Plan Review Details - Permit 01080985
Plan Review Stops For Permit 01080985
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-09-13 Cont ID  
Sent By hpiskura Date 2001-09-13 Time 15:46 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-11-13 Cont ID  
Sent By dpalmer Date 2001-11-13 Time 07:29 Rev Time 0.00
Received By dpalmer Date 2001-11-13 Time 07:29 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-09-24 Cont ID  
Sent By dpalmer Date 2001-09-24 Time 17:06 Rev Time 0.00
Received By dpalmer Date 2001-09-24 Time 17:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-30 Cont ID  
Sent By dpalmer Date 2001-08-30 Time 07:24 Rev Time 0.00
Received By dpalmer Date 2001-08-30 Time 07:24 Sent To  
Notes
2001-08-30 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE
 MISSING REQ`D SIGN PER 600-5 AND LOADS
 SHOWN PER 220-3B-6.
  
 2)NOTE: PLEASE NOTE MISSING OUTLET(S)
 FOR SHOW WINDOW 210-62 AND LOADS PER
 220-12A,220-3B-7
  
 3)NOTE: PLEASE NOTE THAT NO INFORMATION
 SHOWN FOR MAIN SERVICE COMING IN?
 OCP OF MAIN DISC? AIC RATING?
 PLEASE NOTE THAT RISER SHOWS AND EQUIP-
 -MENT GROUNDING CONDUCTOR FROM METER TO
 MAIN? PLEASE NOTE THAT THIS WOULD BE
 PARALELLING THE NEUTRAL.
  
 4)NOTE: PLEASE NOTE THAT LOADS SHOWN
 ON PANEL SCHEDULE ARE SHOWN AT CONNECTED
 AMPERAGES? PLEASE SHOW LOAD CALCULATIONS
 AND ALL CONTINUOUS LOADS AT 125%
 LIGHTING) PER 220 AND 230-42/215-3
  
 5)NOTE: PLEASE NOTE THAT PLANS ARE NOT
 SHOWING GUTTER AT SAME LOCATION AS PANEL
 ? PLEASE CLARIFY. A/C DISCONNECTA ARE
 SHOWN AS BEING TAPPED CONDUCTORS AND
 NEED TO FALL UNDER 240-21 FOR TAPPED
 CONDUCTORS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REAVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-09-12 Cont ID  
Sent By lsmith Date 2001-09-12 Time 14:49 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-09-27 Cont ID  
Sent By mcarsill Date 2001-09-27 Time 10:39 Rev Time 0.00
Received By mcarsill Date 2001-09-27 Time 10:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-08-21 Cont ID  
Sent By mcarsill Date 2001-08-21 Time 11:20 Rev Time 0.00
Received By mcarsill Date 2001-08-21 Time 11:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-11-13 Cont ID  
Sent By pkrauss Date 2001-11-13 Time 16:20 Rev Time 0.30
Received By pkrauss Date 2001-11-13 Time 16:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-10-04 Cont ID  
Sent By pkrauss Date 2001-10-04 Time 14:28 Rev Time 0.35
Received By pkrauss Date 2001-10-04 Time 14:27 Sent To  
Notes
2001-10-04 00:00:00 
  
 MECHANICAL PLANS TO BE PULLED FROM
 SUBMITTAL.MECHANICAL CONTRACTOR TO
 APPLY FOR SEPARATE PERMIT.A/C
 EQUIPMENT REMAINING THE SAME. DUCT WORK
 MAY BE REPLACED AT A LATER DATE.
 PLEASE SUBMIT PLANS WIHT MECHANICAL
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-09-06 Cont ID  
Sent By pkrauss Date 2001-09-06 Time 15:08 Rev Time 0.40
Received By pkrauss Date 2001-09-06 Time 15:08 Sent To  
Notes
2001-09-06 00:00:00******************DENIED****************
  
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89 AS WELL AS AIR
 BALANCE SCHEDULE TO SHOW COMPLIANCE
 WITH 1997 SMC 501.2.
  
 CONDENSATE SHALL NOT GO TO THE SANITARY.
 MUST COMPLY WITH AMMENDED 1994 SPC 804.3
 #2 OR 3.
  
 ADDITIONAL PERMITS REQUIRED FOR HOODS,
 FIRE SUPRESSION, AND WALK-IN COOLERS.
 PLEASE PROVIDE PLANS AND MANUFACTURER
 SUBMITTAL DATA WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-11-13 Cont ID  
Sent By kstevens Date 2001-11-13 Time 08:43 Rev Time 0.50
Received By kstevens Date 2001-11-13 Time 08:43 Sent To  
Notes
2001-11-13 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) THREE COMPARTMENT SINK TO DRAIN INDIR
 ECTLY TO A FLOOR SINK PER SPC SEC 804.1.
  
 2) HAND SINK TO DRAIN DIRECTLY INTO SAN-
 ITARY NOT TO FLOOR SINK.
  
 3) VENT REQUIRED AT UPSTREAM OF EACH
 BRANCH, (BEFORE 1ST FLOOR SINK), PER
 SPC SEC 921.4.2.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-10-03 Cont ID  
Sent By dpalmer Date 2001-11-13 Time 07:29 Rev Time 1.00
Received By kstevens Date 2001-10-03 Time 22:05 Sent To  
Notes
2001-10-03 00:00:00PASSED/PROVISO
  
 PER SPC-94 SEC 60.7.83 AIR CHAMBERS
 SHALL COMPLY AND BE RECHARGABLE AND ACC-
 ESSIBLE PER WH-PDI 201. AIR CHAMBERS ARE
 A TEMPORY FIX AND SHOULD NOT BE USED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-09-04 Cont ID  
Sent By kstevens Date 2001-09-04 Time 13:42 Rev Time 1.50
Received By kstevens Date 2001-09-04 Time 13:42 Sent To  
Notes
2001-09-04 00:00:00DENIED
 REFERENCE: SPC-94 -
  
 1) PAGES A-6 & P-1, HUB DRAINS NOT ALLOW
 ED. INDIRECT WASTE TO DRAIN TO A FLOOR
 SINK PER SPC-94 SECTIONS 804.5 AND 807.
  
 2) WATER HEATER TO BE READILY ACCESSIBLE
 PER SPC-94 SECTION 501.7. IF ON A SHELF,
 A PERMINATE SHIPS LADDER AND A PERMINATE
 WORK PLATFORM ARE REQUIRED. THE WORK
 AREA SHALL BE PROVIDED THAT IS A MINIMUM
 OF 30"WIDE FROM THE BASE OF THE HEATER.
 SMC-97 SECTION 304.4.1.
  
 3) PAGE A-6, WATER FILTRATION SYSTEM
 SHALL BE NSF APPROVED PER SPC SEC. 615.1
 615.2. PLEASE SUBMIT MANUFACTURE INFO.
  
 4) PAGE P-1, 4" HUB DRAIN, 3" HUB DRAIN,
 AND 3" HUB DRAIN NOT ALLOWED. SEE COM-
 MENT #1.
  
 5) 3" VENT THRU ROOF REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-09-12 Cont ID  
Sent By lsmith Date 2001-09-12 Time 14:49 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***