| Plan Review Stops For Permit 01090052 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2002-11-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-11-15 |
Time |
06:17 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-11-15 00:00:00 | REVISION #9 DATED 11/12/02 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2002-10-28 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-10-28 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-10-28 00:00:00 | RE: REVISIONS LABELED {7} AS BUILTS, | | | DATED 9/30/02. | | | | | | PAGE ASI #002 "NEW 2X4 18 GA STEEL | | | CHANELS ATTACHED WITH 1 5/8" SELF | | | TAPPING SCREWS" | | | | | | WHAT ARE THEY ATTACHED TO? IT APPEARS | | | THAT THEY ARE LAYING ON TOP OF A PIECE | | | GYPSUM.WHAT IS THE SPACING?SPAN? | | | | | | ASI 003 AND 004, SAME.PLEASE PROVIDE | | | SPECIFIC DESIGN INFORMATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2002-08-22 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-08-22 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-08-22 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2002-08-22 00:00:00 | REVISION #6 DATED 7/31/02 | | | | | | SHEET A2.1, THE DOOR SHOWN AS (204) | | | SERVING MECHANICAL ROOM (206) DOES NOT | | | COMPLY WITH FBC 1012.1.4.PLEASE REVISE | | | AS NECESSARY. | | | | | | SHEET A5.1, SHOW SPECIFIC CONNECTION | | | DETAILS FOR THE ATTACHMENT OF THE | | | SOFFIT TO THE STRUCTURE ABOVE AND A | | | FRAMING LAYOUT.SEE FBC 104.2.1. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2002-06-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-06-25 |
Time |
07:17 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-06-25 00:00:00 | REVISIONS 6/11/02JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
N |
Date |
2002-01-25 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-01-25 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-01-25 |
Time |
11:23 |
Sent To |
|
|
| Notes |
| 2002-01-25 00:00:00 | NO CHANGES FROM PREVIOUS REVIEW, SAME PL | | | ANS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-01-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-01-03 |
Time |
13:06 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-11-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-11-20 |
Time |
07:23 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-09-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-09-24 |
Time |
06:49 |
Rev Time |
5.00 |
| Received By |
jwitmer |
Date |
2001-09-24 |
Time |
06:49 |
Sent To |
|
|
| Notes |
| 2001-09-24 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01090052 | | | 314 CLEMATIS ST | | | CONT : ITASCA CON | | | (561) 241-4999 | | | | | | TYPE V PROTECTED/SPRINKLERED | | | | | | COMMENT ON TENANT BUILDOUT!!! FUTURE | | | TENANT BUILDOUT SPACE 210 IF SPACE IS | | | SUBDIVIDED INTO SMALLER TENANT SPACES | | | THERE MAYBE A PROBLEM, SBC 1020.1 SINGLE | | | EXIT REQUIREMENTS, 75' MAXIMUM TRAVEL | | | DISTANCE TO A SINGLE EXIT. | | | | | | 1)- SHEET A2.1 DOORS 202,203,205,207& | | | 211 REQUIRE A RATING, NOT GIVEN? | | | 2)- DOOR 203 ELEVATOR MACHINE ROOM | | | RATING? | | | 3)- STAIRWELL (201) REQUIRES A 1 HR EN- | | | CLOSURE, IT IS A REQUIRED EXIT. BY DEFIN | | | ITION, EXIT: THAT PORTION OF A MEANS OF | | | EGRESS WHICH IS SEPERATED FROM ALL OTHER | | | SPACES OF A BUILDING OR STRUCTURE BY | | | CONSTRUCTION AND OPENING PROTECTIVES, AS | | | REQUIRED FOR EXITS, TO PROVIDE A PROTECT | | | ED WAY OF TRAVEL TO THE EXIT DISCHARGE. | | | SBC 3003.1.4. ELEVATORS SHALL NOT BE IN | | | A COMMON ENCLOSING SHAFT, AND THE PATH | | | OF TRAVEL FROM ONE FLIGHT OF STAIRS TO | | | THE NEXT SHALL NOT PASS DIRECTLY IN | | | FRONT OF THE ELEVATOR DOORS. | | | SEE 3003.1.5 ELEVATOR LOBBY EXCEPTION! | | | 