Plan Review Details - Permit 01080628
Plan Review Stops For Permit 01080628
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-10-19 Cont ID  
Sent By pkrauss Date 2001-11-06 Time 10:10 Rev Time 2.00
Received By jwitmer Date 2001-10-19 Time 16:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-09-17 Cont ID  
Sent By hpiskura Date 2001-09-17 Time 11:09 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-09-17 00:00:00SBC 704.3 REQUIRES A ONE HOUR FIRE
 RESISTANT SEPARATION BETWEEN INDIVIDUAL
 TENANTS.SBC 1001.1.3 PROHIBITS EGRESS
 THROUGH ADJACENT TENANT SPACES.TO
 COMPLY WITH THOSE SECTIONS, THE
 EXISTING STORE FRONT GLASS MUST MEET
 THE FIRE RATING REQUIREMENTS.PLEASE
 REVISE AS NECESSARY.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-11-05 Cont ID  
Sent By dpalmer Date 2001-11-05 Time 10:10 Rev Time 0.00
Received By dpalmer Date 2001-11-05 Time 08:59 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-10-22 Cont ID  
Sent By dpalmer Date 2001-10-22 Time 21:54 Rev Time 0.00
Received By dpalmer Date 2001-10-22 Time 21:54 Sent To  
Notes
2001-10-22 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT NOW JUST THE
 TWO SETS OF PLANS ARE BEING SUBMITTED
 FOR REVIEW.
 PLEASE NOTE THAT FEED GOING TO GUTTER
 THAT FEEDS DISC "DS" AND PANEL "3MA"
 DOESN'T SHOW ANY MAIN FEEDING THIS?
 PLEASE CALRFIY? TAPPED CONDUCTORS?
 NOTHING SHOWN FOR "MDP" SCHEDULE FEEDING
 THIS EQUIPMENT? OCP?. PLEASE NOTE TAPS
 PER 240-21.
  
 2)NOTE: PLEASE NOTE THAT NOTE FROM FIRST
 TWO REVIEWS, PLEASE CLARIFY IF REVISED
 LOADS SHOWN ARE AT THE 125% ??
 PLEASE CALRIFY.
  
 3)NOTE: PLEASE CLARIFY WHERE DISC "DS"
 IS BEING FED FROM? PLEASE NOTE THAT LOAD
 SHOWN FOR PANEL "3MA" IS AT 336AMPS,
 PLEASE NOTE THAT PANEL SCHEDULE FOR 3MA
 DOESN'TSHOW FEEDING DISC "DS"?
 FEEDERS GOINGTO GUTTER ARE RATED FOR
 380AMPS? PLEASE CLARIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-10-10 Cont ID  
Sent By dpalmer Date 2001-10-10 Time 21:37 Rev Time 0.00
Received By dpalmer Date 2001-10-10 Time 21:37 Sent To  
Notes
2001-10-10 00:00:00************* UNSAT *************
  
 PLEASE NOTE THAT NOTE FROM FIRST REVIEW
 NEEDS TO BE SHOWN.? ALL CONTINUOUS LOADS
 AT 125%. PER 230-42/215-2/3
  
  
 1)NOTE: PLEASE ALSO NOTE THAT FOUR
 DIFFERENT SETS OF PLANS WERE SUBMITTED
 SHOW DIFF LIGHTING AND FLOOOR PLANS
 AND DATED AS NEW PLANS? PLEASE ALSO
 NOTE THAT COMPLETELY REVISED RISER
 DIAGRAMS WERE SUBMITTED W/ OLD FLOOR
 PLANS???? YET NEW FLOOR PLANS ARE WITH
 OLD RISER DIAGRAM WITH REVISED SIGNED
 AND SEALED BY ENGINEER OF RECORD??????
  
  
 PLEASE SUBMIT TWO SETS OF PLANS FOR
 REVIEW AND TAKE OLD ELECTRICAL OUT?
 IT IS NOT CLEAR WHICH ONES THEY ARE?
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 2)NOTE: PLEASE SUBMIT PANEL (MDP )
 SCHEDULE. PLEASE CLARIFY IF MDP HAS ONE
 MAIN ?
 SIZE OF EXISTING MDP? OCP
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-28 Cont ID  
Sent By dpalmer Date 2001-08-28 Time 21:12 Rev Time 0.00
Received By dpalmer Date 2001-08-28 Time 21:12 Sent To  
Notes
2001-08-28 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS AND LARGEST MOTOR NEEDS TO BE
 SHOWN AT 125%. (LIGHTING)
 230-42/215-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-09-04 Cont ID  
Sent By lsmith Date 2001-09-04 Time 13:19 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-10-11 Cont ID  
Sent By mcarsill Date 2001-10-11 Time 15:38 Rev Time 0.00
Received By mcarsill Date 2001-10-11 Time 15:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-15 Cont ID  
Sent By mcarsill Date 2001-08-15 Time 13:03 Rev Time 0.00
Received By mcarsill Date 2001-08-15 Time 13:03 Sent To  
Notes
2001-08-15 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS. PLANS INDICATE THAT FLOOR
 WILL BE COMPLETELY FIRE SPRINKLER
 PROTECTED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-11-06 Cont ID  
Sent By pkrauss Date 2001-11-06 Time 10:08 Rev Time 0.45
Received By pkrauss Date 2001-11-06 Time 08:09 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-10-15 Cont ID  
Sent By dpalmer Date 2001-11-05 Time 10:10 Rev Time 0.45
Received By pkrauss Date 2001-10-15 Time 12:18 Sent To  
Notes
2001-10-15 00:00:00******************PROVISO***************
  
  
 SPOKE WITH WAYNE JOHNSON (JLSD), ENG OF
 RECORD.TO SUBMIT OUTSIDE AIR
 CALCULATIONS FOR 3RD FLOOR FOR BY
 LETTER.
 10-15-01PHK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-09-07 Cont ID  
Sent By pkrauss Date 2001-09-07 Time 08:07 Rev Time 2.00
Received By pkrauss Date 2001-09-06 Time 15:31 Sent To  
Notes
2001-09-07 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-1989.
  
 2.AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2.
  
 3.NO COMBUSTIBLES ABOVE THE CEILING
 IN THE RETURN AIR PLENUM.
  
 4.FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 AS REQUIRED AS PER 1997 SMC 406.1.
  
 5.NOTIFICATION TO ALARM/STROBE AS PER
 NFPA 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-11-05 Cont ID  
Sent By dpalmer Date 2001-11-05 Time 10:10 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-11-05 00:00:00F/S SINK ADDED FOR CONDENSATE. PES
2001-10-21 00:00:00PLUMBING REVIEW, F/S FOR CONDENSATE.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-08-30 Cont ID  
Sent By kstevens Date 2001-08-30 Time 10:38 Rev Time 0.00
Received By pschmitz Date 2001-10-21 Time 15:08 Sent To  
Notes
2001-08-30 00:00:00PASSED/PROVISO
  
 PAGE P-1, CONDENSATE TO RUN TO FLOOR
 SINK. HUB DRAINS NOT ALLOWED. SPC-94
 804.3 AND 807.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-09-04 Cont ID  
Sent By lsmith Date 2001-09-04 Time 13:19 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved