| Plan Review Stops For Permit 01080750 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-08-15 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-15 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-15 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2001-08-15 00:00:00 | WHEN THE PLANS WERE SUBMITTED ONLY 114' | | | 6" PVC WAS HIGHLIGHTED ON THE PLANS. | | | ON 8/15/01 THIS OFFICE CONTACTED SCOTT | | | LEITH OF MESSIER LAND DEVELOPING. HE | | | WAS ADVISED THAT ALL OF THE UNDERGOUND | | | PIPING ON THE PLANS THAT ARE CONNECTED | | | TO THE FIRE HYDRANTS WILL BE CONSIDERED | | | THE FIRE MAIN SINCE A SEPARATE WATER | | | LINE WILL BE INSTALLED. THIS MEANS THAT | | | THE FIRE LINE WILL BE REQUIRED TO BE | | | TESTED AND INSTALLED IN ACCORDANCE WITH | | | NFPA 24. INSPECTIONS WILL BE PERFORMED | | | BY FIRE RESCUE AND ELECTRONIC SWITCHES | | | WILL BE REQUIRED ON THE BACKFLOW | | | DEVICES. THE PLANS IDENTIFY THIS LINE | | | AS A WATER MAIN, THIS IS NOT CORRECT. | | | THE LINE IS A DEDICATED FIRE LINE | | | ON PRIVATE PROPERTY. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|