Plan Review Details - Permit 01080317
Plan Review Stops For Permit 01080317
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2002-03-27 Cont ID  
Sent By pkrauss Date 2002-10-28 Time 14:18 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-03-27 00:00:00TRUSS REVIEW CORRECTIONS NOTED

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2002-03-13 Cont ID  
Sent By jwitmer Date 2002-03-13 Time 10:57 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-03-13 00:00:00BUILDING PLAN REVIEW
 213 S CONGRESS
 01080317
  
 1)- THE ORIGINAL PLAN INDICATES ON PAGE
 A-1 THE PAVILION SHALL BE A FUTURE STRUC
 TURE. THERE IS NO DETAILS TIE THIS STRUC
 TURE TO THE PERMITTED WORK.
  
 2) THE BUILDING OFFICIAL DETERMINED THAT
 THIS PAVILION SHALL REQUIRE A SEPERATE
 PERMIT TO BE REVIEWED UNDER THE 2001
 FLORIDA BUILDING CODE.
  
 BUILDING PLAN REVIEW
 JIM WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2002-03-12 Cont ID  
Sent By dpalmer Date 2002-03-13 Time 10:21 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-03-12 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01080317
 213 S CONGRESS
  
 1997 SBC= STANDARD BUILDING CODE
  
 1) TRUSS SHOP DRAWINGS TO BE REVIEWED
 BY THE DESIGNER OF RECORD AND APPROVED
 BEFORE BUILDING DEPARTMENT REVIEW
  
 2) SHEET S-4 SECTION "A" INDICATES A 3
 POINT BEARING TRUSS, THE TRUSS DRAWINGS
 INDICATE A 2 POINT BEARING, THE LOADS
 ARE GREATER THAN ALLOWED,ONLY THE UPLIFT
 OF 160% CAN BE USED NOT THE AVERAGE
 ULTIMATE! SEE H16 FOR OVER THE TOP USE.
 SEE MGT SERIES FOR LARGER UPLIFTS.
  
 3) SHEETS4 INDICATES A STRAP "ETA12"
 NOT TO BE FOUND IN THE 2002 SIMPSON CATA
 LOG?
  
 4) SHEET S4 ALSO INDICATES A DETAIL "C"
 WITH THE USE OF A "H-10" , HOW WILL THE
 ANCHOR BE TAPCONED WITH A 4"X4" ANGLE
 IN FRONT OF IT?

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-10-22 Cont ID  
Sent By jwitmer Date 2001-10-22 Time 15:13 Rev Time 1.00
Received By jwitmer Date 2001-10-22 Time 15:13 Sent To  
Notes
2001-10-22 00:00:00PROVISO: STORM SHUTTERS TO BE UNDER SEPE
 RATE PERMIT WITH ASSOCIATED FEES, PER
 CONVERESATION W/C. BRANCH 10/22/01 JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-10-19 Cont ID  
Sent By jwitmer Date 2001-10-19 Time 15:30 Rev Time 3.00
Received By jwitmer Date 2001-10-19 Time 15:30 Sent To  
Notes
2001-10-19 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01080317
 213 S CONGRESS AV
  
 1)- SBC 1606.4.1/ 1707.4.1 AMENDMENTS:
 ALL GLAZED OPENINGS SHALL SHOW EVIDENCE
 OF COMPLIANCE WITH THE STANDARD FOR
 DETERMINING IMPACT RESISTANCE FROM WIND-
 BORN DEBRIS, SSTD 12-97. EITHER THROUGH
 GLAZING PASSING THE LARGE MISSLE
 TESTING OR STORM SHUTTERS THAT HAVE PASS
 ED THE SBCCI OR DADE COUNTY PRODUCT TEST
 ING FOR IMPACT RESISTANCE GLAZING.
 THE STORM SHUTTERS CAN BE SUBMITT-
 ED AS A SEPERATE PERMIT WITH FEES, THE
 CONTRACTOR WILL NEED TO DETERMINE IF THE
 SHUTTERS WILL BE PART OF THE BUILDING
 PERMIT.
 JIM WITMER (561) 659-8096X8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-08-28 Cont ID  
Sent By hpiskura Date 2001-08-28 Time 15:27 Rev Time 0.00
Received By hpiskura Date 2001-08-28 Time 11:22 Sent To  
Notes
2001-08-28 00:00:00BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PERMIT PLANS STAMPED
 AND A COPY OF THE RECEIPT ATTACHED TO
 THE PERMIT APPLICATION.CALL 233-5025
 FOR MORE INFORMATION.
  
