Plan Review Details - Permit 01080701
Plan Review Stops For Permit 01080701
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-09-17 Cont ID  
Sent By hpiskura Date 2001-09-17 Time 12:27 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-01 Cont ID  
Sent By dpalmer Date 2001-10-01 Time 23:48 Rev Time 0.00
Received By dpalmer Date 2001-10-01 Time 23:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-28 Cont ID  
Sent By dpalmer Date 2001-08-28 Time 21:25 Rev Time 0.00
Received By dpalmer Date 2001-08-28 Time 21:25 Sent To  
Notes
2001-08-28 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT COVER SHEET
 SHOWS ELECTRICAL UNDER THE "96" NEC.
 PLEASE NOTE WE ARE UNDER "99" NEC.
 PLEASE CORRECT.
  
 2)NOTE: PLEASE ALSO NOTE THAT PER
 CITY OF WEST PALM BEACH LOCAL AMENDMENTS
 210-50. OUTLET SPACING TO MEET LOCAL
 CODE. EVERY 20'FT OF UNENCUMBERED WALL
 SPACE.
  
 3)NOTE: PLEASE NOTE THAT LOADS FOR TRACK
 LIGHTING NEEDS TO BE SHOWN PER 220-12B.
  
 4)NOTE: PLEASE CLARIFY THAT ALL
 ELECTRICAL SHOWN ON SINGLE LINE DIAGRAM
 IS EXISTING. PANELS SHOWN AS EXISTING,
 WHAT ABOUT WIRE? PLEASE NOTE THAT THE
 TAPPED CONDUCTOR FROM DISCONNECT WITH
 200A OCP FOR #3. THIS IS OK BUT, #3
 NEEDS TO TERMINATE IN A PANEL WITH OCP
 THAT LIMITS LOAD TO 100AMPS. PLEASE
 NOTE THAT PANEL IS SHOWN WITH BUS ONLY??
 PLEASE NOTE THAT THE #3`S ARE RATED FOR
 100A PER 310-16 AND ALSO TERMINATE IN
 A 125A MCB PANEL"A"?? PLEASE NOTE THAT
 TAPPED CONDUCTORS NEED TO MEET ART:
 240-21 FOR 10' AND 25'.
  
 5)NOTE: PLEASE NOTE THAT PANEL "B "
 NEEDS TO BE SHOWN ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-09-06 Cont ID  
Sent By lsmith Date 2001-09-06 Time 08:01 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-10-11 Cont ID  
Sent By mcarsill Date 2001-10-11 Time 16:04 Rev Time 0.00
Received By mcarsill Date 2001-10-11 Time 16:04 Sent To  
Notes
2001-10-11 00:00:00FS PERMIT # 01090133 ALREADY SUBMITTED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-10-10 Cont ID  
Sent By mcarsill Date 2001-10-10 Time 14:23 Rev Time 0.00
Received By mcarsill Date 2001-10-10 Time 14:23 Sent To  
Notes
2001-10-10 00:00:00COULD NOT LOCATE FIRE SPRINKLER
 DRAWINGS WITH RE-SUBMITTED PLANS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-20 Cont ID  
Sent By mcarsill Date 2001-08-20 Time 08:14 Rev Time 0.00
Received By mcarsill Date 2001-08-20 Time 08:14 Sent To  
Notes
2001-08-20 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
 2) INTERIOR FINISH TO COMPLY WITH
 STANDARD BUILDING CODE 1997 AND THE
 LIFE SAFETY CODE, 1985 EDITION.
 3) WRONG EDITION OF THE LIFE SAFETY CODE
 NOTED IN CODES AND ORDINANCES SECTION.
 SHOULD READ 1985 EDITION OF THE LIFE
 SAFETY CODE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-10-10 Cont ID  
Sent By pkrauss Date 2001-10-01 Time 09:07 Rev Time 0.45
Received By pkrauss Date 2001-10-01 Time 08:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-09-07 Cont ID  
Sent By pkrauss Date 2001-09-07 Time 10:16 Rev Time 0.45
Received By pkrauss Date 2001-09-07 Time 10:16 Sent To  
Notes
2001-09-07 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
  
 2.NO COMBUSTIBLES ABOVE THE CEILING
 IN THE RETURN AIR PLENUM.
 1997 SMC 609.1.1
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS. 1997 SMC
 406.1 AND NFPA 90A 4-4.4.3.
  
 4.AIR FROM THE RESTROOMS SHALL NOT BE
 RECIRCULATED AS PER 1997 SMC 503.3.1
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-10-15 Cont ID  
Sent By kstevens Date 2001-10-15 Time 14:25 Rev Time 0.50
Received By kstevens Date 2001-10-15 Time 14:25 Sent To  
Notes
2001-10-15 00:00:00PASSED/PROVISO
  
 MINIMUM SIZE FLOOR DRAINS TO BE 3".

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-10-11 Cont ID  
Sent By kstevens Date 2001-10-11 Time 09:16 Rev Time 0.50
Received By kstevens Date 2001-10-11 Time 09:16 Sent To  
Notes
2001-10-11 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) FLOOR DRAINS ARE REQUIRED TO BE A
 MINIMUM OF 3" PER SPC-94 SEC 409.4.1.1.
 PLEASE CORRECT SIZE OF FLOOR DRAINS AND
 RESUBMIT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-30 Cont ID  
Sent By kstevens Date 2001-08-30 Time 15:24 Rev Time 1.50
Received By kstevens Date 2001-08-30 Time 15:24 Sent To  
Notes
2001-08-30 00:00:00DENIED
  
 REFERENCE - SPC-94 - FACBC-97
  
 1) FLOOR DRAINS ARE REQUIRED IN PUBLIC
 TOILET ROOMS PER SPC-94 SECT. 409.4.1.1.
 FLOOR DRAIN SHALL BE EQUIPPED WITH A
 TRAP PRIMER. PAGE AO.1/P3.1
  
 2) SANITARY RISER DIAGRAM REQUIRED WITH
 ALL PIPE SIZES INDICATED.
  
 3) BENCH IN DRESSING ROOM SHALL BE FIXED
 TO THE WALL WITH THE LONGEST DIMENSION.
 PAGE A0.1 AND PAGE A7.1 DETAIL #4
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-09-06 Cont ID  
Sent By lsmith Date 2001-09-06 Time 08:01 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***