4)-SHEET A2.1 WALL "A", A6.0 WALL SCHEDU | | | LE INDICATES TEST UL: U-465 1 HR RATING | | | S-2 INDICATES 18 GAUGE "FLEXIBLE" TOP & | | | BOTTOM TRACK, DOES THE "FLEXIBLE TRACK" | | | HAVE A UL RATING? | | | 5)- A2.2 DETAIL 3 RESTROOMS SEE ATTACHED | | | DRAWINGS FOR NOTICE OF CHANGE TO THE | | | FL ACCESSIBILITY CODE FOR HANDICAPPED | | | RESTROOMS FIGURE 30(E). | | | 6)- SBC 1204.2 RESTROOMS FOR PUBLIC USE. | | | THE WALLS & FLOORS OF ALL RESTROOMS | | | (PUBLIC) SHALL BE LINED WITH NONABSORB- | | | ANT MATERIALS TO A HEIGTH OF 4 FT ABOVE | | | THE FLOOR. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096X 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2002-11-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-11-15 |
Time |
06:17 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2002-11-15 |
Time |
06:17 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2002-08-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-08-21 |
Time |
19:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-08-21 |
Time |
20:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2002-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-01-31 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-01-31 |
Time |
16:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2001-12-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-13 |
Time |
12:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-13 |
Time |
12:46 |
Sent To |
|
|
| Notes |
| 2001-12-13 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE TAPPING A TAP FROM | | | MAIN GUTTER TO OTHER GUTTER. 240-21 | | | | | | 2)NOTE: PLEASE NOTE SIZECONDUCTORS | | | IN MAIN GUTTER IS NOT SHOWN. | | | | | | 3)NOTE: PLEASE STILL NEED TO CLARIFY | | | HOW CONDUCTORSARE COMING IN FROM | | | OUTSIDE? ROOM TENDS TO SIT BACK IN FROM | | | OUTSIDE WALL AND NO MORE THAN 8' OF UN- | | | -PROTECTEDPER LOCAL AMENDMENTS. | | | | | | 4)NOTE: PLEASE NOTE THE SIZE OF GROUND- | | | -ING ELECTRODE CONDUCTOR PER 250-66 | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-11-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-07 |
Time |
22:08 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-07 |
Time |
22:08 |
Sent To |
|
|
| Notes |
| 2001-11-07 00:00:00 | ******************** UNSAT *********** | | | | | | 1)NOTE: PLEASE NOTE THAT THE RISER | | | DIAGRAM SUBMITTED SHOWS AN OVERHEAD | | | SERVICE? PLEASE CLARIFY? PLANS | | | SHOW NEW SERVICE IN EXISTING ELECTRICAL | | | ROOM UPSTAIRS, SHOW HOW SERVICE IS | | | COMING IN THROUGH WALLS AND OTHER SPACE | | | SHOWN BEHIND SERVICE WALL? | | | | | | 2)NOTE: PLEASE NOTE THAT A NEW CAN ONLY | | | BE ADDED IF ITEMS IN 230-2 ARE MET. | | | PLANS DO NOT SHOW ENOUGH DETAIL FOR THIS | | | ? THE EXSITING SERVICE SIZE IS NOT LARGE | | | ENOUGH? DOES NOT SHOW VOLTAGE? PHASES? | | | PLEASE NOTE I CANNOT FIND WHERE PLANS DE | | | TAIL A 2HR SEPARATION BETWEEN EXSITING | | | AND NEW AREA IN ORDER FOR IT TO BE | | | CONSIDERED A SEPARTE BLDG FOR A NEW | | | SERVICE. | | | | | | 3)NOTE: PLEASE CALRIFY WHERE NEW METERS | | | AND DISCONNECTS ARE? PLEASE SEE E-3 | | | ELEC ROOM ONLY SHOWS HOUSE PANEL? | | | | | | 4)NOTE: PLEASE CLARIFY HOW CONDUITS ARE | | | GOING TO RUN TO TENANTS 1&2. IF THROUGH | | | STAIRS/EXIT CORRIDOR, THEN REQ`MENTS FOR | | | FIRE PLAN REVIEW MUST BE SHOWN. PLEASE | | | SEE FIRE REVIEW FOR THIS. EXT 8497 | | | | | | 5)NOTE: PLEASE CLARIFY LOAD FOR NEW | | | ELEVATOR LOAD ON HOUSE PANEL? SHOWN AS | | | 1-POLE 20A 1KW LOAD ? | | | | | | | | | 6)NOTE: PLEASE CLARIFY EQUIPMENT GROUND- | | | ING CONDUCTOR BETWEEN MAINS AND PANELS. | | | 250-122 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW, IF THERE ARE ANY QUESTIONS,OR | | | IF A MEETING WOULD LIKE TO BE SET UP TO | | | GO OVER ANY ITEMS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-09-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-09-18 |
