Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-08-22 Cont ID  
Sent By pkrauss Date 2001-08-22 Time 11:17 Rev Time 0.35
Received By pkrauss Date 2001-08-22 Time 11:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-16 Cont ID  
Sent By pkrauss Date 2001-08-16 Time 07:42 Rev Time 0.35
Received By pkrauss Date 2001-08-16 Time 07:39 Sent To  
Notes
2001-08-16 00:00:00*******************DENIED***************
  
  
 PLEASE SUBMIT THE FOLLOWING INFORMATION
 FOR REVIEW:
  
  
 1.INDICATE RETURN AIR LOCATION AND
 GRILL SIZE ON PLAN.
  
 2.INDICATE GRILL SIZE FOR SUPPLY DROPS
 UPSTAIRS.
  
 3.CLARIFY LOCATION OF AHU, CLOSET OR
 ATTIC.SHOULD AHU BE LOCATED IN THE
 ATTIC, SHALL COMPLY WITH 1997 SMC
 304.4.1 OPENING NO LESS THAN 22" X
 36".ALSO AMENDED 1997 SMC 304.4.2,
 SHALL HAVE A CONVIENCE OUTLET AND
 A LIGHT ON THE SERVICE SIDE OF THE
 EQUIPMENT CONTROLLED BY A SWITCH
 AT THE ACCESS OPENING.
  
 4.INDICATE LINE SIZE OF LIQUID,
 SUCTION AND CONDENSATE.
  
 5.LIST MATERIAL FOR CONDENSATE AND
 TERMINATION.
  
 6.PLEASE INDICATE MATERIAL AND R VALUE
 OF DUCTWORK.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.