Plan Review Details - Permit 01081308
Plan Review Stops For Permit 01081308
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-10-31 Cont ID  
Sent By jwitmer Date 2001-10-31 Time 11:41 Rev Time 1.50
Received By jwitmer Date 2001-10-31 Time 06:39 Sent To  
Notes
2001-10-31 00:00:00PROVISO ARCH FAX HISTORIC APPROVAL FOR
 THE WORK ON THE EXTERIOR. 10/31/01 JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-09-18 Cont ID  
Sent By jwitmer Date 2001-09-18 Time 18:41 Rev Time 1.50
Received By jwitmer Date 2001-09-18 Time 18:41 Sent To  
Notes
2001-09-18 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01081308
 1703 S LAKE AV
 CONT: WOOLEMS, INC
 PHONE : 835-0401
  
 SBC= 1997 STANDARD BUILDING CODE
  
 1)- GENERAL NOTES CORRECTION 1997
 STANDARD BUILDING CODE
  
 2)- SHEET A-6 "C" DISCREPANCY B/A-6 &
 C/A-6, C-CHANEL BOTH DETAILS INDICATE
 THAT THE CUT SECTION IS FOR THE SAME
 ROOM, BOTH DIRECTIONS? ROOM #110 IS NOT
 INDICATED ON A-2?
 3)- NOTE A-6 SEC "C" 12"X 6" LAG BOLTS?
 4)- THE SAME SECTION AS ABOVE IS TO BE
 DESIGNED FOR 125 LBS/SQ FT. LIGHT STOR-
 AGE SBC TABLE 1604.1. IF NOT USED FOR
 STORAGE, VERTICAL ACCESSIBILITY WILL
 BE AN ISSUE!
 5)- SEC "B" OF A-6 ENGINEER OF RECORD TO
 APPROVE THE ADDITIONAL WEIGHT OF AIR
 HANDLER #2, THE ATTACHMENT TO THE ROOF
 FRAMING MEMBERS .
 6)- SHEET A-2 CUT SECTION 1/A-4.THE
 APPLICATION INDICATES THAT ENCLOSING THE
 MATERIAL STORAGE YARD W/ CONCRETE BLOCK
 THERE IS NO FOUNDATION PLAN, DETAILS FOR
 REBAR, COLUMNS OR BEAM.
 7)- THE PLANS ALSO INDICATE A FOOTING
 F-1 TB-1 COLUMN, A NEW WF 8X21 STEEL
 BEAM, IS THIS AREA TO BE INCLUDED IN
 THIS PERMIT? IF SO NOT ENOUGH INFORMA-
 TION TO DO A REVIEW!!!
  
 BUILDING PLAN EVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-11-28 Cont ID  
Sent By dpalmer Date 2001-11-28 Time 18:55 Rev Time 0.00
Received By dpalmer Date 2001-11-28 Time 18:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-10-30 Cont ID  
Sent By dpalmer Date 2001-10-30 Time 17:51 Rev Time 0.00
Received By dpalmer Date 2001-10-30 Time 17:41 Sent To  
Notes
2001-10-30 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE NOW
 BEING SUBMITTED WITH A NEW PANEL BEING
 ADDED, BUT DOES NOT SHOW WHERE IT IS
 BEING FED FROM? WIRE? CONDUIT? LOAD ON
 EQUIPMENT FEEDING IT???
 PLANS SHOW EXISTING PANELS "A" AND "B"
 BUT DON'T SHOW NEW PANEL"B"?
 PLEASE CLARIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. THE OTHER COMMENTS FROM FIRST
 REVIEW WERE ADDRESSED.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-09-18 Cont ID  
Sent By dpalmer Date 2001-09-18 Time 20:16 Rev Time 0.00
Received By dpalmer Date 2001-09-18 Time 20:16 Sent To  
Notes
2001-09-18 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PLANS NEED MORE
 FOR COMPLETE REVIEW/
 PLEASE SHOW LIGHTING,EXIT LTS, EM LTS,
 ETC. EXISTING? NEW?
  
 2)NOTE: PLEASE NOTE THAT OUTLET SPACING
 TO MEET LOCAL CODE. 210-50
 EVERY 12' IN STUDIO`S AND EVERY 20' IN
 STORAGE AREAS.
  
