Plan Review Details - Permit 01080557
Plan Review Stops For Permit 01080557
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-05-02 Cont ID  
Sent By hpiskura Date 2002-05-02 Time 09:33 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-05-02 00:00:00FOR REVISIONS DATED 3/27/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-12-07 Cont ID  
Sent By jwitmer Date 2001-12-07 Time 07:46 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-12-07 00:00:00PROVISO: CONTRACTOR PULLED STOREFRONT
 FROM PERMIT, SEPERATE PERMIT/W ASSOCI-
 ATED FEES.
 STORM SHUTTERS REQUIRED FOR NEW GLAZED
 OPENINGS WITHOUT LARGE MISSLE IMPACT
 TESTING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-11-20 Cont ID  
Sent By jwitmer Date 2001-11-20 Time 11:51 Rev Time 1.75
Received By jwitmer Date 2001-11-20 Time 11:50 Sent To  
Notes
2001-11-20 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01080557
 112 N DIXIE HWY
 BERET & BAGUETTE
 FRENCH BAKERY & COFFEE
 MARION CONSTRUCTION
 TEL: 722-8472
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- SHEET EX-1 RE: CAPPING & SCUPPERS,
 SHOW COMPLIANCE WITH 1517.6.4.
 A) SHOW CALCULATIONS FOR THE ROOF DRAIN
 AGE AS PER THE STANDAARD PLUMBING CODE.
 CHAPTER 11.
 B) PLANS ARE NOT CLEAR AS TO WHAT IS
 SCUPPRS FOR ROOF DRAINAGE AND WHICH ARE
 EMERGENCY OVERFLOW SCUPPERS, WHICH ARE
 BEING DELETED? SHOW CODE COMPLIANCE.
 FROM PREVIOUS PLAN REVIEW.
  
 2)- SHEET A-5 INDICATES THE USE OF PT
 WOOD ON THE EXTERIOR OF THE BUILDING.
 SBC F 102.2.1. / EXTERIOR WALLS OF BUILD
 INGS LOCATED IN THE FIRE DISTRICT SHALL
 COMPLY WITH THE REQUIREMENTS IN TABLE
 600." NO COMBUSTIBLES, NO TYPE VI CON-
 STRUCTION ALLOWED.
  
 3)- NEW GLAZING INCLUDING THE SKYLIGHTS
 PRODUCT APPROVAL FOR ALL GLAZED OPENINGS
 ARE REQUIRED(2 COPIES) SBCCI OR DADE
 COUNTY PRODUCT TESTING REPORTS ARE
 REQUIRED. LARGE MISSLE IMPACT RESISTANCE
 TESTING WILL BE REQUIRED.SBC 1606.4.1*/
 SBC 1707.4.1*.PREVIOUS REVIEW.
  
 4)- SHEET A-5 INDICATES A NEW GLASS
 DOOR, SIDELITE & TRANSOM, MISSING PRO-
 DUCT TESTING REPORT EITHER SBCCI OR DADE
 COUNTY ARE ACCEPTED.SBC 1606.4.1.*/
 SBC1707.4..1.*.
  
 5)- REVISION DATES ARE NOT REVISED ON
 THE LATEST DRAWINGS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-09-17 Cont ID  
Sent By hpiskura Date 2001-09-17 Time 08:13 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-09-17 00:00:00SHEET EX-1 RE: CAPPING OF SCUPPERS.
 ROOF DRAINAGE, INCLUDING EMERGENCY
 OVERFLOWMUST BE MAINTAINED IN
 ACCORDANCE WITH SBC 1517.6.4.
  
 THE NEW GLAZING INCLUDING THE SKYLIGHTS
 MUST COMPLY WITH THE CITY'S HURRICANE
 MISSILE IMPACT RESISTANCE REQUIREMENTS.
 PLEASE PROVIDE SPECIFIC DETAILS.
  
 PROVIDE A RECENT SURVEY SO THAT
 COMPLIANCE WITH SBC 3203 AND OTHER
 ISSUES MAY BE DETERMINED.
  
