| Plan Review Stops For Permit 01081222 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-10-09 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-10-09 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-09-14 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-09-14 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-14 00:00:00 | THE STAIRS AT THE WEST END OF THE | | | BUILDING ARE REQUIRED BY SBC | | | 1006.1.1 TO BE SEPARATED FROM THE | | | REMAINDER OF THE BUILDING BY FIRE RATED | | | CONSTRUCTION. | | | | | | THE OPENINGS AND USE OF A FIRE RATED | | | STAIR SHAFT ARE LIMITED BY SBC | | | 1006.1.3.IT APPEARS THE ELEVATOR | | | LOBBY IS OPEN TO THE STAIR SHAFT. | | | PLEASE REVISE AS NECESSARY. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-10-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-09 |
Time |
18:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-09 |
Time |
18:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-09-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-09-06 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-09-06 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2001-09-06 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SUBMIT INFORMATION FOR | | | GENERATOR SYSTEM. CUT SHEETS | | | | | | 2)NOTE: PLEASE NOTE SEPARATE PLANS AND | | | PERMIT(S) REQ`D FOR FUEL SYSTEM PER | | | MECH/FIRE DEPT. | | | | | | 3)NOTE: PLEASE NOTE THAT PLANS CALL FOR | | | NEW GENERATOR SYSTEM AND NO ELECTRICAL | | | DETAIL SHOWN FOR REVIEW. WIRING/RISER | | | DIAGRAM. | | | | | | 4)NOTE: PLEASE NOTE THAT PLANS MENTION | | | OWNER SUPPLIED AND CONTRACTOR INSTALLED. | | | PLEASE NOTE THAT UNDER CITY-WIDE ADMIN- | | | -ISTRATIVE CODE COMPLETE VALUE OF JOB | | | IS TO INCLUDE ALL LABOR AND MATERIALS | | | REGUARDLES OF WHO SUPPLIES. | | | 104.7.5 | | | | | | 5)NOTE: PLEASE PROVIDE INFORMATION FOR | | | EM LTS AND EXITS LTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-09-14 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-09-14 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-10-03 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-03 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-03 |
Time |
08:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-08-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-23 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-23 |
Time |
14:36 |
Sent To |
|
|
| Notes |
| 2001-08-23 00:00:00 | 1) PLEASE CLEARLY INDICATE ON THE | | | PLANS THE LOCATIONS OF NEW OR EXISTING | | | EMERGENCY LIGHTS AND EXIT SIGNS. | | | 2) PLEASE CLEARLY INDICATE LOCATIONS | | | OF EXISTING OR NEW FIRE ALARM EQUIPMENT. | | | 3) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR WALLS | | | AND CEILINGS. | | | 4) IT APPEARS THAT A TABLE IS LOCATED | | | IN FRONT OF AN AISLE THAT LEADS TO | | | A REQUIRED EXIT DOOR. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
C |
Date |
2001-10-11 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-09-12 |
Time |
14:12 |
Rev Time |
0.33 |
| Received By |
pkrauss |
Date |
2001-09-12 |
Time |
14:12 |
Sent To |
|
|
| Notes |
| 2001-09-12 00:00:00 | PROVISO: | | | NO COMBUSTIBLES ALLOWED IN RETURN AIR | | | PLENUM SPACE. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-10-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-10 |
Time |
17:00 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-10-10 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2001-10-10 00:00:00 | PASSED/PROVISO | | | | | | LAV REQUIRED IN HDCP STALLS 1ST FLOOR |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-09-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-05 |
Time |
10:56 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2001-09-05 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2001-09-05 00:00:00 | DENIED | | | | | | REFERENCE FACBC-97 - SPC-94 | | | | | | 1) RESTROOMS TO COMPLY WITH FACBC-97 | | | SECTIONS. 4.16, 4.17, 4.18, & 4.19. | | | | | | 2) BREAK ROOM AND VENDING ROOM SINKS TO | | | COMPLY WITH FACBC-97 SECTION 4.24. | | | | | | 3) DRINKING FOUNTAINS REQUIRED PER SPC- | | | 94 TABLE 407, AND SHALL COMPLY WITH | | | FACBC-97 SECTION 4.15. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT.8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-09-14 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-09-14 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|