Time |
18:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-09-18 |
Time |
18:11 |
Sent To |
|
|
| Notes |
| 2001-09-18 00:00:00 | ****************** UNSAT ************** | | | | | | 1)NOTE: PLEASE CLARIFY SERVICE ENTRANCE | | | CONDUCTORS? RISER SHOWS OH SERV AND | | | SERVICE BEING INSIDE? SERVICE IS SHOWN | | | ON SECOND FLOOR IN ROOM.? PLEASE CALRIFY | | | PLEASE ALSO CLARIFY 2HR MEANS OF | | | SEPARATION REQ`D FOR ADDITIONAL SERVICE | | | UNDER 230-2. PIPE SHOWN GOING THROUGH | | | EXISTING SEPARATE BLDG. 230-3. | | | | | | 2)NOTE: PLEASE NOTE THAT ELECTRICAL ROOM | | | WOULD REQ` 2HR SEPARATION FROM EXISTING | | | SPACE FOR NEW SERVICE BEING ADDED. | | | BLDG CODE AND FIRE CODE | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE NAY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
F |
Date |
2002-08-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-08-29 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-08-29 |
Time |
17:12 |
Sent To |
|
|
| Notes |
| 2002-08-29 00:00:00 | 1) MECHANICAL DOOR SWINGS TOO FAR INTO | | | THE EXIT CORRIDOR. PLEASE REVISE | | | AS NECESSARY. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2002-02-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-02-06 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-02-06 |
Time |
13:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-12-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-12 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-12 |
Time |
14:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-11-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-14 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-14 |
Time |
11:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-09-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-09-05 |
Time |
12:22 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-09-05 |
Time |
12:22 |
Sent To |
|
|
| Notes |
| 2001-09-05 00:00:00 | 1) PLEASE EXPLAIN HOW STOREFRONT DOORS | | | WILL MEET THE REQUIREMENTS FOR AT | | | LEAST 20 MINUTE FIRE RATINGS. | | | 2) STAIRS PROVIDING EXITING SHALL BE | | | ENCLOSED BY AT LEAST A ONE HOUR | | | FIRE SEPARATION. | | | 3) NO INTERIOR FINISH CLASSIFICATION | | | INFORMATION PROVIDED FOR WALLS AND | | | CEILINGS. | | | 4) EXITS FOR PROPOSED TENANT SPACE #1 | | | ARE NOT PROPERLY SEPARATED FROM ONE | | | ANOTHER BY DISTANCE AS REQUIRED BY | | | FIRE CODE REQUIREMENTS. | | | 5) WILL THE SECOND FLOOR HAVE A SINGLE | | | OR MULTIPLE TENANTS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2002-08-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-08-22 |
Time |
12:45 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-08-22 |
Time |
10:16 |
Sent To |
|
|
| Notes |
| 2002-08-22 00:00:00 | AS BUILT REVISIONS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2002-02-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-01 |
Time |
11:24 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-02-01 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2002-02-01 00:00:00 | | | | PROVISO: (MECHANICAL PERMIT 01090064) | | | | | | PROVIDE MANUFACTURER SUBMITTAL DATA FOR | | | THE CONDENSATE PUMP PRIOR TO INSPECTION. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2001-12-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-14 |
Time |
15:40 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-12-14 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2001-12-14 00:00:00 | *******************DENIED*************** | | | | | | | | | PROVSIOUS COMMENTS NEVER ADDRESSED. | | | SEE COMMENTS DATED FROM 9-24-01. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-11-16 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-16 |