 SHEET A5.THIS BUILDING IS LOCATED IN
 THE DESIGNATED FIRE DISTRICT AND
 COMBUSTIBLE CONSTRUCTION IS NOT
 PERMITTED WITHIN OR ON THE OUTSIDE OF
 EXTERIOR WALLS.SEE SBC F 102.
  
 PROVIDE A CLEAR SCOPE OF WORK TO BE
 ACCOMPLISHED UNDER THIS PERMIT FOR THE
 $150,000 VALUATION DIFFERNTIATING THAT
 WHICH IS TO BE PERFORMED AT COST PLUS.
  
 SHEET A3.THE EXIT LIGHT SHOWN AT DOOR
 D03 IS ILL PLACED.SEE SBC 1001.1.3.
 IT WOULD SERVE BETTER ON THE KITCHEN
 SIDE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-04-29 Cont ID  
Sent By dpalmer Date 2002-04-29 Time 18:16 Rev Time 0.00
Received By dpalmer Date 2002-04-29 Time 18:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-11-07 Cont ID  
Sent By dpalmer Date 2001-11-07 Time 18:45 Rev Time 0.00
Received By dpalmer Date 2001-11-07 Time 18:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-28 Cont ID  
Sent By dpalmer Date 2001-08-28 Time 20:36 Rev Time 0.00
Received By dpalmer Date 2001-08-28 Time 20:36 Sent To  
Notes
2001-08-28 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATINGS WERE SHOWN
 FOR PANELS BUT NOT FOR MAIN.
  
 2) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC), PER 230-42 AND
 215-3
  
 3)NOTE: PLEASE NOTE THAT PLANS NEED TO
 SHOW TRACK LIGHTING LOAD CALCULATIONS
 PER 220-12B
  
 4)NOTE: PLEASE NOTE THAT LOAD SHOWN FOR
 EXISTING SERVICE IS AT 21KW AND LOAD
 SHOWN FOR NEW SERVICE PUTS LOAD OVER
 SERVICE ENTRANCE CONDUCTOR RATINGS. PER
 310-16
 PLEASE PROVIDE A ONE WEEK SIGNED AND
 SEALED READ OUT FOR EXISTING SERVICE OR
 A 12 MONTHS WORTH OF FPL STATEMENTS FOR
 VERIFICATION OF LOAD.
  
