| Plan Review Stops For Permit 01080384 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-10-03 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-10-03 |
Time |
08:10 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-03 00:00:00 | ITEMS #5 AND #6 ON THE JWITMER 9/10/01 | | | REVIEW HAVE NOT BEEN ADDRESSED. | | | | | | THE PLANS CALL OUT A 1994 EDITION OF | | | THEFLORIDA ACCESSIBILITY CODE.THE | | | OCTOBER1997 IS CURRENTLY IN EFFECT. | | | | | | WHAT IS THE PURPOSE OF THE "WATER | | | CURTAIN" CALLED OUT IN NOTE G ON SHEET | | | A-1.1?UNLESS IT IS A TESTED ASSEMBLY | | | OR APPLIED ALONG WITH THE OTHER | | | REQUIREMENTS FOUND IN SBC 414 IT IS | | | WITHOUT STANDING FOR CODE COMPLIANCE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-09-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-09-10 |
Time |
14:25 |
Rev Time |
3.50 |
| Received By |
jwitmer |
Date |
2001-09-10 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2001-09-10 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01080384 | | | 326 FERN ST / 2ND FLOOR | | | "PLAN REVIEW" | | | QUINCY JOHNSON ARCHETECTS | | | TEL: (561) 997-9997 | | | FAX: (561) 997-1610 | | | | | | SBC= STANDARD BUILDING CODE 1997 EDI. | | | 1)- CODE RESEARCH GOVERNING CODE : | | | ADOPTED 1997 SBC | | | | | | 2)- TRAVEL DISTANCE: NOT 750', SBC | | | TABLE 1004 SPRINKLERED 250'. | | | | | | 3)- SBC TABLE 704.2.4 SPRINKLERED/ SEE | | | RATING FOR EXIT ACCESS CORRIDOR. | | | | | | 4)- SBC SEC.1020.1(2) 3500' > REQUIRE | | | 2 EXITS,1/2 THE DIAGONAL DISTANCE BE- | | | TWEEN THE 2 EGRESS DOORS.SEE 1004.1.4. | | | | | | 5)- THE SPACE TO THE RIGHT OF THIS TEN- | | | ANT SPACE WILL ALSO REQUIRE (2) EGRESS | | | DOORS @ 1/2 THE DIAGONAL DISTANCE BE- | | | TWEEN DOORS. | | | | | | | | | 6)-SBC 1020.2 LOCKING : A SIGN " THIS | | | EXIT TO REMAIN UNLOCKED WHEN THIS BUILD- | | | ING IS OCCUPIED. | | | | | | SBC 803.3 THE MINIMUM INTERIOR FINISH | | | CLASSIFICATION AS PER ASTM E 84. FLAME- | | | SPREAD & SMOKE DEVELOPMENT. | | | | | | PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-08-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-28 |
Time |
21:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-28 |
Time |
20:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-10-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-02 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-02 |
Time |
12:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-08-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-14 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-14 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2001-08-14 00:00:00 | 1) WRONG BUILDING CODE REFERENCED ON | | | PLANS. SHOULD READ 1997 STANDARD | | | BUILDING CODE. | | | 2) CODE RESEARCH BOX INDICATES A | | | MAXIMUM TRAVEL DISTANCE OF 750 FEET. | | | THIS INFORMATION IS OBVIOUSLY AN ERROR. | | | 3) CLASS B, STYLE C FIRE ALARM CIRCUITS | | | NOTED IN FIRE ALARM NOTES IS NOT | | | CORRECT. ONLY CLASS A, STLE D ALLOWED. | | | 4) PLEASE INDICATE FIRE RATINGS FOR | | | DOORS 2,3,AND 6. | | | 5) PLEASE INDICATE EMERGENCY LIGHTS | | | IN TENANT HALLWAY. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-08-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-29 |
Time |
14:55 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-08-29 |
Time |
12:45 |
Sent To |
|
|
| Notes |
| 2001-08-29 00:00:00 | *******************PROVISO************** | | | | | | | | | MINIMUM OF 18" BETWEEN ROOF SURFACE AND | | | BOTTOM OF THE SUPPORT RAIL.AMENDED | | | 1997 SMC 304.2.5. | | | | | | NO COMBUSTIBLES ABOVE THE CEILING IN THE | | | RETURN AIR PLENUM.1997 SMC 609.1.1. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-10-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-11 |
Time |
18:49 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2001-10-11 |
Time |
18:49 |
Sent To |
|
|
| Notes |
| 2001-10-11 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) PLUMBING NOTES #13. AIR CHAMBERS DO | | | NOT WORK AND SHOULD NOT BE INSTALLED. | | | IF THEY ARE INSTALLED THEY SHALL COMPLY | | | WITH SPC-94 SEC 607.8.3 AND BE RECHARG- | | | ABLE AND ACCESSABLE. PAGE PO.1 | | | 2) PAGE PO.1 DOMESTIC WATER ISOMETRIC. | | | PLEASE COMPLY WITH MANUFACTURE INSTALL- | | | ATION INSTRUCTIONS AND WH-PDI 201, | | | PLACEMENT OF WATER HAMMER ARRESTORS NOT | | | AT TOP OF DROP AS SHOWN. SEE ATTACHED | | | SHEET. | | | 3) P2.1 CONDENSATE TO TERMINATE PER | | | MODEL COUNTYWIDE AMENDMENTS TO SPC-94 | | | SEC 804.3 NOT INTO SANITARY. PLEASE | | | SHOW PROPER DRAINAGE OF CONDENSATE. | | | 4) PAGE P2.1 BREAKROOM (#215) SINK TO | | | COMPLY WITH FACBC-97 SEC 4.24 - HEIGTH | | | SEC 4.24.2, KNEE CLEARANCE 4.24.3, | | | CLEAR FLOOR SPACE 4.24.5 ECT. SHOW DE- | | | TAILS. | | | 5) PAGE P2.1 DRINKING FOUNTAIN SHALL | | | COMPLY WITH FACBC-97 SEC 4.1.3(10(A), | | | PROVISIONS TO BE MADE FOR THOSE WHO HAVE | | | DIFFICULTY BENDING OR STOOPING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|