Plan Review Details - Permit 01081536
Plan Review Stops For Permit 01081536
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-10-18 Cont ID  
Sent By lmartine Date 2001-10-18 Time 10:40 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-10-18 00:00:00PERMIT IS FOR CONCRETE PADS ONLY
 L. MARTINEZ 10/18/01

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-10-05 Cont ID  
Sent By pkrauss Date 2001-10-05 Time 15:40 Rev Time 0.10
Received By pschmitz Date   Time   Sent To  
Notes
2001-10-18 00:00:00PERMIT IS FOR CONCRETE PAD ONLY
 L. MARTINEZ 10/18/01

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-09-24 Cont ID  
Sent By dpalmer Date 2001-09-24 Time 19:23 Rev Time 0.00
Received By dpalmer Date 2001-09-24 Time 19:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-10-02 Cont ID  
Sent By mcarsill Date 2001-10-02 Time 12:32 Rev Time 0.00
Received By mcarsill Date 2001-10-02 Time 12:32 Sent To  
Notes
2001-10-02 00:00:00RECEIVED LETTER THAT HAS BEEN ATTACHED
 TO PLANS. THE LETTER INDICATES THAT
 A SHED WILL BE BUILT OF NON-COMBUSTIBLE
 MATERIALS. PLANS WILL BE SUBMITTED
 REGARDING THIS CHANGE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-09-25 Cont ID  
Sent By mcarsill Date 2001-09-25 Time 15:53 Rev Time 0.00
Received By mcarsill Date 2001-09-25 Time 15:53 Sent To  
Notes
2001-09-25 00:00:001) PLEASE BE ADVISED THAT THE WOOD SHED
 WITH METAL SIDING IS TOO CLOSE TO THE
 BULK OXYGEN TANK. THE BULK OXYGEN TANK
 MUST BE SEPARATED BY AT LEAST 50 FEET
 FROM WOOD FRAME BUILDINGS. PLEASE SEE
 NFPA 50, SECTION 2.2.1.
 2) NO PARKING OR PUBLIC SIDEWALKS ARE
 PERMITTED WITHIN 10 FEET OF BULK
 OXYGEN TANK. PLEASE SEE NFPA 50,SECTION
 2.2.12.
 3) BULK OXYGEN TANKS MUST BE AT LEAST
 50 FEET FROM ANY NON-AMBULATORY AREAS.
 PLEASE SEE NFPA 50,SECTION 2.2.11
 4) SAFETY RELEASE DEVICES ARE REQUIRED.
 PLEASE SEE NFPA 50,SECTION 3-3.
 5) SIGNAGE REQUIRED "OXYGEN,NO SMOKING,
 OR OPEN FLAMES". PLEASE SEE NFPA 50,
 SECTION 3.5.8.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop Z ZONING
Rev No 2 Status P Date 2001-09-24 Cont ID  
Sent By sgraham Date 2001-09-24 Time 09:45 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2001-09-05 Cont ID  
Sent By sgraham Date 2001-09-05 Time 12:13 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-09-05 00:00:00FIRE DEPT WILL NOT APP LOCATION