| Plan Review Stops For Permit 01080317 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2002-03-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-10-28 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-27 00:00:00 | TRUSS REVIEW CORRECTIONS NOTED |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2002-03-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-03-13 |
Time |
10:57 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-13 00:00:00 | BUILDING PLAN REVIEW | | | 213 S CONGRESS | | | 01080317 | | | | | | 1)- THE ORIGINAL PLAN INDICATES ON PAGE | | | A-1 THE PAVILION SHALL BE A FUTURE STRUC | | | TURE. THERE IS NO DETAILS TIE THIS STRUC | | | TURE TO THE PERMITTED WORK. | | | | | | 2) THE BUILDING OFFICIAL DETERMINED THAT | | | THIS PAVILION SHALL REQUIRE A SEPERATE | | | PERMIT TO BE REVIEWED UNDER THE 2001 | | | FLORIDA BUILDING CODE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2002-03-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-13 |
Time |
10:21 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-12 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01080317 | | | 213 S CONGRESS | | | | | | 1997 SBC= STANDARD BUILDING CODE | | | | | | 1) TRUSS SHOP DRAWINGS TO BE REVIEWED | | | BY THE DESIGNER OF RECORD AND APPROVED | | | BEFORE BUILDING DEPARTMENT REVIEW | | | | | | 2) SHEET S-4 SECTION "A" INDICATES A 3 | | | POINT BEARING TRUSS, THE TRUSS DRAWINGS | | | INDICATE A 2 POINT BEARING, THE LOADS | | | ARE GREATER THAN ALLOWED,ONLY THE UPLIFT | | | OF 160% CAN BE USED NOT THE AVERAGE | | | ULTIMATE! SEE H16 FOR OVER THE TOP USE. | | | SEE MGT SERIES FOR LARGER UPLIFTS. | | | | | | 3) SHEETS4 INDICATES A STRAP "ETA12" | | | NOT TO BE FOUND IN THE 2002 SIMPSON CATA | | | LOG? | | | | | | 4) SHEET S4 ALSO INDICATES A DETAIL "C" | | | WITH THE USE OF A "H-10" , HOW WILL THE | | | ANCHOR BE TAPCONED WITH A 4"X4" ANGLE | | | IN FRONT OF IT? |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-10-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-10-22 |
Time |
15:13 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2001-10-22 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2001-10-22 00:00:00 | PROVISO: STORM SHUTTERS TO BE UNDER SEPE | | | RATE PERMIT WITH ASSOCIATED FEES, PER | | | CONVERESATION W/C. BRANCH 10/22/01 JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-10-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-10-19 |
Time |
15:30 |
Rev Time |
3.00 |
| Received By |
jwitmer |
Date |
2001-10-19 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2001-10-19 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01080317 | | | 213 S CONGRESS AV | | | | | | 1)- SBC 1606.4.1/ 1707.4.1 AMENDMENTS: | | | ALL GLAZED OPENINGS SHALL SHOW EVIDENCE | | | OF COMPLIANCE WITH THE STANDARD FOR | | | DETERMINING IMPACT RESISTANCE FROM WIND- | | | BORN DEBRIS, SSTD 12-97. EITHER THROUGH | | | GLAZING PASSING THE LARGE MISSLE | | | TESTING OR STORM SHUTTERS THAT HAVE PASS | | | ED THE SBCCI OR DADE COUNTY PRODUCT TEST | | | ING FOR IMPACT RESISTANCE GLAZING. | | | THE STORM SHUTTERS CAN BE SUBMITT- | | | ED AS A SEPERATE PERMIT WITH FEES, THE | | | CONTRACTOR WILL NEED TO DETERMINE IF THE | | | SHUTTERS WILL BE PART OF THE BUILDING | | | PERMIT. | | | JIM WITMER (561) 659-8096X8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-08-28 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-08-28 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2001-08-28 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2001-08-28 00:00:00 | BEFORE A PERMIT TO CONSTRUCT CAN BE | | | ISSUED IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, THE PERMIT PLANS STAMPED | | | AND A COPY OF THE RECEIPT ATTACHED TO | | | THE PERMIT APPLICATION.CALL 233-5025 | | | FOR MORE INFORMATION. | | | | | | SHOW THE