Time |
10:24 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-11-16 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2001-11-16 00:00:00 | *******************DENIED*************** | | | | | | | | | SEE COMMENTS FROM REVIEW DATED 9/24/01 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-09-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-24 |
Time |
13:57 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2001-09-24 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2001-09-24 00:00:00 | ********************DENIED************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW: | | | | | | 1.FIRE DAMPERS ARE REQUIRED FOR DUCTS | | | THAT PENETRATE A WALL OR PARTITION | | | WITH A FIRE RESISTANCE RATING OF 1 | | | HOUR OR MORE. | | | | | | 2.FIRE DAMPERS ARE ALSO REQUIRED FOR | | | DUCTS PENETRATING ONLY ONE FLOOR OF | | | A BUILDING REQUIRING THE PROTECTION | | | OF VERTICAL OPENINGS WHEN THE DUCT | | | IS NOT PROTECTED BY A SHAFT | | | ENCLOSURE. | | | | | | 3.FIRE DAMPER LOCATIONS SHALL BE | | | IDENTIFIED ON THE PLAN. | | | | | | 4.FIRE DAMPERS SHALL COMPLY WITH THE | | | REQUIREMENTS OF UL 555 AND SHALL | | | BEAR THE LABEL OF AN APPROVED | | | TESTING AGENCY. | | | | | | 5.PLEASE PROVIDE A DETAIL OF FIRE | | | DAMPER INSTALLATION. | | | | | | 6.PLEASE IDENTIFY CONDENSATE ON PLAN. | | | AS PER AMENDED 1994 SPC 804.3, UNITS | | | LARGER THAN 3 TONS SHALL TERMINATE | | | INTO STORM DRAIN OR AN APPROVED | | | DRYWELL. | | | | | | NOTE:FAN SHUTDOWN BY DUCT SMOKE | | | DETECTOR SHALL HAVE NOTIFICATION | | | TO ALARM/STROBE IN NORMALLY | | | OCCUPIED AREAS. NFPA 90A 4-4.4.3. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2002-10-23 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2002-10-23 |
Time |
07:54 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-10-23 00:00:00 | REVISION FOR F/D IN WOMENS REST RM, PES |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2002-08-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-08-26 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-08-26 |
Time |
08:12 |
Sent To |
|
|
| Notes |
| 2002-08-26 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) FLOOR DRAIN IN WOMENS TOILET ROOM NOT | | | VENTED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2002-02-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-02-08 |
Time |
14:01 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2002-02-08 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2002-02-08 00:00:00 | PROVISO: WATER HAMMER ARRESTORS SHALL BE | | | LOCATED NEAR FIXTURES NOT AT TOP OF DROP |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2002-01-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-31 |
Time |
18:58 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2002-01-31 |
Time |
18:58 |
Sent To |
|
|
| Notes |
| 2002-01-31 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SHT P-2 WATER RISER DIAGRAM, AIR | | | CHAMBER DETAIL NOT SHOWN AS REQUSTED IN | | | LAST REVIEW. SEE SHEET PROVIDED AND GIVE | | | DETAILS ON PLANS FOR VALVES IN AIR | | | CHAMBERS. | | | 2) SHT P-2 PREVIOUS COMMENTS NOT ADDRESS | | | ED PROPERLY. VENT FOR DOUBLE LAV IS | | | STILL GOING UP AND THEN BACK DOWN. THIS | | | IS NOT ACCEPTABLE. | | | 3) SHT P-2 WATER HEATER EMERGENCY PAN | | | DRAIN SHALL BE 1" NOT 3/4" AS SHOWN. | | | SPC SEC 507.8.2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2002-01-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-07 |
Time |
18:15 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2002-01-07 |
Time |
18:15 |
Sent To |
|
|
| Notes |
