Plan Review Details - Permit 01080750
Plan Review Stops For Permit 01080750
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-08-15 Cont ID  
Sent By mcarsill Date 2001-08-15 Time 15:47 Rev Time 0.00
Received By mcarsill Date 2001-08-15 Time 15:47 Sent To  
Notes
2001-08-15 00:00:00WHEN THE PLANS WERE SUBMITTED ONLY 114'
 6" PVC WAS HIGHLIGHTED ON THE PLANS.
 ON 8/15/01 THIS OFFICE CONTACTED SCOTT
 LEITH OF MESSIER LAND DEVELOPING. HE
 WAS ADVISED THAT ALL OF THE UNDERGOUND
 PIPING ON THE PLANS THAT ARE CONNECTED
 TO THE FIRE HYDRANTS WILL BE CONSIDERED
 THE FIRE MAIN SINCE A SEPARATE WATER
 LINE WILL BE INSTALLED. THIS MEANS THAT
 THE FIRE LINE WILL BE REQUIRED TO BE
 TESTED AND INSTALLED IN ACCORDANCE WITH
 NFPA 24. INSPECTIONS WILL BE PERFORMED
 BY FIRE RESCUE AND ELECTRONIC SWITCHES
 WILL BE REQUIRED ON THE BACKFLOW
 DEVICES. THE PLANS IDENTIFY THIS LINE
 AS A WATER MAIN, THIS IS NOT CORRECT.
 THE LINE IS A DEDICATED FIRE LINE
 ON PRIVATE PROPERTY.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910