Plan Review Details - Permit 01080263
Plan Review Stops For Permit 01080263
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2001-08-30 Cont ID  
Sent By mamini Date 2001-08-30 Time 16:16 Rev Time 2.00
Received By mamini Date 2001-08-30 Time 16:16 Sent To  
Notes
2001-08-30 00:00:00PASSED:
 1. RESPONSES TO THE PREVIOUS REVIEW
 COMMENTS DATED 8-08-01 SATISFACTORY AND
 IMPLEMENTED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-08-08 Cont ID  
Sent By mamini Date 2001-08-08 Time 10:40 Rev Time 5.00
Received By mamini Date 2001-08-08 Time 09:16 Sent To  
Notes
2001-08-08 00:00:00FAILED:
 1. PLEASE PROVIDE DETAILS FOR THE RIPRAP
 ENDWALL OR REFER TO FDOT STD. INDEX.
 2. PLEASE PROVIDE STOP BARS AT ALL NEW
 AND EXISTING DRIVEWAYS.
 3. PLEASE COORDINATE WITH PUBLIC
 UTILITIES ENGINEERING SERVICES REGARDING
 THE PROPOSED LIFT STATION AND ALL THE
 NEW CONNECTIONS TO CITY'S SERVICES, 659-
 8040.
 4. WE RECOMMEND TO LOCATE THE PROP. 3"
 DUAL REDUCED PRESSURE BACKFLOW PREVENTER
 ASSEMBLY AT THE CORNER NEXT TO THE 3"
 METER.ALL THE BACKFLOW PREVENTERS MUST
 BE HIDDEN FROM VIEW WITH SHRUBS.
 5. PLEASE STATE THE PURPOSE OF THE WATER
 METER AS MARKED ON SHEET C-2.
 6. PLEASE PROVIDE DETAILS FOR THE
 PROPOSED DUMPSTER.IT SHOULD BE
 DETAILED PER CITY'S REQUIREMENT IF TO BE
 PICKED UP BY THE CITY.
 7. PLEASE PROVIDE STORM WATER
 CALCULATIONS FOR OUR REVIEW.
 8. PLEASE PROVIDE PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR ENTIRE SITE.
 9. ALL UTILITIES THAT ARE ABANDONED MUST
 BE GROUTED AND PLUGGED.
 1O. ANY WORK WITHIN PUBLIC R.O.W WILL
 REQUIRE A SEPARATE PERMIT FROM CITY'S
 ENGINEER OFFICE, 659-8040.
 11. PLEASE CALL RODNEY COMPO, INDUSTRIAL
 PRETREATMENT INSPECTOR FOR INSTALLATION
 AND OR INSPECTION OF THE PROP. GREASE
 TRAP, 837-4051EXT. 4074.
 12. CITY STD. AND DETAILS MAY BE
 OBTAINED FROM PUBLIC UTILITIES
 ENGINEERING SERVICES DEPARTMENT 659-8040
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-09-04 Cont ID  
Sent By mcarsill Date 2001-09-04 Time 09:38 Rev Time 0.00
Received By mcarsill Date 2001-09-04 Time 09:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-09 Cont ID  
Sent By mcarsill Date 2001-08-09 Time 09:56 Rev Time 0.00
Received By mcarsill Date 2001-08-09 Time 09:56 Sent To  
Notes
2001-08-09 00:00:001) NO PORTIONS OF THE UNDERGOUND FIRE
 LINES ARE TO BE RUN UNDERNEATH ANY
 BUILDINGS.
 2) ALL UNDERGROUND FIRE LINES TO BE
 PRESSURE TESTED FOR TWO HOURS.
 3) PLEASE INDICATE ANY AND ALL FIRE
 HYDRANT LOCATIONS ON EAST AVENUE AND
 LOCATED ON THE HOSPICE SITE.
 4) ELECTRONIC DEVICES REQUIRED ON
 OS&Y VALVES.
 5) NEW UNDERGROUND FIRE LINES TO COMPLY
 WITH NFPA 24, UTILITY AND FIRE RESCUE
 REQUIREMENTS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910