Plan Review Details - Permit 01090049
Plan Review Stops For Permit 01090049
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-11-20 Cont ID  
Sent By jwitmer Date 2001-11-20 Time 17:40 Rev Time 1.00
Received By jwitmer Date 2001-11-20 Time 17:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-10-22 Cont ID  
Sent By jwitmer Date 2001-10-22 Time 17:02 Rev Time 1.50
Received By jwitmer Date 2001-10-22 Time 17:02 Sent To  
Notes
2001-10-22 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01090049
 1555 PALM BEACH LAKES # 9TH FL
 ANDERSON MOORE CONSTRUCTION
 TEL : 626-4411
 FAX : 626-4411
 CELL: 662-1819
  
 SBC= 1997 STANDARD BUILDING CODE
  
 1)-SBC 412.6.1 REQUIRES THE ELEVATOR
 LOBBY TO BE SEPERATED FROM THE REMAINDER
 OF THE BUILDING WITH 1 HR RATED
 CONSTRUCTION.
 SBC 412.6.2 EXIT STAIRWAYS, CHUTES,
 JANITOR CLOSETS,SERVICE ROOMS- MECH.,
 GUEST ROOMS, ETC., SHALL NOT OPEN INTO
 THE ELEVATOR LOBBY.
  
 2)- SHEET A-1 DETAIL#2: PROVIDE A FIRE
 DESIGN NUMBER FOR THE PARTITION DEPICTED
  
 3)- FL ACCES CODE 4.13.6 MANEUVERING
 CLEARENCES AT DOORS, 23 & 34 REQUIRE
 12" ON THE PUSH SIDE OF THE DOOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-09-18 Cont ID  
Sent By hpiskura Date 2001-09-18 Time 10:59 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-09-18 00:00:00THE COMMON PATH OF TRAVEL FROM THE
 VICINITY OF OFFICE #132 EXCEEDS THE 75'
 ALLOWED BY SBC 1004.1.3.PLEASE REVISE
 AS NECESSARY.
  
 SBC 412.6.1 REQUIRES ELEVATOR LOBBIES TO
 BE SEPARATED FROM THE REMAINDER OF THE
 BUILDING WITH 1 HOUR FIRE RATED
 CONSTRUVCTION.SEE ALSO 412.6.2.
  
 THE EXIT DOORS SERVING THE NORTH SIDE
 OFFICE SPACE DO NOT MEET THE 1/2
 DIAGONAL DISTANCE SEPARATION
 REQUIREMENTS OF SBC 1004.1.4.PLEASE
 REVISE AS NECESSARY.
  
 PROVIDE A FIRE DESIGN NUMBER FOR THE
 PARTITION SHOWN IN SECTION 2/A1.SEE
 SBC 701.5.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-09-17 Cont ID  
Sent By dpalmer Date 2001-09-17 Time 22:42 Rev Time 0.00
Received By dpalmer Date 2001-09-17 Time 22:37 Sent To  
Notes
2001-09-17 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PLANS MUST
 CONTAIN TITLE BLOCK BY THE ARCH OF
 RECORD. 61G15-23 FS/FAC 481.221
 PLEASE SEE PANEL SCHEDULES.
  
 2)NOTE: PLEASE CLARIFY PANEL "LA", PANEL
 IS SHOWN AS "MLO". PLEASE NOTE THAT
 MAIN IS REQ`D PER 384-16E
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-11-02 Cont ID  
Sent By rmcdouga Date 2001-11-02 Time 09:59 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-09-05 Cont ID  
Sent By mcarsill Date 2001-09-05 Time 13:31 Rev Time 0.00
Received By mcarsill Date 2001-09-05 Time 13:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-10-22 Cont ID  
Sent By ndenmark Date 2001-10-22 Time 09:04 Rev Time 0.33
Received By ndenmark Date 2001-10-22 Time 09:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-09-24 Cont ID  
Sent By pkrauss Date 2001-09-24 Time 16:32 Rev Time 0.45
Received By pkrauss Date 2001-09-24 Time 16:30 Sent To  
Notes
2001-09-24 00:00:00******************DENIED****************
  
  
 PLEASE IDENTIFY ALL FIRE DAMPERS ON
 PLAN.PROVIDE A INSTALLATION DETAIL.
  
 AREAS WITH 300 CFM OR GREATER SHALL HAVE
 A RETURN AIR FROM THAT SPACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-10-30 Cont ID  
Sent By kstevens Date 2001-10-30 Time 09:48 Rev Time 0.33
Received By kstevens Date 2001-10-30 Time 09:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-09-12 Cont ID  
Sent By kstevens Date 2001-09-12 Time 10:37 Rev Time 0.33
Received By kstevens Date 2001-09-12 Time 10:37 Sent To  
Notes
2001-09-12 00:00:00DENIED
 REFERENCES SPC-94 - FACBC-97
  
 1) PAGE A-3 HDCP RESTROOM, LAV TO COMPLY
 WITH FACBC-97 SECT. 4.19.2.
  
 2) PAGE A-3 WATER RISER DIAGRAM. AIR
 CHAMBERS TO COMPLY WITH SPC-94 SECT.
 607.8.3 ACCESSABLE AND RECHARGABLE. IF
 WATER HAMMER ARRESTORS ARE USED THEY
 SHALL COMPLY WITH MANUFACTURE'S INSTALL-
 ATION INSTRUCTIONS AND WH-PDI 201 FOR
 SIZE AND LOCATION. (NOT AT TOP OF DROP)
  
 3) PAGE A-3 WATER RISER DIAGRAM. EACH
 WATER SUPPLY BRANCH LINE SHALL HAVE A
 SHUTOFF VALVE INSTALLED. SPC-94 SEC.
 610.4.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377