Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-10-09 Cont ID  
Sent By hpiskura Date 2001-10-09 Time 15:50 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-09-14 Cont ID  
Sent By hpiskura Date 2001-09-14 Time 10:29 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-09-14 00:00:00THE STAIRS AT THE WEST END OF THE
 BUILDING ARE REQUIRED BY SBC
 1006.1.1 TO BE SEPARATED FROM THE
 REMAINDER OF THE BUILDING BY FIRE RATED
 CONSTRUCTION.
  
 THE OPENINGS AND USE OF A FIRE RATED
 STAIR SHAFT ARE LIMITED BY SBC
 1006.1.3.IT APPEARS THE ELEVATOR
 LOBBY IS OPEN TO THE STAIR SHAFT.
 PLEASE REVISE AS NECESSARY.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-09 Cont ID  
Sent By dpalmer Date 2001-10-09 Time 18:40 Rev Time 0.00
Received By dpalmer Date 2001-10-09 Time 18:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-09-06 Cont ID  
Sent By dpalmer Date 2001-09-06 Time 11:34 Rev Time 0.00
Received By dpalmer Date 2001-09-06 Time 11:30 Sent To  
Notes
2001-09-06 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE SUBMIT INFORMATION FOR
 GENERATOR SYSTEM. CUT SHEETS
  
 2)NOTE: PLEASE NOTE SEPARATE PLANS AND
 PERMIT(S) REQ`D FOR FUEL SYSTEM PER
 MECH/FIRE DEPT.
  
 3)NOTE: PLEASE NOTE THAT PLANS CALL FOR
 NEW GENERATOR SYSTEM AND NO ELECTRICAL
 DETAIL SHOWN FOR REVIEW. WIRING/RISER
 DIAGRAM.
  
 4)NOTE: PLEASE NOTE THAT PLANS MENTION
 OWNER SUPPLIED AND CONTRACTOR INSTALLED.
 PLEASE NOTE THAT UNDER CITY-WIDE ADMIN-
 -ISTRATIVE CODE COMPLETE VALUE OF JOB
 IS TO INCLUDE ALL LABOR AND MATERIALS
 REGUARDLES OF WHO SUPPLIES.
 104.7.5
  
 5)NOTE: PLEASE PROVIDE INFORMATION FOR
 EM LTS AND EXITS LTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-09-14 Cont ID  
Sent By hpiskura Date 2001-09-14 Time 10:36 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-10-03 Cont ID  
Sent By mcarsill Date 2001-10-03 Time 08:48 Rev Time 0.00
Received By mcarsill Date 2001-10-03 Time 08:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-23 Cont ID  
Sent By mcarsill Date 2001-08-23 Time 14:36 Rev Time 0.00
Received By mcarsill Date 2001-08-23 Time 14:36 Sent To  
Notes
2001-08-23 00:00:001) PLEASE CLEARLY INDICATE ON THE
 PLANS THE LOCATIONS OF NEW OR EXISTING
 EMERGENCY LIGHTS AND EXIT SIGNS.
 2) PLEASE CLEARLY INDICATE LOCATIONS
 OF EXISTING OR NEW FIRE ALARM EQUIPMENT.
 3) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 4) IT APPEARS THAT A TABLE IS LOCATED
 IN FRONT OF AN AISLE THAT LEADS TO
 A REQUIRED EXIT DOOR.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status C Date 2001-10-11 Cont ID  
Sent By ndenmark Date 2001-09-12 Time 14:12 Rev Time 0.33
Received By pkrauss Date 2001-09-12 Time 14:12 Sent To  
Notes
2001-09-12 00:00:00PROVISO:
 NO COMBUSTIBLES ALLOWED IN RETURN AIR
 PLENUM SPACE.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-10-10 Cont ID  
Sent By kstevens Date 2001-10-10 Time 17:00 Rev Time 0.50
Received By kstevens Date 2001-10-10 Time 17:00 Sent To  
Notes
2001-10-10 00:00:00PASSED/PROVISO
  
 LAV REQUIRED IN HDCP STALLS 1ST FLOOR

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-09-05 Cont ID  
Sent By kstevens Date 2001-09-05 Time 10:56 Rev Time 1.50
Received By kstevens Date 2001-09-05 Time 10:56 Sent To  
Notes
2001-09-05 00:00:00DENIED
  
 REFERENCE FACBC-97 - SPC-94
  
 1) RESTROOMS TO COMPLY WITH FACBC-97
 SECTIONS. 4.16, 4.17, 4.18, & 4.19.
  
 2) BREAK ROOM AND VENDING ROOM SINKS TO
 COMPLY WITH FACBC-97 SECTION 4.24.
  
 3) DRINKING FOUNTAINS REQUIRED PER SPC-
 94 TABLE 407, AND SHALL COMPLY WITH
 FACBC-97 SECTION 4.15.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT.8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-09-14 Cont ID  
Sent By hpiskura Date 2001-09-14 Time 10:36 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***