLE. IF WATER
 HAMMER ARRESTORS ARE USED, THEY SHALL
 COMPLY WITH MANUFACTURE INSTALLATION IN-
 STRUCTIONS AND WH-PDI 201 FOR SIZING AND
 LOCATION. THEY ARE NOT LOCATED AT TOP OF
 RISERS OR DROPS.
 7) PAGE P2 WATER HEATER DETAIL. SHUT OFF
 VALVE SHALL BE LOCATED CLOSE TO HEATER.
 (ACCESSABLE).
 8) SHOW LOCATION OF WATER HEATER. PAN
 DRAIN TO BE 1", AND RELIEF VALVE DIS-
 CHARGE SHALL BE FULL SIZED SEPARATLY TO
 THE OUTSIDE OF THE BUILDING AND SHALL
 TERMINATE 6" ABOVE GRADE. SPC-94 SECTS.
 507.8.2 & 507.8.4
  
 REVIEW BY KEN STEVENS
 (561) 569-8096 EXT. 8377