| Plan Review Stops For Permit 01081013 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2001-09-20 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-09-20 |
Time |
11:04 |
Rev Time |
2.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-20 00:00:00 | PROVISO | | | ------- | | | | | | SUBMIT PRODUCT TESTING FOR APPROVAL FOR | | | ALL EXTERIOR GLAZING AND DOORS. COMPLY | | | WITH WINDLOADS AND MISSILE IMPACT. | | | | | | | | | L.MARTINEZ | | | 659-8096 | | | #8456 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
N |
Date |
2001-10-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-04 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-04 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2001-10-04 00:00:00 | ************** NOTE********** | | | | | | PLANS PULLED FROM ELECTRICAL PLAN | | | REVIEW. PLANS TO BE SUBMITTED SEPARATELY | | | FOR ELEC PER CONTRACTOR, RAY DEVIO. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2001-10-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-03 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-03 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2001-10-04 00:00:00 | SAME NOTES AS BEFORE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-09-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-09-24 |
Time |
18:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-09-24 |
Time |
18:50 |
Sent To |
|
|
| Notes |
| 2001-09-24 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT IF THE SHOW | | | WINDOW WAS THE ONLY ISSUE, THE PLANS | | | COULD HAVE BEEN REDLINED. | | | PLEASE NOTE THAT ALL CHANGES TO SIGNED | | | AND SEALED PLANS, ARE TO BE DONE BY THE | | | ENGINEER OF RECORD PER FS/ FAC. 471.025 | | | | | | 2)NOTE: PLEASE NOTE THAT 600-5, LETTER | | | MENTIONS TENANT AJACENT TENANTS,?? | | | PLEASE CALRIFY HOW THIS MEETS 600-5. | | | | | | 3)NOTE: PLEASE NOTE THAT THE LOAD CALCU- | | | -LATIONS THAT WERE SUBMITTED ON SHEET 6 | | | WERE NOT COMPLETE AND SHOWN PER ART220. | | | PLEASE SHOW.215-5 TRACK LIGHTING 220-12B | | | NOTE CIRCUIT ADDED FOR SHOW WINDOW, NOT | | | SIGNED PER ENG OF REC. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. PLEASE NOTE THAT PLANS WERE | | | COMING BACK FOR OTHER COMMENTS. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-09-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-09-18 |
Time |
21:31 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-09-18 |
Time |
21:31 |
Sent To |
|
|
| Notes |
| 2001-09-18 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLEASE NOTE THAT COMPLETE LOAD | | | CALCUALTIONS WERE NOT SUBMITTED> PLEASE | | | SHOW! INCLUDING SQ FTETC. PER 220 | | | PLEASE SHOW TRACK LIGHTING PER 220-12B | | | | | | 2)NOTE: PLEASE NOTE MISSING SHOW WINDOW | | | RECEPTS PER 210-62/ LOADS PER 220-12A | | | | | | 3)NOTE: PLEASE NOTE/CLARIFY SIGN CIRCUIT | | | PER 600-5. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-09-20 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-09-20 |
Time |
07:26 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-09-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-09-24 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-09-24 |
Time |
15:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-08-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-28 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-28 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2001-08-28 00:00:00 | 1) PLANS NOT SIGNED AND SEALED. PLANS | | | CONTAIN ARCHITECHT'S TITLE BLOCK. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-09-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-20 |
Time |
08:41 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2001-09-20 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2001-09-20 00:00:00 | | | | | | | INSUFFICIENT INFORMATION FOR MECHANICAL | | | REVIEW. | | | | | | PLEASE SUBMIT PLANS WITH MECHANICAL | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2001-10-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-04 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2001-09-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-27 |
Time |
10:27 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-09-27 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2001-09-27 00:00:00 | DENIED | | | REFERENCE SPC-94 | | | | | | PLEASE ADDRESS PREVIOUS COMMENTS FROM | | | PAST REVIEWS. PRIMARY AND SECONDARY ROOF | | | DRAINAGE FOR EXISTING ROOF WITH CALCULA- | | | TIONS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-09-22 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-09-22 |
Time |
13:16 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-22 00:00:00 | PLUMBING PLAN REVIEW, DENIED | | | PLEASE ADDRESS PREVIOUS COMMENTS DATED | | | 09-05-01. | | | SHOW PRIMARY AND SECONDARY ROOF DRAINAGE | | | WITH CALCULATIONS,FOR THE EXISTING ROOF, | | | SIZES OF ROOF DRAINS AND SCUPPERS | | | THIS PERMIT IS FOR STORE FRONT ADDITION, | | | INTERIOR DEMOLITION AND BUILT-UP ROOF. | | | END OF COMMENT PAUL SCHMITZ | | | QUESTIONS 561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-09-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-05 |
Time |
13:48 |
Rev Time |
1.75 |
| Received By |
kstevens |
Date |
2001-09-05 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2001-09-05 00:00:00 | DENIED | | | REFERENCE SPC-94 | | | REVIEW FOR THIS PERMIT PER PAGE #1, | | | THE ONLY PLUMBING WILL BE FOR ROOF | | | DRAINS, SECONDARY ROOF DRAINS, AND | | | RELATED PIPING. | | | 1) PLEASE SUBMIT A STORM RISER DIAGRAM, | | | AND ROOF DRAIN, AND SECONDARY DRAIN | | | CALCULATIONS FOR NEW ROOF. PLEASE USE | | | SPC SEC. 1108, AND 1109. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-08-28 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-08-28 |
Time |
11:24 |
Rev Time |
0.25 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|