| Plan Review Stops For Permit 01080756 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2001-09-10 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-09-10 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-08-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-28 |
Time |
17:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-28 |
Time |
17:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-09-12 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-09-12 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-08-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-16 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-16 |
Time |
15:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-10-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-02 |
Time |
13:13 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-10-02 |
Time |
12:25 |
Sent To |
|
|
| Notes |
| 2001-10-02 00:00:00 | ******************PROVISO*************** | | | | | | | | | EXISTING RTU FRESH AIR INTAKE SHALL BE | | | A MINIMUM OF 10' FROM ANY EXHAUST | | | TERMINATING AT THE ROOF. | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | | IN NORMALLY OCCUPIED AREAS AS PER NFPA | | | 90A 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-09-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-06 |
Time |
14:00 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-09-06 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2001-09-06 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE AIR BALANCE SCHEDULE TO | | | SHOW COMPLIANCE WITH 1997 SMC 501.2. | | | | | | OUTSIDE AIR CALCULATIONS ARE INCORRECT | | | FOR A BEAUTY SALON TYPE OF ENVIRONMENT. | | | ASHRAE 62-89 TABLE 2, INDICATES 25 CFM | | | PER PERSON. | | | | | | EXHAUST FROM MANICURE AREA SHALL COMPLY | | | WITH ASHRAE 62-89 5.7, CONTAMINANTS FROM | | | LOCAL SOURCES WITHIN THE SPACE SHALL BE | | | CONTROLLED BY COLLECTION AND REMOVAL AS | | | CLOSE TO THE SOURCE AS PRACTICABLE. | | | | | | | | | PRIOR TO CONNECTING TO ANY EXISTING DUCT | | | WORK, CALL FOR AN INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-10-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-09 |
Time |
13:11 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-10-09 |
Time |
13:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-09-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-28 |
Time |
20:17 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-09-28 |
Time |
20:17 |
Sent To |
|
|
| Notes |
| 2001-09-28 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) PAGE P1, KEY NOTE #2, ALSO PAGE P2, | | | WATER ISOMETRIC. BACKFLOW IS REQUIRED ON | | | WATER SERVICE TO THIS BUILDING TO PRO- | | | TECT THE POTABLE WATER FROM THE COSMO- | | | TOLOGY BUILDING. | | | | | | 2) PAGE P2, WATER ISOMETRIC. AIRCHAMBERS | | | ARE STILL SHOWN. PLEASE REMOVE IF NOT | | | USING AIR CHAMBERS. WATER HAMMER ARREST- | | | ORS SHALL BE INSTALLED PER MANUFACTURES | | | INSTALLATION INSTRUCTIONS AND WH-PDI 201 | | | AND NOT AT THE TOP OF THE DROP AS SHOWN. | | | SEE ATTACHED SHEET FROM WH-PDI 201 FOR | | | EXAMPLE OF LOCATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-08-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-08-31 |
Time |
17:53 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2001-08-31 |
Time |
17:53 |
Sent To |
|
|
| Notes |
| 2001-08-31 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FCABC-97 | | | | | | 1) PAGES A1 & A2, PER FCABC-97 SECTION | | | 4.17.3, EXCEPTION: NEW CONSTRUCTION (2), | | | THE ACCESSIBLE WATER CLOSET SHALL BE | | | LOCATED IN THE CORNER, DIAGONAL TO THE | | | DOOR. | | | | | | 2) PAGE A1 & A2, PER FCABC-97 SECTION | | | 4.22.5, IF URNALS ARE PROVIDED, THEN AT | | | LEAST ONE SHALL COMPLY WITH 4.18. | | | | | | 3) PAGE P1, KEY NOTES #2, ALSO PAGE P2, | | | WATER ISOMETRIC, BACKFLOW IS REQUIRED | | | ON WATER SERVICE. | | | | | | 4) PAGE P1, KEY NOTES #'S 10 & 11, | | | PRESSURE RELIEF LINE ONLY REQUIRED TO BE | | | 3/4", AND PAN DRAIN LINE IS REQUIRED TO | | | BE 1". | | | | | | 5) PAGE P1, KEY NOTES #'S 7 & 8 SHOULD | | | BE REVERSED. | | | | | | 6) PAGE P2, GENERAL NOTES #16, AIR CHAM- | | | BERS SHALL COMPLY WITH SPC-94 SECTIONS | | | 607.8.2 & 607.8.3 (ACCESSABLE AND RE- | | | CHARGEABLE). IF WATER HAMMER ARRESTORS | | | ARE USED, THEY SHALL COMPLY WITH MANU- | | | FACTURE'S INSTALLATION INSTRUCTIONS WITH | | | RESPECT TO SIZE AND LOCATION. SEE PDI- | | | WH 201 ALSO. | | | | | | 7) PAGES A1, A2, P1 & P2. FLOOR DRAINS | | | ARE REQUIRED IN PUBLIC BATH ROOMS. ALSO | | | THEY ARE REQUIRED TO HAVE TRAP PRIMERS | | | TO MAINTAIN WATER SEAL. SPC-94 SECTION | | | 409.4.1.1. | | | | | | 8) PAGES A1, A2 & P1, SINK IN DISPENSARY | | | TO COMPLY WITH FACBC-97 SECTION 4.24 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-09-12 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-09-12 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|