 SHOW THE DISTANCE TO THE EXISTING
 STORAGE BUILDING AND ANY WALL OPENINGS
 SO THAT COMPLIANCE WITH SBC TABLE 600
 MAY BE DETERMINED.
  
 INCLUDE A SKETCH OF THE BUILDING SHOWING
 THE WIND PRESSURE ZONES.
  
 PROVIDE THE TEST REPORTS AND OR NOTICE
 OF ACCEPTANCE REPORTS FOR THE DOORS,
 WINDOWS AND ROOF COVERING AT TIME OF
 PERMIT APPLICATION.
  
 A RESIDENT INSPECTOR WILL BE REQUIRED
 FOR THIS PROJECT, CONTACT DON NEELY FOR
 MORE INFORMATION.659-8096 X 8333.
  
 THE FIRE SPRINKLER CALCULATIONS AND THE
 ENERGY CODE ARE REQUIRED TO BE SIGNED
 AND SEALED BY THE REGISTERED DESIGN
 PROFESSIONAL.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-04-24 Cont ID  
Sent By btrobaug Date 2002-04-24 Time 12:54 Rev Time 0.00
Received By btrobaug Date 2002-04-24 Time 07:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-03-13 Cont ID  
Sent By dpalmer Date 2002-03-13 Time 10:21 Rev Time 0.00
Received By dpalmer Date 2002-03-13 Time 09:49 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-10 Cont ID  
Sent By dpalmer Date 2001-10-10 Time 21:52 Rev Time 0.00
Received By dpalmer Date 2001-10-10 Time 21:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-08-21 Cont ID  
Sent By dpalmer Date 2001-08-21 Time 21:07 Rev Time 0.00
Received By dpalmer Date 2001-08-21 Time 20:37 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-11-09 Cont ID  
Sent By mamini Date 2001-11-09 Time 11:15 Rev Time 2.00
Received By mamini Date 2001-11-09 Time 11:15 Sent To  
Notes
2001-11-09 00:00:00PASSED :
 1. RESPONSES TO THE PREVIOUS REVIEW
 COMMENTS DATED 10-29-01 SATISFACTORY,
 REQUESTED INFORMATIONS PROVIDED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-10-29 Cont ID  
Sent By mamini Date 2001-10-29 Time 15:41 Rev Time 0.00
Received By mamini Date 2001-10-29 Time 15:41 Sent To  
Notes
2001-10-29 00:00:00FAILED:
 1. INSUFFICENT INFORMATIONS FOR CIVIL
 ENGINEERING REVIEW, PLEASE SUBMIT CIVIL
 PLANS FOR OUR REVIEW AND APPROVAL.
 2. CIVIL PLANS SHUOLD INCLUDE STORM
 WATER CALCULATIONS, PERVIOUS &
 IMPERVIOUS CALCULATIONS FOR ENTIRE SITE
 AND POLLUTION PREVENTION PLAN.
 3. WE RECOMMEND A SEPARATE PERMIT
 APPLICATIONS FOR UNDERGROUND UTILITIES/
 PAVEMENT AND SITE WORKS.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-10-03 Cont ID  
Sent By mcarsill Date 2001-10-03 Time 12:35 Rev Time 0.00
Received By mcarsill Date 2001-10-03 Time 12:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-08 Cont ID  
Sent By mcarsill Date 2001-08-08 Time 13:13 Rev Time 0.00
Received By mcarsill Date 2001-08-08 Time 13:13 Sent To  
Notes
2001-08-08 00:00:001) PLEASE PROVIDE OCCUPANT LOAD
 CALCULATIONS FOR THE BUILDING. PLEASE
 PROVIDE CLIENT TO STAFF RATIO'S FOR
 THE BUILDING. ALSO PLEASE INDICATE
 HOURS OF OPERATION.
 2) BUILDING ADDRESS TO COMPLY WITH
 CITY CODE 3343-00.
 3) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
 4) PLEASE PROVIDE SEPARATE PLANS AND
 PERMITS FOR FIRE ALARM SYSTEM.
 5) RECEPTACLE COVERS REQUIRED FOR
 ALL ELECTRICAL OUTLETS.
 6) CLOSET DOOR LOCKS SHALL BE OPENABLE
 FROM THE INSIDE.
 7) BATHROOM DOOR LOCKS ARE TO BE
 OPENABLE FROM THE OUTSIDE.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-03 Cont ID  
Sent By btrobaug Date 2002-12-03 Time 13:06 Rev Time 0.00
Received By btrobaug Date 2002-12-03 Time 13:06 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-12-12 Cont ID  
Sent By pkrauss Date 2002-12-12 Time 11:41 Rev Time 0.50
Received By pkrauss Date 2002-12-12 Time 11:01 Sent To  
Notes
2002-12-12 00:00:00MECH PERMIT 01121060

