| Plan Review Stops For Permit 01080628 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-10-19 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-06 |
Time |
10:10 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
2001-10-19 |
Time |
16:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-09-17 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-09-17 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-17 00:00:00 | SBC 704.3 REQUIRES A ONE HOUR FIRE | | | RESISTANT SEPARATION BETWEEN INDIVIDUAL | | | TENANTS.SBC 1001.1.3 PROHIBITS EGRESS | | | THROUGH ADJACENT TENANT SPACES.TO | | | COMPLY WITH THOSE SECTIONS, THE | | | EXISTING STORE FRONT GLASS MUST MEET | | | THE FIRE RATING REQUIREMENTS.PLEASE | | | REVISE AS NECESSARY. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2001-11-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-05 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-05 |
Time |
08:59 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2001-10-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-22 |
Time |
21:54 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-22 |
Time |
21:54 |
Sent To |
|
|
| Notes |
| 2001-10-22 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT NOW JUST THE | | | TWO SETS OF PLANS ARE BEING SUBMITTED | | | FOR REVIEW. | | | PLEASE NOTE THAT FEED GOING TO GUTTER | | | THAT FEEDS DISC "DS" AND PANEL "3MA" | | | DOESN'T SHOW ANY MAIN FEEDING THIS? | | | PLEASE CALRFIY? TAPPED CONDUCTORS? | | | NOTHING SHOWN FOR "MDP" SCHEDULE FEEDING | | | THIS EQUIPMENT? OCP?. PLEASE NOTE TAPS | | | PER 240-21. | | | | | | 2)NOTE: PLEASE NOTE THAT NOTE FROM FIRST | | | TWO REVIEWS, PLEASE CLARIFY IF REVISED | | | LOADS SHOWN ARE AT THE 125% ?? | | | PLEASE CALRIFY. | | | | | | 3)NOTE: PLEASE CLARIFY WHERE DISC "DS" | | | IS BEING FED FROM? PLEASE NOTE THAT LOAD | | | SHOWN FOR PANEL "3MA" IS AT 336AMPS, | | | PLEASE NOTE THAT PANEL SCHEDULE FOR 3MA | | | DOESN'TSHOW FEEDING DISC "DS"? | | | FEEDERS GOINGTO GUTTER ARE RATED FOR | | | 380AMPS? PLEASE CLARIFY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-10-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-10 |
Time |
21:37 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-10 |
Time |
21:37 |
Sent To |
|
|
| Notes |
| 2001-10-10 00:00:00 | ************* UNSAT ************* | | | | | | PLEASE NOTE THAT NOTE FROM FIRST REVIEW | | | NEEDS TO BE SHOWN.? ALL CONTINUOUS LOADS | | | AT 125%. PER 230-42/215-2/3 | | | | | | | | | 1)NOTE: PLEASE ALSO NOTE THAT FOUR | | | DIFFERENT SETS OF PLANS WERE SUBMITTED | | | SHOW DIFF LIGHTING AND FLOOOR PLANS | | | AND DATED AS NEW PLANS? PLEASE ALSO | | | NOTE THAT COMPLETELY REVISED RISER | | | DIAGRAMS WERE SUBMITTED W/ OLD FLOOR | | | PLANS???? YET NEW FLOOR PLANS ARE WITH | | | OLD RISER DIAGRAM WITH REVISED SIGNED | | | AND SEALED BY ENGINEER OF RECORD?????? | | | | | | | | | PLEASE SUBMIT TWO SETS OF PLANS FOR | | | REVIEW AND TAKE OLD ELECTRICAL OUT? | | | IT IS NOT CLEAR WHICH ONES THEY ARE? | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | 2)NOTE: PLEASE SUBMIT PANEL (MDP ) | | | SCHEDULE. PLEASE CLARIFY IF MDP HAS ONE | | | MAIN ? | | | SIZE OF EXISTING MDP? OCP | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-08-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-28 |
Time |
21:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-28 |
Time |
21:12 |
Sent To |
|
|
| Notes |
| 2001-08-28 00:00:00 | **************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT ALL CONTINUOUS | | | LOADS AND LARGEST MOTOR NEEDS TO BE | | | SHOWN AT 125%. (LIGHTING) | | | 230-42/215-3 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-09-04 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-09-04 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-10-11 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-11 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-11 |
Time |
15:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-08-15 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-15 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-15 |
Time |
13:03 |
Sent To |
|
|
| Notes |
| 2001-08-15 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. PLANS INDICATE THAT FLOOR | | | WILL BE COMPLETELY FIRE SPRINKLER | | | PROTECTED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-11-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-06 |
Time |
10:08 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-11-06 |
Time |
08:09 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-10-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-05 |
Time |
10:10 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-10-15 |
Time |
12:18 |
Sent To |
|
|
| Notes |
| 2001-10-15 00:00:00 | ******************PROVISO*************** | | | | | | | | | SPOKE WITH WAYNE JOHNSON (JLSD), ENG OF | | | RECORD.TO SUBMIT OUTSIDE AIR | | | CALCULATIONS FOR 3RD FLOOR FOR BY | | | LETTER. | | | 10-15-01PHK |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-09-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-07 |
Time |
08:07 |
Rev Time |
2.00 |
| Received By |
pkrauss |
Date |
2001-09-06 |
Time |
15:31 |
Sent To |
|
|
| Notes |
| 2001-09-07 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | | ASHRAE 62-1989. | | | | | | 2.AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2. | | | | | | 3.NO COMBUSTIBLES ABOVE THE CEILING | | | IN THE RETURN AIR PLENUM. | | | | | | 4.FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | | AS REQUIRED AS PER 1997 SMC 406.1. | | | | | | 5.NOTIFICATION TO ALARM/STROBE AS PER | | | NFPA 90A 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-11-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-05 |
Time |
10:10 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-11-05 00:00:00 | F/S SINK ADDED FOR CONDENSATE. PES | | 2001-10-21 00:00:00 | PLUMBING REVIEW, F/S FOR CONDENSATE. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2001-08-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-08-30 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2001-10-21 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2001-08-30 00:00:00 | PASSED/PROVISO | | | | | | PAGE P-1, CONDENSATE TO RUN TO FLOOR | | | SINK. HUB DRAINS NOT ALLOWED. SPC-94 | | | 804.3 AND 807. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-09-04 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-09-04 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|