DISTANCE TO THE EXISTING | | | STORAGE BUILDING AND ANY WALL OPENINGS | | | SO THAT COMPLIANCE WITH SBC TABLE 600 | | | MAY BE DETERMINED. | | | | | | INCLUDE A SKETCH OF THE BUILDING SHOWING | | | THE WIND PRESSURE ZONES. | | | | | | PROVIDE THE TEST REPORTS AND OR NOTICE | | | OF ACCEPTANCE REPORTS FOR THE DOORS, | | | WINDOWS AND ROOF COVERING AT TIME OF | | | PERMIT APPLICATION. | | | | | | A RESIDENT INSPECTOR WILL BE REQUIRED | | | FOR THIS PROJECT, CONTACT DON NEELY FOR | | | MORE INFORMATION.659-8096 X 8333. | | | | | | THE FIRE SPRINKLER CALCULATIONS AND THE | | | ENERGY CODE ARE REQUIRED TO BE SIGNED | | | AND SEALED BY THE REGISTERED DESIGN | | | PROFESSIONAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2002-04-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-04-24 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-04-24 |
Time |
07:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-03-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-13 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-13 |
Time |
09:49 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-10-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-10 |
Time |
21:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-10 |
Time |
21:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-08-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-21 |
Time |
21:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-21 |
Time |
20:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2001-11-09 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-11-09 |
Time |
11:15 |
Rev Time |
2.00 |
| Received By |
mamini |
Date |
2001-11-09 |
Time |
11:15 |
Sent To |
|
|
| Notes |
| 2001-11-09 00:00:00 | PASSED : | | | 1. RESPONSES TO THE PREVIOUS REVIEW | | | COMMENTS DATED 10-29-01 SATISFACTORY, | | | REQUESTED INFORMATIONS PROVIDED. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2001-10-29 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-10-29 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
mamini |
Date |
2001-10-29 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2001-10-29 00:00:00 | FAILED: | | | 1. INSUFFICENT INFORMATIONS FOR CIVIL | | | ENGINEERING REVIEW, PLEASE SUBMIT CIVIL | | | PLANS FOR OUR REVIEW AND APPROVAL. | | | 2. CIVIL PLANS SHUOLD INCLUDE STORM | | | WATER CALCULATIONS, PERVIOUS & | | | IMPERVIOUS CALCULATIONS FOR ENTIRE SITE | | | AND POLLUTION PREVENTION PLAN. | | | 3. WE RECOMMEND A SEPARATE PERMIT | | | APPLICATIONS FOR UNDERGROUND UTILITIES/ | | | PAVEMENT AND SITE WORKS. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-10-03 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-03 |
Time |
12:35 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-03 |
Time |
12:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-08-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-08 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-08 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2001-08-08 00:00:00 | 1) PLEASE PROVIDE OCCUPANT LOAD | | | CALCULATIONS FOR THE BUILDING. PLEASE | | | PROVIDE CLIENT TO STAFF RATIO'S FOR | | | THE BUILDING. ALSO PLEASE INDICATE | | | HOURS OF OPERATION. | | | 2) BUILDING ADDRESS TO COMPLY WITH | | | CITY CODE 3343-00. | | | 3) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | 4) PLEASE PROVIDE SEPARATE PLANS AND | | | PERMITS FOR FIRE ALARM SYSTEM. | | | 5) RECEPTACLE COVERS REQUIRED FOR | | | ALL ELECTRICAL OUTLETS. | | | 6) CLOSET DOOR LOCKS SHALL BE OPENABLE | | | FROM THE INSIDE. | | | 7) BATHROOM DOOR LOCKS ARE TO BE | | | OPENABLE FROM THE OUTSIDE. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-12-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-03 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-12-03 |
Time |