 5)NOTE: PLEASE ALSO PLACE NOTE ON PLANS
 E-3 FOR LIGHTING FIX SCHEDULE.
 "ALL FIXTURES AND COMPONENTS TO BE "UL"
 LISTED".
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-09-10 Cont ID  
Sent By lsmith Date 2001-09-10 Time 15:53 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-04-19 Cont ID  
Sent By mcarsill Date 2002-04-19 Time 09:50 Rev Time 0.00
Received By mcarsill Date 2002-05-02 Time 09:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-12-10 Cont ID  
Sent By mcarsill Date 2001-12-10 Time 13:24 Rev Time 0.00
Received By mcarsill Date 2001-12-10 Time 13:24 Sent To  
Notes
2001-12-10 00:00:001) THE DISPLAY CASE IS NOT TO INTERFERE
 WITH EXIT ACCESS TO THE DOUBLE DOORS
 THAT WILL BE USED FOR EXITING ONCE THEY
 HAVE BEEN RELOCATED. ON 12.10.01 SPOKE
 MR. A NARDI AND HE ADVISED THAT THE
 DISPLAY CASE WILL NOT INTERFERE WITH
 EXIT ACCESS TO THE DOORS AND THAT
 HANDICAPPED ACCESSIBILITY WILL BE
 PROVIDED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-11-14 Cont ID  
Sent By mcarsill Date 2001-11-14 Time 10:48 Rev Time 0.00
Received By mcarsill Date 2001-11-14 Time 10:48 Sent To  
Notes
2001-11-14 00:00:001) PREVIOUS COMMENT RESPONSES NOT
 ACCEPTABLE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-15 Cont ID  
Sent By mcarsill Date 2001-08-15 Time 10:54 Rev Time 0.00
Received By mcarsill Date 2001-08-15 Time 10:53 Sent To  
Notes
2001-08-15 00:00:001) PLEASE INDICATE OPERABLE WINDOWS USED
 FOR RESCUE OR VENTILATION PURPOSES. IF
 NO OPERABLE WINDOWS ARE PROVIDED, THEN
 THE BUILDING MAY BE CONSIDERED
 WINDOWLESS, AND A FIRE SPRINKLER SYSTEM
 WOULD BE REQUIRED.
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE INSTALLATION OF ANY HOOD, DUCT
 AND EXTINGUISHING SYSTEMS.
 3) PLEASE INDICATE OCCUPANT LOAD FOR
 THIS FACILITY. PLEASE INCLUDE STAFF
 TOTAL.
 4) EXIT DOORS DO1 AND DO2 ARE NOT
 SEPARATED FROM ONE ANOTHER BY HALF THE
 OVERALL DIAGONAL DIMENSION OF THE ROOM
 OR AREA SERVED. IT WAS ALSO NOTED THAT
 EXITING IS BEING BROUGHT THRU THE
 KITCHEN WHICH IS NOT PERMITTED BY FIRE
 CODE REGULATIONS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-04-22 Cont ID  
Sent By pkrauss Date 2002-04-22 Time 09:54 Rev Time 0.50
Received By pkrauss Date 2002-04-22 Time 09:54 Sent To  
Notes
2002-04-22 00:00:00 
 ADDITIONAL PERMIT REQUIRED FOR HOOD AND
 FIRE SUPRESSION.PLEASE PROVIDE PLANS
 AND MANUFACTURER SUBMITTAL DATA WITH
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-12-08 Cont ID  
Sent By pkrauss Date 2001-12-08 Time 07:12 Rev Time 0.40
Received By pkrauss Date 2001-12-08 Time 07:06 Sent To  
Notes
2001-12-08 00:00:00 
 PROVISO FROM PREVIOUS COMMENTS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-11-20 Cont ID  
Sent By pkrauss Date 2001-11-20 Time 14:55 Rev Time 0.50
Received By pkrauss Date 2001-11-20 Time 14:36 Sent To  
Notes
2001-11-20 00:00:00******************PROVISO***************
  
  
 EXHAUST DUCT CONVEYING NOXIOUS GASES,
 FLAMMABLE VAPORS, CORROSIVE VAPORS
 SHALL TERMINATE OUTSIDE THE BUILDING
 AND BE LOCATED 10 FT FROM ANY ADJACENT
 BUILDING, PARKING AREA, ADJACENT
 PROPERTY LINE, WINDOW, DOOR OR AIR
 INTAKE OPENING.
  
 PLEASE NOTE - GREASE DUCT SHALL BE
 INSPECTED PRIOR TO BEING ENCLOSED.
 PROVIDE DETAIL OF SHAFT ENCLOSURE AND
 TERMINATION OF GREASE DUCT WITH MECH
 HOOD PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-08-28 Cont ID  
Sent By pkrauss Date 2001-08-28 Time 16:44 Rev Time 0.50
Received By pkrauss Date 2001-08-28 Time 16:21 Sent To  
Notes
2001-08-28 00:00:00*******************PROVISO**************
  
  
 10' MINIMUM CLEARANCE BETWEEN EXHAUST
 TERMINATION AND FRESH AIR INTAKE.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION AND WALK-IN COOLERS.
 PLEASE SUMIT PLANS AND MANUFACTURER
 SUBMITTAL DATA WITH PERMIT APPLICATION.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 6 Status P Date 2002-06-04 Cont ID  
Sent By kstevens Date 2002-06-04 Time 11:58 Rev Time 0.00
Received By kstevens Date 2002-06-04 Time 11:58 Sent To  
Notes
2002-06-04 00:00:00BAKERY - DEPT OF AGRICULTURE NOW PER
 HOTEL AND BUSINESS DEPT.

Review Stop P PLUMBING
Rev No 5 Status P Date 2002-05-02 Cont ID  
Sent By kstevens Date 2002-05-02 Time 18:04 Rev Time 0.00
Received By kstevens Date 2002-05-02 Time 18:04 Sent To  
Notes
2002-05-02 00:00:00REVISION OK - PENDING OK FROM HOTEL
 AND RESTURANT DIVISION, DEPT. OF BUSIN-
 ESS REGULATION.

