Plan Review Details - Permit 01080756
Plan Review Stops For Permit 01080756
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-09-10 Cont ID  
Sent By hpiskura Date 2001-09-10 Time 09:47 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-08-28 Cont ID  
Sent By dpalmer Date 2001-08-28 Time 17:02 Rev Time 0.00
Received By dpalmer Date 2001-08-28 Time 17:02 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-09-12 Cont ID  
Sent By lsmith Date 2001-09-12 Time 07:55 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-08-16 Cont ID  
Sent By mcarsill Date 2001-08-16 Time 15:45 Rev Time 0.00
Received By mcarsill Date 2001-08-16 Time 15:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-10-02 Cont ID  
Sent By pkrauss Date 2001-10-02 Time 13:13 Rev Time 0.40
Received By pkrauss Date 2001-10-02 Time 12:25 Sent To  
Notes
2001-10-02 00:00:00******************PROVISO***************
  
  
 EXISTING RTU FRESH AIR INTAKE SHALL BE
 A MINIMUM OF 10' FROM ANY EXHAUST
 TERMINATING AT THE ROOF.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS AS PER NFPA
 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-09-06 Cont ID  
Sent By pkrauss Date 2001-09-06 Time 14:00 Rev Time 0.40
Received By pkrauss Date 2001-09-06 Time 13:54 Sent To  
Notes
2001-09-06 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE AIR BALANCE SCHEDULE TO
 SHOW COMPLIANCE WITH 1997 SMC 501.2.
  
 OUTSIDE AIR CALCULATIONS ARE INCORRECT
 FOR A BEAUTY SALON TYPE OF ENVIRONMENT.
 ASHRAE 62-89 TABLE 2, INDICATES 25 CFM
 PER PERSON.
  
 EXHAUST FROM MANICURE AREA SHALL COMPLY
 WITH ASHRAE 62-89 5.7, CONTAMINANTS FROM
 LOCAL SOURCES WITHIN THE SPACE SHALL BE
 CONTROLLED BY COLLECTION AND REMOVAL AS
 CLOSE TO THE SOURCE AS PRACTICABLE.
  
  
 PRIOR TO CONNECTING TO ANY EXISTING DUCT
 WORK, CALL FOR AN INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-10-09 Cont ID  
Sent By kstevens Date 2001-10-09 Time 13:11 Rev Time 0.33
Received By kstevens Date 2001-10-09 Time 13:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-09-28 Cont ID  
Sent By kstevens Date 2001-09-28 Time 20:17 Rev Time 0.50
Received By kstevens Date 2001-09-28 Time 20:17 Sent To  
Notes
2001-09-28 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PAGE P1, KEY NOTE #2, ALSO PAGE P2,
 WATER ISOMETRIC. BACKFLOW IS REQUIRED ON
 WATER SERVICE TO THIS BUILDING TO PRO-
 TECT THE POTABLE WATER FROM THE COSMO-
 TOLOGY BUILDING.
  
 2) PAGE P2, WATER ISOMETRIC. AIRCHAMBERS
 ARE STILL SHOWN. PLEASE REMOVE IF NOT
 USING AIR CHAMBERS. WATER HAMMER ARREST-
 ORS SHALL BE INSTALLED PER MANUFACTURES
 INSTALLATION INSTRUCTIONS AND WH-PDI 201
 AND NOT AT THE TOP OF THE DROP AS SHOWN.
 SEE ATTACHED SHEET FROM WH-PDI 201 FOR
 EXAMPLE OF LOCATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-31 Cont ID  
Sent By kstevens Date 2001-08-31 Time 17:53 Rev Time 1.50
Received By kstevens Date 2001-08-31 Time 17:53 Sent To  
Notes
2001-08-31 00:00:00DENIED
 REFERENCE: SPC-94 - FCABC-97
  
 1) PAGES A1 & A2, PER FCABC-97 SECTION
 4.17.3, EXCEPTION: NEW CONSTRUCTION (2),
 THE ACCESSIBLE WATER CLOSET SHALL BE
 LOCATED IN THE CORNER, DIAGONAL TO THE
 DOOR.
  
 2) PAGE A1 & A2, PER FCABC-97 SECTION
 4.22.5, IF URNALS ARE PROVIDED, THEN AT
 LEAST ONE SHALL COMPLY WITH 4.18.
  
 3) PAGE P1, KEY NOTES #2, ALSO PAGE P2,
 WATER ISOMETRIC, BACKFLOW IS REQUIRED
 ON WATER SERVICE.
  
 4) PAGE P1, KEY NOTES #'S 10 & 11,
 PRESSURE RELIEF LINE ONLY REQUIRED TO BE
 3/4", AND PAN DRAIN LINE IS REQUIRED TO
 BE 1".
  
 5) PAGE P1, KEY NOTES #'S 7 & 8 SHOULD
 BE REVERSED.
  
 6) PAGE P2, GENERAL NOTES #16, AIR CHAM-
 BERS SHALL COMPLY WITH SPC-94 SECTIONS
 607.8.2 & 607.8.3 (ACCESSABLE AND RE-
 CHARGEABLE). IF WATER HAMMER ARRESTORS
 ARE USED, THEY SHALL COMPLY WITH MANU-
 FACTURE'S INSTALLATION INSTRUCTIONS WITH
 RESPECT TO SIZE AND LOCATION. SEE PDI-
 WH 201 ALSO.
  
 7) PAGES A1, A2, P1 & P2. FLOOR DRAINS
 ARE REQUIRED IN PUBLIC BATH ROOMS. ALSO
 THEY ARE REQUIRED TO HAVE TRAP PRIMERS
 TO MAINTAIN WATER SEAL. SPC-94 SECTION
 409.4.1.1.
  
 8) PAGES A1, A2 & P1, SINK IN DISPENSARY
 TO COMPLY WITH FACBC-97 SECTION 4.24
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-09-12 Cont ID  
Sent By lsmith Date 2001-09-12 Time 07:55 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***