13:06 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2002-12-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-12-12 |
Time |
11:41 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2002-12-12 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2002-12-12 00:00:00 | MECH PERMIT 01121060 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2002-10-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-03 |
Time |
13:07 |
Rev Time |
2.00 |
| Received By |
pkrauss |
Date |
2002-10-23 |
Time |
12:01 |
Sent To |
P |
|
| Notes |
| 2002-10-23 00:00:00 | DENIED: | | | | | | 1.PLEASE REFERENCE GAS PERMIT NUMBER. | | | SEPARATE PERMIT REQUIRED FOR GAS, | | | THIS WAS SUBMITTED UNDER THE | | | SUBMITTED UNDER THE "PLUMBING" | | | PERMIT. | | | | | | 2.PROVIDE MANUFACTURER SUBMITTAL DATA | | | & SIZING CHART FOR THE TRACPIPE. | | | | | | 3.IDENTIFY TYPE OF PIPE BEING | | | INSTALLED BETWEEN THE WATER HEATER | | | AND DRYER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-10-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-13 |
Time |
08:26 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-10-13 |
Time |
08:07 |
Sent To |
|
|
| Notes |
| 2001-10-13 00:00:00 | *******************PROVISO************** | | | | | | | | | CONDENSER UNIT STAND SHALL BE A MINIMUM | | | OF 18" BETWEEN THE ROOF SURFACE AND THE | | | BOTTOM OF THE SUPPORT RAIL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-08-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-09 |
Time |
10:03 |
Rev Time |
3.00 |
| Received By |
pkrauss |
Date |
2001-08-09 |
Time |
08:33 |
Sent To |
|
|
| Notes |
| 2001-08-09 00:00:00 | ********************DENIED************** | | | | | | | | | 1.AHU-1 FOR THE BOARD ROOM DOES NOT | | | INDICATE A DUCT SMOKE DETECTOR. | | | | | | 2.PLAN M-5, EF #2 IS LESS THAN 10' | | | FROM RTU-5 AIR INTAKE. 1997 SMC | | | 506.1 STATES TERMINATION OF EXHAUST | | | OUTLETS SHALL BE A MINIMUM OF 10' | | | FROM FRESH AIR INTAKES ON 40" ABOVE | | | THE ROOF SURFACE. | | | | | | 3.PLAN M-6DETAIL OF CONDENSER UNIT | | | STAND, DOES NOT SPECIFY HEIGHT OF | | | STAND.AMENDED 1997 SMC 304.2.5 | | | REQUIRES A MINIMUM OF 18" FROM THE | | | ROOF SURFACE TO THE BOTTOM OF THE | | | SUPPORT RAIL. | | | | | | 4.PLEASE INDICATE CONDENSATE LINE | | | LINE SIZE, ROUTING AND TERMINATION | | | ON PLANS FOR REVIEW. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2002-10-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-10-29 |
Time |
11:45 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-10-29 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2002-10-29 00:00:00 | DENIED | | | | | | 1) FOURTH NOTICE - GAS PERMIT REQUIRED | | | PLEASE SUBMIT PLANS WHEN APPLYING FOR | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER STANDARD | | | GAS CODE. | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | 3. TYPE OF GAS, (LP OR NATURAL) | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE STANDARD GAS CODE SECS. 305.2 THRU | | | 305.4 AND TABLES 305.4(A) THRU 305.4(E). | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | THE STANDARD GAS CODE SEC. 305.4(I). | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER THE STANDARD GAS | | | CODE SECS. 402.4 THRU 402.4.4.7. | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER STANDARD GAS CODE SEC. 305.2. IF | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER THE STANDARD GAS CODE SECS | | | 602 THRU 612. | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | STANDARD GAS CODE SEC. 402. | | | 10. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | 11. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND | | | APPURTENANCES PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2002-06-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-10-23 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-06-20 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2002-06-20 00:00:00 | SUBMITTAL NOT ACCEPTABLE. NO GAS PERMIT | | | APPLIED FOR. GAS PERMIT REQUIRED, SEE | | | ATTACHED SHEET FOR GAS PERMIT REQUIRE- | | | MENTS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2002-05-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-05-06 |