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2002-10-23 Cont ID  
Sent By btrobaug Date 2002-12-03 Time 13:07 Rev Time 2.00
Received By pkrauss Date 2002-10-23 Time 12:01 Sent To P
Notes
2002-10-23 00:00:00DENIED:
  
 1.PLEASE REFERENCE GAS PERMIT NUMBER.
 SEPARATE PERMIT REQUIRED FOR GAS,
 THIS WAS SUBMITTED UNDER THE
 SUBMITTED UNDER THE "PLUMBING"
 PERMIT.
  
 2.PROVIDE MANUFACTURER SUBMITTAL DATA
 & SIZING CHART FOR THE TRACPIPE.
  
 3.IDENTIFY TYPE OF PIPE BEING
 INSTALLED BETWEEN THE WATER HEATER
 AND DRYER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-10-13 Cont ID  
Sent By pkrauss Date 2001-10-13 Time 08:26 Rev Time 0.45
Received By pkrauss Date 2001-10-13 Time 08:07 Sent To  
Notes
2001-10-13 00:00:00*******************PROVISO**************
  
  
 CONDENSER UNIT STAND SHALL BE A MINIMUM
 OF 18" BETWEEN THE ROOF SURFACE AND THE
 BOTTOM OF THE SUPPORT RAIL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-09 Cont ID  
Sent By pkrauss Date 2001-08-09 Time 10:03 Rev Time 3.00
Received By pkrauss Date 2001-08-09 Time 08:33 Sent To  
Notes
2001-08-09 00:00:00********************DENIED**************
  
  
 1.AHU-1 FOR THE BOARD ROOM DOES NOT
 INDICATE A DUCT SMOKE DETECTOR.
  
 2.PLAN M-5, EF #2 IS LESS THAN 10'
 FROM RTU-5 AIR INTAKE. 1997 SMC
 506.1 STATES TERMINATION OF EXHAUST
 OUTLETS SHALL BE A MINIMUM OF 10'
 FROM FRESH AIR INTAKES ON 40" ABOVE
 THE ROOF SURFACE.
  
 3.PLAN M-6DETAIL OF CONDENSER UNIT
 STAND, DOES NOT SPECIFY HEIGHT OF
 STAND.AMENDED 1997 SMC 304.2.5
 REQUIRES A MINIMUM OF 18" FROM THE
 ROOF SURFACE TO THE BOTTOM OF THE
 SUPPORT RAIL.
  
 4.PLEASE INDICATE CONDENSATE LINE
 LINE SIZE, ROUTING AND TERMINATION
 ON PLANS FOR REVIEW.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 6 Status F Date 2002-10-29 Cont ID  
Sent By kstevens Date 2002-10-29 Time 11:45 Rev Time 0.50
Received By kstevens Date 2002-10-29 Time 11:45 Sent To  
Notes
2002-10-29 00:00:00DENIED
  
 1) FOURTH NOTICE - GAS PERMIT REQUIRED
 PLEASE SUBMIT PLANS WHEN APPLYING FOR
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER STANDARD
 GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE STANDARD GAS CODE SECS. 305.2 THRU
 305.4 AND TABLES 305.4(A) THRU 305.4(E).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 THE STANDARD GAS CODE SEC. 305.4(I).
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER THE STANDARD GAS
 CODE SECS. 402.4 THRU 402.4.4.7.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER STANDARD GAS CODE SEC. 305.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER THE STANDARD GAS CODE SECS
 602 THRU 612.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 STANDARD GAS CODE SEC. 402.
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 5 Status F Date 2002-06-20 Cont ID  
Sent By pkrauss Date 2002-10-23 Time 15:45 Rev Time 0.00
Received By kstevens Date 2002-06-20 Time 08:39 Sent To  
Notes
2002-06-20 00:00:00SUBMITTAL NOT ACCEPTABLE. NO GAS PERMIT
 APPLIED FOR. GAS PERMIT REQUIRED, SEE
 ATTACHED SHEET FOR GAS PERMIT REQUIRE-
 MENTS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-05-06 Cont ID  
Sent By kstevens Date 2002-05-06 Time 19:02 Rev Time 0.00
Received By kstevens Date 2002-05-06 Time 19:02 Sent To  
Notes
2002-05-06 00:00:00REVISION OK - ADDED LAVS, HAND SINK, C/O
 3 COMP KIT SINKECT