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-12-11 Cont ID  
Sent By lmartine Date 2001-12-11 Time 17:57 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2001-12-11 00:00:00PROVISO:SEPERATE PLANS & PERMIT FOR GAS.
 SEE BLOCK STAMP, FOR APPROVAL BY PAUL
 SHMITZ, DATED 12/11/01LM

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-12-04 Cont ID  
Sent By kstevens Date 2001-12-04 Time 13:08 Rev Time 1.25
Received By kstevens Date 2001-12-04 Time 13:08 Sent To  
Notes
2001-12-04 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) PER PREVIOUS PLAN REVIEW 11-13-01,
 NEW PLANS SUBMITTED SHALL HAVE PLAN RE-
 VIEW AND STAMP FROM DEPT OF BUSINESS
 HOTEL AND RESTURANTS ATTACHED TO THEM.
 2) PER PREVIOUS PLAN REVIEW 11-13-01,
 URNALS SHALL COMPLY WITH FACBC 4.18.
 4.18.3 REQUIRES A MINIMUM 30"X48" CLEAR
 FLOOR SPACE. SHT A-4 SHOWS 2'3-1/2",
 SHTS A-1, A-2, & A-3 HAVE NO MEASURMENTS
 3) SHT A-4, DOOR SWINGS FOR DO6, & DO9
 REQUIRE EITHER NEW SIGNED AND SEALED
 SHEETS OR BE INITILED AND DATED BY ARC-
 HITECT OF RECORD. PER PREVIOUS REVIEW
 11-13-01.
 4) PER PREVIOUS REVIEW, GAS PERMIT
 APPLICATION REQUIREMENT SHEET #9, SUBMIT
 MANUFACTURE SHEETS FOR GAS EQUIPMENT PER
 SGC-97 SECS 602 THRU 612.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-11-13 Cont ID  
Sent By kstevens Date 2001-11-13 Time 18:48 Rev Time 1.50
Received By kstevens Date 2001-11-13 Time 18:47 Sent To  
Notes
2001-11-13 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97 - SGC-97
  
 1) PLANS STAMPED BY DEPT OF BUSINESS AND
 PROFESSIONAL REGULATION ARE NOT THE SET
 BEING SUBMITTED FOR PLAN REVIEW. NO SEAL
 OR SIGNITURE ON THESE PLANS.
 2) PAGE A-4 DETAIL A FOR URNAL DOES NOT
 SHOW CLEAR FLOOR SPACE AS REQUESTED. NO
 MEASUREMENT GIVEN, 30"X48" REQUIRED.
 3) PAGE A-4, ROOMS DO6, DO7, DO8, & DO9
 DOORS SHALL NOT SWING INTO CLEAR FLOOR
 SPACE OF FIXTURES OR TURNING RADIUS. DO7
 AND DO8 WERE PENNED IN BUT ALL HAVE TO
 SWING OUT AND SHOULD NOT BE PENNED IN
 UNLESS CHANGES ARE SIGNED AND DATED.
 4) PAGES P-1, 3 COMPARTMENT SINK IN FOOD
 PREP AREA DOES NOT REQUIRE TRAPS, IT
 SHALL DRAIN TO FLOOR SINK.
 5) PAGE P-1, FUNNEL FLOOR DRAINS NOT
 APPROVED. ALL INDIRECT WASTE SHALL DRAIN
 TO FLOOR SINK.
 6) PAGES P-1, & P-2 TWO WAY CLEAN OUTS
 ON BLDG DRAIN WHERE IT TIES INTO BLDG
 SEWER SHALL HAVE 2-WAY CLEAN OUTS. SHOW
 C/O'S ON PLANS PLEASE. SPC SEC 710.2.1
 (6) & 710.2.2.
 7) GAS PERMIT APPLICATION SHEET #'S 6 &
 9 WHERE NOT ADDRESSED. PLEASE SUPPLY IN-
 FORMATION REQUESTED.
 8) PAGE P-2 GAS ISOMETERIC RISER DIAGRAM
 REQUIRES A UNION BETWEEN MANUAL VALVE &
 SOLENOID VALVE FOR HOOD SHUT OFF.
 9) CALCULATIONS FOR COMBUSTION AIR NOT
 ACCEPTABLE. DOOR TO HEATER ROOM CAN BE
 CLOSED AND LOCKED WHICH WOULD MAKE THE
 ROOM A CONFINED SPACE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-29 Cont ID  
Sent By kstevens Date 2001-08-29 Time 16:50 Rev Time 0.00
Received By kstevens Date 2001-08-29 Time 16:50 Sent To  
Notes
2001-08-29 00:00:00DENIED
  
