Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-10-03 Cont ID  
Sent By hpiskura Date 2001-10-03 Time 08:10 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-10-03 00:00:00ITEMS #5 AND #6 ON THE JWITMER 9/10/01
 REVIEW HAVE NOT BEEN ADDRESSED.
  
 THE PLANS CALL OUT A 1994 EDITION OF
 THEFLORIDA ACCESSIBILITY CODE.THE
 OCTOBER1997 IS CURRENTLY IN EFFECT.
  
 WHAT IS THE PURPOSE OF THE "WATER
 CURTAIN" CALLED OUT IN NOTE G ON SHEET
 A-1.1?UNLESS IT IS A TESTED ASSEMBLY
 OR APPLIED ALONG WITH THE OTHER
 REQUIREMENTS FOUND IN SBC 414 IT IS
 WITHOUT STANDING FOR CODE COMPLIANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-09-10 Cont ID  
Sent By jwitmer Date 2001-09-10 Time 14:25 Rev Time 3.50
Received By jwitmer Date 2001-09-10 Time 14:25 Sent To  
Notes
2001-09-10 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01080384
 326 FERN ST / 2ND FLOOR
 "PLAN REVIEW"
 QUINCY JOHNSON ARCHETECTS
 TEL: (561) 997-9997
 FAX: (561) 997-1610
  
 SBC= STANDARD BUILDING CODE 1997 EDI.
 1)- CODE RESEARCH GOVERNING CODE :
 ADOPTED 1997 SBC
  
 2)- TRAVEL DISTANCE: NOT 750', SBC
 TABLE 1004 SPRINKLERED 250'.
  
 3)- SBC TABLE 704.2.4 SPRINKLERED/ SEE
 RATING FOR EXIT ACCESS CORRIDOR.
  
 4)- SBC SEC.1020.1(2) 3500' > REQUIRE
 2 EXITS,1/2 THE DIAGONAL DISTANCE BE-
 TWEEN THE 2 EGRESS DOORS.SEE 1004.1.4.
  
 5)- THE SPACE TO THE RIGHT OF THIS TEN-
 ANT SPACE WILL ALSO REQUIRE (2) EGRESS
 DOORS @ 1/2 THE DIAGONAL DISTANCE BE-
 TWEEN DOORS.
  
  
 6)-SBC 1020.2 LOCKING : A SIGN " THIS
 EXIT TO REMAIN UNLOCKED WHEN THIS BUILD-
 ING IS OCCUPIED.
  
 SBC 803.3 THE MINIMUM INTERIOR FINISH
 CLASSIFICATION AS PER ASTM E 84. FLAME-
 SPREAD & SMOKE DEVELOPMENT.
  
 PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-08-28 Cont ID  
Sent By dpalmer Date 2001-08-28 Time 21:02 Rev Time 0.00
Received By dpalmer Date 2001-08-28 Time 20:51 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-10-02 Cont ID  
Sent By mcarsill Date 2001-10-02 Time 12:06 Rev Time 0.00
Received By mcarsill Date 2001-10-02 Time 12:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-14 Cont ID  
Sent By mcarsill Date 2001-08-14 Time 15:52 Rev Time 0.00
Received By mcarsill Date 2001-08-14 Time 15:52 Sent To  
Notes
2001-08-14 00:00:001) WRONG BUILDING CODE REFERENCED ON
 PLANS. SHOULD READ 1997 STANDARD
 BUILDING CODE.
 2) CODE RESEARCH BOX INDICATES A
 MAXIMUM TRAVEL DISTANCE OF 750 FEET.
 THIS INFORMATION IS OBVIOUSLY AN ERROR.
 3) CLASS B, STYLE C FIRE ALARM CIRCUITS
 NOTED IN FIRE ALARM NOTES IS NOT
 CORRECT. ONLY CLASS A, STLE D ALLOWED.
 4) PLEASE INDICATE FIRE RATINGS FOR
 DOORS 2,3,AND 6.
 5) PLEASE INDICATE EMERGENCY LIGHTS
 IN TENANT HALLWAY.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-08-29 Cont ID  
Sent By pkrauss Date 2001-08-29 Time 14:55 Rev Time 0.45
Received By pkrauss Date 2001-08-29 Time 12:45 Sent To  
Notes
2001-08-29 00:00:00*******************PROVISO**************
  
  
 MINIMUM OF 18" BETWEEN ROOF SURFACE AND
 BOTTOM OF THE SUPPORT RAIL.AMENDED
 1997 SMC 304.2.5.
  
 NO COMBUSTIBLES ABOVE THE CEILING IN THE
 RETURN AIR PLENUM.1997 SMC 609.1.1.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT 8388.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-11 Cont ID  
Sent By kstevens Date 2001-10-11 Time 18:49 Rev Time 1.25
Received By kstevens Date 2001-10-11 Time 18:49 Sent To  
Notes
2001-10-11 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PLUMBING NOTES #13. AIR CHAMBERS DO
 NOT WORK AND SHOULD NOT BE INSTALLED.
 IF THEY ARE INSTALLED THEY SHALL COMPLY
 WITH SPC-94 SEC 607.8.3 AND BE RECHARG-
 ABLE AND ACCESSABLE. PAGE PO.1
 2) PAGE PO.1 DOMESTIC WATER ISOMETRIC.
 PLEASE COMPLY WITH MANUFACTURE INSTALL-
 ATION INSTRUCTIONS AND WH-PDI 201,
 PLACEMENT OF WATER HAMMER ARRESTORS NOT
 AT TOP OF DROP AS SHOWN. SEE ATTACHED
 SHEET.
 3) P2.1 CONDENSATE TO TERMINATE PER
 MODEL COUNTYWIDE AMENDMENTS TO SPC-94
 SEC 804.3 NOT INTO SANITARY. PLEASE
 SHOW PROPER DRAINAGE OF CONDENSATE.
 4) PAGE P2.1 BREAKROOM (#215) SINK TO
 COMPLY WITH FACBC-97 SEC 4.24 - HEIGTH
 SEC 4.24.2, KNEE CLEARANCE 4.24.3,
 CLEAR FLOOR SPACE 4.24.5 ECT. SHOW DE-
 TAILS.
 5) PAGE P2.1 DRINKING FOUNTAIN SHALL
 COMPLY WITH FACBC-97 SEC 4.1.3(10(A),
 PROVISIONS TO BE MADE FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***