| 2002-01-07 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) PER PREVIOUS REVIEW SHT P-2 AIR | | | CHAMBERS SHALL BE ACCESSIBLE AND RECHARG | | | EABLE PER WH-PDI 201 SPC SEC 607.8.3. | | | SEE ATTACHED SHEET FOR APPROVED AIR | | | CHAMBERS. SHOW DETAIL ON PLANS IF USING | | | AIR CHAMBERS. | | | | | | 2) PER PREVIOUS REVIEW SHT P-2 VENT NOT | | | APPROVED. VENT FOR DOUBLE LAV IN WOMENS | | | RESTROOM RISES AND THEN DROPS DOWN INTO | | | VENT HEADER. THIS IS NOT A LEGAL VENT. | | | | | | 3) PER PREVIOUS REVIEW SHT P-2 PAN DRAIN | | | NOT SHOWN. PLUMBING NOTES #27 NOT APPRO- | | | VED. SPC SEC 507.8.3 - 507.8.4 RELIEF | | | LINE AND PAN DRAIN LINE TO BE PIPED FULL | | | SIZE SEPARATELY AND TERMINATE NO LESS | | | THAN 6" ABOVE GROUND. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-11-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-13 |
Time |
15:55 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2001-11-13 |
Time |
15:55 |
Sent To |
|
|
| Notes |
| 2001-11-13 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) PAGE P-2, SANT RISER DIAGRAM. URNAL | | | SHALL BE WALL MOUNT NOT FLOOR MOUNT AS | | | SHOWN ON RISER. DRINKING FOUNTAIN SHOWN | | | ON MENS SIDE OF ALCOVE ON FLOOR PLAN AND | | | ON WOMENS SIDE ON RISER. PLEASE CLARIFY. | | | 2) PAGE P-2, WATER RISER DIAGRAM. DOUBLE | | | LAV SHOWN IN MENS ROOM AND DRINKING | | | FOUNTAIN SHOWN ON WOMENS SIDE. AIR CHAM- | | | BERS ARE QUICK FIX AND REQUIRE ACCESS & | | | SHALL BE RECHARGEABLE PER SPC SEC 607.8. | | | 3. AND PER PDI-WH 201. IF WATER HAMMER | | | ARRESTORS ARE USED THEY SHALL BE SIZED & | | | LOCATED PER MANUFACTURE INSTALLATION IN- | | | STRUCTIONS AND PDI-WH 201. NOT LOCATED | | | ON TOP OF DROP AS SHOWN. | | | 4) PAGE P-2 VENT ON SANT. RISER DIAGRAM | | | SHALL NOT GO UP - OVER - & DOWN AS SHOWN | | | FOR LAV IN WOMENS ROOM. | | | 5) PAGE P-2 PLEASE INDICATE WHERE AND | | | HOW THE PAN DRAIN AND T&P TERMINATE FROM | | | WATER HEATER. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-09-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-12 |
Time |
16:40 |
Rev Time |
1.75 |
| Received By |
kstevens |
Date |
2001-09-12 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2001-09-12 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) PAGES A2.0 & A2.2 DETAIL 3 RESTROOM | | | PLAN. 3 LAVS REQUIRED IN WOMEN'S REST- | | | ROOM PER SPC-94 TABLE 407. | | | 2) PAGE A2.2 DETAIL 3 RESTROOM PLAN. | | | HDCP STALL NOT WIDE ENOUGH. SHOWS 6'0" | | | AND IT SHOULD BE 7'0" PER FACBC-97, FIG. | | | 30(E). | | | 3) PAGE A2.2 DETAIL 7 RESTROOM ELEVATION | | | URNAL TO COMPLY WITH FACBC-97 SECTIONS | | | 4.22.5 & 4.18.2. 17" TO LIP ECT. | | | 4) PAGE A2.2 DETAIL 4 RESTROOM ENTRANCE | | | ELEVATION. 1 DRINKING FOUNTAIN SHALL | | | COMPLY WITH FACBC-97 SECT. 4.15, AND 1 | | | DRINKING FOUNTAIN SHALL COMPLY WITH | | | FACBC-97 SECT. 4.1.3(10). | | | 5) PAGE P2 SANITARY RISER DIAGRAM. URNAL | | | NOT SHOWN ON RISER DIAGRAM. | | | 6) PAGE P2 WATER RISER DIAGRAM AND PLUMB | | | ING NOTES #13. AIR CHAMBERS TO COMPLY | | | WITH SPC-94 SECT. 607.8.2 & 607.8.3. | | | ACCESSABLE AND RECHARGABLE. IF WATER | | | HAMMER ARRESTORS ARE USED, THEY SHALL | | | COMPLY WITH MANUFACTURE INSTALLATION IN- | | | STRUCTIONS AND WH-PDI 201 FOR SIZING AND | | | LOCATION. THEY ARE NOT LOCATED AT TOP OF | | | RISERS OR DROPS. | | | 7) PAGE P2 WATER HEATER DETAIL. SHUT OFF | | | VALVE SHALL BE LOCATED CLOSE TO HEATER. | | | (ACCESSABLE). | | | 8) SHOW LOCATION OF WATER HEATER. PAN | | | DRAIN TO BE 1", AND RELIEF VALVE DIS- | | | CHARGE SHALL BE FULL SIZED SEPARATLY TO | | | THE OUTSIDE OF THE BUILDING AND SHALL | | | TERMINATE 6" ABOVE GRADE. SPC-94 SECTS. | | | 507.8.2 & 507.8.4 | | | | | | REVIEW BY KEN STEVENS | | | (561) 569-8096 EXT. 8377 |
|
|