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-11-14 Cont ID  
Sent By pschmitz Date 2001-11-14 Time 10:27 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-11-14 00:00:00PROVISO SEPERATE PLANS & PERMIT FOR GAS
2001-11-10 00:00:00PREVIOUS PLAN REVIEW DATED 10-27-01 NOT
 ADDRESSED. PAUL S.NOT APPROVED.`

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-10-27 Cont ID  
Sent By pschmitz Date 2001-10-27 Time 13:58 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-10-27 00:00:00PLUMBING PLAN REVIEW, DENIED.
 PLEASE ADDRESS PREVIOUS NOTES 08-22-01
 (3) SHT P-1, REFERENCE TO AIR CHAMBERS,
 PDI-WH 201,STATES AIR CHAMBERS ARE A
 TEMPOARY FIX.USE WATER HAMMER ARRESTOR
 PLACEMENT PER MFG INSTRUCTIONS, NOT AT
 HIGH POINT OF SYSTEM, SPECIFY TYPE.
 (5) SHT P-3 RM C-35 GWH, SAFE WASTE NOT
 ALLOWED, SEC 1001.8 PLBG FIXTURES TO BE
 SEPERATELY TRAPED.
 (NEW COMMENT) SHT P-3,6" BUILDING DRAIN.
 SEC 914,BUILDING DRAIN SHALL NOT PASS
 THRU A BATTERY VENTED BRANCH.
 ALSO TWO WAY CLEANOUT LOCATED 3' OUTSIDE
 BUILDING, SEC 710.2
 PLEASE SUBMIT CIVIL PLANS, SHOWING ALL
 SITE UTILITIES.
 SEPERATE PLANS FOR GAS AND IRRIGATION
 SIGNED AND SEALED AT TIME OF PERMIT.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-22 Cont ID  
Sent By kstevens Date 2001-08-22 Time 19:33 Rev Time 0.00
Received By kstevens Date 2001-08-22 Time 19:33 Sent To  
Notes
2001-08-22 00:00:00DENIED
 REFERENCE: SPC-94/FACBC-97
  
 1) PROVIDE AVERAGE DAILY ATTENDENCE FIG-
 URES FOR CLASSROOMS TO COMPUTE MINIMUM
 FACILITIES PER TABLE 407- SPC-94
  
 2) PAGE A12 WATER CLOSETS TO COMPLY WITH
 SECT. 4.16 - LAVS. TO COMPLY WITH 4.19 -
 URNALS TO COMPLY WITH 4.18 - SINKS TO
 COMPLY WITH 4.24 - FACBC-97.
  
 3) PAGE P-1 GENERAL PLUMBING NOTES #12.
 AIR CHAMBERS SHALL COMPLY WITH SPC-94,
 607.8.2 & 607.8.3 ACCESSABLE/RECHARGE-
 ABLE (PDI WH 201).-WATER HAMMER ARR-
 ESTORS SHALL BE INSTALLED PER MANUFACT-
 URES INSTALLATION INSTRUCTION.
  
 4) PAGE P-2 SANITARY - DISHWASHER TO
 DRAIN INTO KITCHEN SINK TAIL PIECE.
  
 5) PAGE P-3 ROOM C35 (LAUNDRY/JANITOR),
 HUB DRAIN NOT ALLOWED. RELIEF LINE TO
 RUN FULL SIZED OUTSIDE TO AN OBSERVABLE
 POINT OR TO A FLOOR SINK WITH TRAP PRIM-
 ER. (PAGE P-10 SHOWS SAME DETAIL)
  
 6) PAGES P-3 & P-5, 6" SANITARY TO RUN
 TO 6 X 4 WYE AFTER 1ST BATHROOM. (C18)
  
 7) PAGE P-10 WATER HEATER DETAIL. DI-
 ELECTRIC UNIONS NOT ALLOWED.
  
 8) SEPARATE GAS PERMIT REQUIRED. SEE
 ATTACHED SHEET FOR GAS PERMIT APPLICAT-
 ION REQUIREMENTS. INFORMATION TO BE FILL
 ED OUT WHEN APPLYING FOR GAS PERMIT.
  
 9) SEPARATE IRRIGATION PERMIT REQUIRED.
 PLUMBING CONTRACTOR TO PROVIDE VALVE AND
 ADAPTOR FOR IRRIGATION CONTRACTOR TO TIE
 INTO.
  
 10) BACKFLOW REQUIRED FOR WATER SERVICE
 INTO NEW BUILDING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-11-01 Cont ID  
Sent By sgraham Date 2001-11-01 Time 10:34 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***