Plan Review Details - Permit 01080548
Plan Review Stops For Permit 01080548
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-09-21 Cont ID  
Sent By hpiskura Date 2001-09-21 Time 08:28 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-09-05 Cont ID  
Sent By hpiskura Date 2001-09-05 Time 11:12 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-09-05 00:00:00SHEET A1 DOOR SCHEDULE, REMARKS, "RATED"
 SHOW A SPECIFIC LABEL REQUIREMENT IN
 ACCORDANCE WITH SBC 705.1.3SAME SHEET
 A2
  
 SHOW A LIFE SAFETY PLAN FOR THE 11TH
 FLOOR TO INCLUDE THE OTHER PORTION OF
 THE FLOOR.
  
 SHEET A2, THE TWO EXITS DO NOT MEET THE
 1/2 DIAGONAL DISTANCE SEPARATION
 REQUIREMENTS OF SBC 1004.1.4.
  
 SHEET A2.EGRESS IS NOT PERMITTED
 THROUGH STORAGE AREAS.SEE SBC
 1001.1.3.
  
  
 THE DECLARED $180K VALUATION APPEARS TO
 BE TOO LOW FOR THIS SCOPE OF WORK.
 PLEASE PROVIDE A COPY OF THE SIGNED
 CONTRACT AND DETAILED TAKEOFF TO VERIFY
 THE SUM.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-08-21 Cont ID  
Sent By dpalmer Date 2001-08-21 Time 19:32 Rev Time 0.00
Received By dpalmer Date 2001-08-21 Time 19:32 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-09-05 Cont ID  
Sent By hpiskura Date 2001-09-05 Time 11:27 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-09-21 Cont ID  
Sent By hpiskura Date 2001-09-21 Time 08:28 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-21 Cont ID  
Sent By mcarsill Date 2001-08-21 Time 08:37 Rev Time 0.00
Received By lsmith Date 2001-08-21 Time 08:37 Sent To  
Notes
2001-08-21 00:00:001) PLEASE INDICATE WHY EXIT SIGN
 MARKINGS FROM BOOKKEEPING 1124 LEADS
 PERSONS INTO STORAGE ROOM 1125.
 EXITING IS NOT PERMITTED THRU
 STORAGE ROOMS, KITCHENS,ETC.
 2) WHAT PRECAUTIONS WILL BE TAKEN TO
 ENSURE THAT THE DEMOLITION ACTIVITIES
 WILL NOT INTERFERE WITH ANY EXITING,
 ETC.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-08-21 Cont ID  
Sent By ndenmark Date 2001-08-21 Time 13:37 Rev Time 0.33
Received By ndenmark Date 2001-08-21 Time 13:37 Sent To  
Notes
2001-08-21 00:00:00PROVISO
 ALL COPPER CONDENSER WATER PIPING TO BE
 BRAZED PER 1997 SMC TABLE 1205
 FIELD VERIFICATION OF FIRE DAMPERS AT
 ALL RATED WALL PENETRATIONS BY DUCTS
 REQUIRED
 NO COMBUSTIBLE MATERIALS, INCLUING PVC
 ALLOWED IN RETURN AIR PLENUM AREA ABOVE
 CEILING.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-08-22 Cont ID  
Sent By kstevens Date 2001-08-22 Time 11:07 Rev Time 0.00
Received By kstevens Date 2001-08-22 Time 11:07 Sent To  
Notes
2001-08-22 00:00:00PASSED/PROVISO
  
 SINKS TO COMPLY WITH 1997 FACBC REQUIRE-
 MENTS.

Review Stop Z ZONING
Rev No 1 Status N Date 2001-09-05 Cont ID  
Sent By hpiskura Date 2001-09-05 Time 11:27 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***