Time |
19:02 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-05-06 |
Time |
19:02 |
Sent To |
|
|
| Notes |
| 2002-05-06 00:00:00 | REVISION OK - ADDED LAVS, HAND SINK, C/O | | | 3 COMP KIT SINKECT |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-11-14 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-11-14 |
Time |
10:27 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-11-14 00:00:00 | PROVISO SEPERATE PLANS & PERMIT FOR GAS | | 2001-11-10 00:00:00 | PREVIOUS PLAN REVIEW DATED 10-27-01 NOT | | | ADDRESSED. PAUL S.NOT APPROVED.` |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-10-27 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-10-27 |
Time |
13:58 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-27 00:00:00 | PLUMBING PLAN REVIEW, DENIED. | | | PLEASE ADDRESS PREVIOUS NOTES 08-22-01 | | | (3) SHT P-1, REFERENCE TO AIR CHAMBERS, | | | PDI-WH 201,STATES AIR CHAMBERS ARE A | | | TEMPOARY FIX.USE WATER HAMMER ARRESTOR | | | PLACEMENT PER MFG INSTRUCTIONS, NOT AT | | | HIGH POINT OF SYSTEM, SPECIFY TYPE. | | | (5) SHT P-3 RM C-35 GWH, SAFE WASTE NOT | | | ALLOWED, SEC 1001.8 PLBG FIXTURES TO BE | | | SEPERATELY TRAPED. | | | (NEW COMMENT) SHT P-3,6" BUILDING DRAIN. | | | SEC 914,BUILDING DRAIN SHALL NOT PASS | | | THRU A BATTERY VENTED BRANCH. | | | ALSO TWO WAY CLEANOUT LOCATED 3' OUTSIDE | | | BUILDING, SEC 710.2 | | | PLEASE SUBMIT CIVIL PLANS, SHOWING ALL | | | SITE UTILITIES. | | | SEPERATE PLANS FOR GAS AND IRRIGATION | | | SIGNED AND SEALED AT TIME OF PERMIT. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-08-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-08-22 |
Time |
19:33 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2001-08-22 |
Time |
19:33 |
Sent To |
|
|
| Notes |
| 2001-08-22 00:00:00 | DENIED | | | REFERENCE: SPC-94/FACBC-97 | | | | | | 1) PROVIDE AVERAGE DAILY ATTENDENCE FIG- | | | URES FOR CLASSROOMS TO COMPUTE MINIMUM | | | FACILITIES PER TABLE 407- SPC-94 | | | | | | 2) PAGE A12 WATER CLOSETS TO COMPLY WITH | | | SECT. 4.16 - LAVS. TO COMPLY WITH 4.19 - | | | URNALS TO COMPLY WITH 4.18 - SINKS TO | | | COMPLY WITH 4.24 - FACBC-97. | | | | | | 3) PAGE P-1 GENERAL PLUMBING NOTES #12. | | | AIR CHAMBERS SHALL COMPLY WITH SPC-94, | | | 607.8.2 & 607.8.3 ACCESSABLE/RECHARGE- | | | ABLE (PDI WH 201).-WATER HAMMER ARR- | | | ESTORS SHALL BE INSTALLED PER MANUFACT- | | | URES INSTALLATION INSTRUCTION. | | | | | | 4) PAGE P-2 SANITARY - DISHWASHER TO | | | DRAIN INTO KITCHEN SINK TAIL PIECE. | | | | | | 5) PAGE P-3 ROOM C35 (LAUNDRY/JANITOR), | | | HUB DRAIN NOT ALLOWED. RELIEF LINE TO | | | RUN FULL SIZED OUTSIDE TO AN OBSERVABLE | | | POINT OR TO A FLOOR SINK WITH TRAP PRIM- | | | ER. (PAGE P-10 SHOWS SAME DETAIL) | | | | | | 6) PAGES P-3 & P-5, 6" SANITARY TO RUN | | | TO 6 X 4 WYE AFTER 1ST BATHROOM. (C18) | | | | | | 7) PAGE P-10 WATER HEATER DETAIL. DI- | | | ELECTRIC UNIONS NOT ALLOWED. | | | | | | 8) SEPARATE GAS PERMIT REQUIRED. SEE | | | ATTACHED SHEET FOR GAS PERMIT APPLICAT- | | | ION REQUIREMENTS. INFORMATION TO BE FILL | | | ED OUT WHEN APPLYING FOR GAS PERMIT. | | | | | | 9) SEPARATE IRRIGATION PERMIT REQUIRED. | | | PLUMBING CONTRACTOR TO PROVIDE VALVE AND | | | ADAPTOR FOR IRRIGATION CONTRACTOR TO TIE | | | INTO. | | | | | | 10) BACKFLOW REQUIRED FOR WATER SERVICE | | | INTO NEW BUILDING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-11-01 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-11-01 |
Time |
10:34 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|