| Plan Review Stops For Permit 01081308 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-10-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-10-31 |
Time |
11:41 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2001-10-31 |
Time |
06:39 |
Sent To |
|
|
| Notes |
| 2001-10-31 00:00:00 | PROVISO ARCH FAX HISTORIC APPROVAL FOR | | | THE WORK ON THE EXTERIOR. 10/31/01 JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-09-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-09-18 |
Time |
18:41 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2001-09-18 |
Time |
18:41 |
Sent To |
|
|
| Notes |
| 2001-09-18 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01081308 | | | 1703 S LAKE AV | | | CONT: WOOLEMS, INC | | | PHONE : 835-0401 | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | | | | 1)- GENERAL NOTES CORRECTION 1997 | | | STANDARD BUILDING CODE | | | | | | 2)- SHEET A-6 "C" DISCREPANCY B/A-6 & | | | C/A-6, C-CHANEL BOTH DETAILS INDICATE | | | THAT THE CUT SECTION IS FOR THE SAME | | | ROOM, BOTH DIRECTIONS? ROOM #110 IS NOT | | | INDICATED ON A-2? | | | 3)- NOTE A-6 SEC "C" 12"X 6" LAG BOLTS? | | | 4)- THE SAME SECTION AS ABOVE IS TO BE | | | DESIGNED FOR 125 LBS/SQ FT. LIGHT STOR- | | | AGE SBC TABLE 1604.1. IF NOT USED FOR | | | STORAGE, VERTICAL ACCESSIBILITY WILL | | | BE AN ISSUE! | | | 5)- SEC "B" OF A-6 ENGINEER OF RECORD TO | | | APPROVE THE ADDITIONAL WEIGHT OF AIR | | | HANDLER #2, THE ATTACHMENT TO THE ROOF | | | FRAMING MEMBERS . | | | 6)- SHEET A-2 CUT SECTION 1/A-4.THE | | | APPLICATION INDICATES THAT ENCLOSING THE | | | MATERIAL STORAGE YARD W/ CONCRETE BLOCK | | | THERE IS NO FOUNDATION PLAN, DETAILS FOR | | | REBAR, COLUMNS OR BEAM. | | | 7)- THE PLANS ALSO INDICATE A FOOTING | | | F-1 TB-1 COLUMN, A NEW WF 8X21 STEEL | | | BEAM, IS THIS AREA TO BE INCLUDED IN | | | THIS PERMIT? IF SO NOT ENOUGH INFORMA- | | | TION TO DO A REVIEW!!! | | | | | | BUILDING PLAN EVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-11-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-28 |
Time |
18:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-28 |
Time |
18:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-10-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-30 |
Time |
17:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-30 |
Time |
17:41 |
Sent To |
|
|
| Notes |
| 2001-10-30 00:00:00 | **************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS ARE NOW | | | BEING SUBMITTED WITH A NEW PANEL BEING | | | ADDED, BUT DOES NOT SHOW WHERE IT IS | | | BEING FED FROM? WIRE? CONDUIT? LOAD ON | | | EQUIPMENT FEEDING IT??? | | | PLANS SHOW EXISTING PANELS "A" AND "B" | | | BUT DON'T SHOW NEW PANEL"B"? | | | PLEASE CLARIFY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. THE OTHER COMMENTS FROM FIRST | | | REVIEW WERE ADDRESSED. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-09-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-09-18 |
Time |
20:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-09-18 |
Time |
20:16 |
Sent To |
|
|
| Notes |
| 2001-09-18 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS NEED MORE | | | FOR COMPLETE REVIEW/ | | | PLEASE SHOW LIGHTING,EXIT LTS, EM LTS, | | | ETC. EXISTING? NEW? | | | | | | 2)NOTE: PLEASE NOTE THAT OUTLET SPACING | | | TO MEET LOCAL CODE. 210-50 | | | EVERY 12' IN STUDIO`S AND EVERY 20' IN | | | STORAGE AREAS. | | | | | | 3)NOTE: PLEASE NOTE THAT ALL ELECTRICAL | | | DEVICES NEED TO HAVE BRANCH CIRCUIT #`S | | | SHOWN ON PLANS AND CORRELATE WITH | | | PANEL SCHEDULES TO BE SUBMITTED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-10-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-10-31 |
Time |
06:37 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-10-22 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-22 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-22 |
Time |
13:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-09-11 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-09-11 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-09-11 |
Time |
09:06 |
Sent To |
|
|
| Notes |
| 2001-09-11 00:00:00 | 1) PLEASE INDICATE EXITS,EXIT SIGNS, | | | AND EMERGENCY LIGHT FIXTURES. | | | 2) MORE DETAILS NEEDED FOR NEW | | | GALVANIZED VENT HOOD. WHAT WILL IT BE | | | USED FOR. | | | 3) NEW CANVAS TO BE FIRE RETARDANT. | | | 4) WRONG BUILDING CODE EDITION | | | REFERENCED. SHOULD READ 1997 EDITION. | | | 5) PLEASE INDICATE LOCATIONS OF FIRE | | | EXTINGUISHERS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-12-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-05 |
Time |
11:08 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-12-05 |
Time |
10:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-10-25 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-25 |
Time |
08:37 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-10-25 |
Time |
08:26 |
Sent To |
|
|
| Notes |
| 2001-10-25 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | 1.TONNAGE OF EXISTING AHU-1. | | | | | | 2.CFM OF NEW SUPPLY DROP IN THE WAX | | | MOLD ROOM. | | | | | | 3.SUBMIT INFORMATION ON FUME EXHAUST | | | HOOD.(CFM OF EXHAUST FAN) | | | | | | 4.PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-09-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-28 |
Time |
13:24 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-09-28 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2001-09-28 00:00:00 | ******************DENIED**************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | | ASHRAE 62-89. | | | | | | 2.EQUIPMENT INFORMATION, MAKE, MODEL, | | | BTU'S, SEER.IS THE EQUIPMENT A | | | RTU, AHU OR HEAT PUMP. | | | | | | 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | OF UNITS 2,000 CFM AND GREATER, WITH | | | NOTIFICATION TO ALARM/STROBE IN | | | NORMALLY OCCUPIED AREAS. 1977 SMC | | | 406.1 AND NFPA 90A 4-4.4.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2001-10-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-30 |
Time |
09:57 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2001-10-30 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2001-10-30 00:00:00 | NO PLUMBING INCLUDED ON THIS JOB. KS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-10-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-03 |
Time |
18:56 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-10-03 |
Time |
18:56 |
Sent To |
|
|
| Notes |
| 2001-10-03 00:00:00 | DENIED | | | REFERENCE: SPC-94 | | | | | | PLEASE PROVIDE INFORMATION ON TWO | | | DOUBLESINKS SHOWN ON PAGES A-2 AND E-1. | | | INDI- CATE IF THEY COMPLY WITH FACBC-97 | | | SEC 4.24. | | | PLEASE PROVIDE A SANITARY AND WATER | | | RISER DIAGRAM SHOWING WHERE THE SYSTEMS | | | WILL BE TIED INTO EXISTING LINES. SHOW | | | PIPE SIZE AND VENTING. ALSO SHOW WATER | | | HAMMER ARRESTORS SIZED AND LOCATED BY | | | MANUFACTURE INSTALLATION INSTRUCTIONS | | | WH-PDI 201. | | | | | | REVIEW BY KEN STEVENS | | | (561) 569-8096 EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-09-10 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-09-10 |
Time |
07:24 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|