 REFERENCE SPC-94/SGC-97/FACBC-97
  
 1) PLANS SHALL BE ROUTED TO DEPT. OF
 BUSINESS REGULATION FOR REVIEW AND
 APPROVAL. COUNTYWIDE AMENDMENTS TO SPC
 SEC. 101.4.7.
 2) PAGE A-4, DETAIL A/A-4, URNAL MUST
 COMPLY WITH FACBC-97 SECTION 4.18
 CLEAR FLOOR SPACE AND TYPE OF URNAL AND
 URNAL HEIGTH ECT.
 3) PAGE A-4, DETAIL G/A-4, W/C TO BE 1'-
 6" OFF WALL. PER FACBC-97 SECTION 4.16.
 4) PAGE A-4, ROOMS DO6-DO7-DO8-DO9,
 DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE OF ANY FIXTURE. FACBC-97
 SECTION 4.17.5.
 5) PAGE P-1, 3 COMPARTMENT SINKS FOR
 DISHWASHING SHALL HAVE A TRAP FOR EACH
 COMPARTMENT. SPC-94, SECTION 1001.8.1
 6) PAGES P-1 & P-2, SAFE WASTES NOT AL-
 LOWED. FLOOR SINKS ARE REQUIRED FOR ALL
 INDIRECT WASTE. SPC-94 SECTIONS 804.1 &
 807.
 7) PAGES P-1 & P-2, 3 COMPARTMENT SINK
 IN FOOD PREPARATION AREA TO DRAIN IN-
 DIRECTLY TO A FLOOR SINK. SPC-94 SECTION
 804.
 8) PAGE P-1, GREASE TRAP TO BE SIZED AND
 LOCATED BY THE CITY UTILITY DEPT. PLEASE
 CONTACT RODNEY COMPO, (561) 837-4074.
 SEE ATTACHED SHEET FOR WPB CITY UTILITY
 APPROVED GREASE TRAP DETAIL.
 9) PAGE P-1, HUB DRAINS NOT ALLOWED. ALL
 INDIRECT WASTE TO FLOOR SINK. SPC-94
 SECTION 804.5.
 10) PAGES P-1 & P-2, ICE MACHINE TO
 DRAIN TO FLOOR SINK NOT FLOOR DRAIN.
 SPC-94 SECTION 804.
 11) PAGE P-2, 2-WAY CLEAN-OUTS ARE REQ-
 UIRED WITH-IN 5' OF EXITING BLDG. SPC-94
 SECTIONS 710.2.1(6) & 710.2.2.
 12) SEPARATE PERMIT FOR GAS. SEE ATTACH-
 ED SHEET FOR GAS PERMIT APPLICATION RE-
 QUIREMENTS.
 13) PAGE P-2 GAS ISOMETRIC RISER DIAGRAM
 FOR GAS SOLENOID VALVE. SHOW DETAIL OF
 EMERGENCY SHUT-OFF VALVE. MANUAL VALVE
 SHALL BE UPSTREAM OF UNION FOR SERVICING
 SOLENOID VALVE.
 14) PAGES A-1, A-2, A-3, A-6, & P-1.
 SUBMIT COMBUSTION AIR CALCULATIONS FOR
 GAS WATER HEATER. SGC-97 SECTION 402.4.4
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-09-10 Cont ID  
Sent By lsmith Date 2001-09-10 Time 15:53 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***