 3)NOTE: PLEASE NOTE THAT ALL ELECTRICAL
 DEVICES NEED TO HAVE BRANCH CIRCUIT #`S
 SHOWN ON PLANS AND CORRELATE WITH
 PANEL SCHEDULES TO BE SUBMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-10-31 Cont ID  
Sent By jwitmer Date 2001-10-31 Time 06:37 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-10-22 Cont ID  
Sent By mcarsill Date 2001-10-22 Time 13:31 Rev Time 0.00
Received By mcarsill Date 2001-10-22 Time 13:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-09-11 Cont ID  
Sent By mcarsill Date 2001-09-11 Time 09:07 Rev Time 0.00
Received By mcarsill Date 2001-09-11 Time 09:06 Sent To  
Notes
2001-09-11 00:00:001) PLEASE INDICATE EXITS,EXIT SIGNS,
 AND EMERGENCY LIGHT FIXTURES.
 2) MORE DETAILS NEEDED FOR NEW
 GALVANIZED VENT HOOD. WHAT WILL IT BE
 USED FOR.
 3) NEW CANVAS TO BE FIRE RETARDANT.
 4) WRONG BUILDING CODE EDITION
 REFERENCED. SHOULD READ 1997 EDITION.
 5) PLEASE INDICATE LOCATIONS OF FIRE
 EXTINGUISHERS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-12-05 Cont ID  
Sent By pkrauss Date 2001-12-05 Time 11:08 Rev Time 0.40
Received By pkrauss Date 2001-12-05 Time 10:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-10-25 Cont ID  
Sent By pkrauss Date 2001-10-25 Time 08:37 Rev Time 0.50
Received By pkrauss Date 2001-10-25 Time 08:26 Sent To  
Notes
2001-10-25 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.TONNAGE OF EXISTING AHU-1.
  
 2.CFM OF NEW SUPPLY DROP IN THE WAX
 MOLD ROOM.
  
 3.SUBMIT INFORMATION ON FUME EXHAUST
 HOOD.(CFM OF EXHAUST FAN)
  
 4.PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-09-28 Cont ID  
Sent By pkrauss Date 2001-09-28 Time 13:24 Rev Time 0.50
Received By pkrauss Date 2001-09-28 Time 13:02 Sent To  
Notes
2001-09-28 00:00:00******************DENIED****************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
  
 2.EQUIPMENT INFORMATION, MAKE, MODEL,
 BTU'S, SEER.IS THE EQUIPMENT A
 RTU, AHU OR HEAT PUMP.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 OF UNITS 2,000 CFM AND GREATER, WITH
 NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS. 1977 SMC
 406.1 AND NFPA 90A 4-4.4.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status N Date 2001-10-30 Cont ID  
Sent By kstevens Date 2001-10-30 Time 09:57 Rev Time 0.25
Received By kstevens Date 2001-10-30 Time 09:52 Sent To  
Notes
2001-10-30 00:00:00NO PLUMBING INCLUDED ON THIS JOB. KS

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-03 Cont ID  
Sent By kstevens Date 2001-10-03 Time 18:56 Rev Time 0.33
Received By kstevens Date 2001-10-03 Time 18:56 Sent To  
Notes
2001-10-03 00:00:00DENIED
 REFERENCE: SPC-94
  
 PLEASE PROVIDE INFORMATION ON TWO
 DOUBLESINKS SHOWN ON PAGES A-2 AND E-1.
 INDI- CATE IF THEY COMPLY WITH FACBC-97
 SEC 4.24.
 PLEASE PROVIDE A SANITARY AND WATER
 RISER DIAGRAM SHOWING WHERE THE SYSTEMS
 WILL BE TIED INTO EXISTING LINES. SHOW
 PIPE SIZE AND VENTING. ALSO SHOW WATER
 HAMMER ARRESTORS SIZED AND LOCATED BY
 MANUFACTURE INSTALLATION INSTRUCTIONS
 WH-PDI 201.
  
 REVIEW BY KEN STEVENS
 (561) 569-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-09-10 Cont ID  
Sent By sgraham Date 2001-09-10 Time 07:24 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***