Plan Review Details - Permit 01080260
Plan Review Stops For Permit 01080260
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2003-01-16 Cont ID  
Sent By hpiskura Date 2003-01-16 Time 11:04 Rev Time 0.00
Received By hpiskura Date 2003-01-16 Time 11:04 Sent To  
Notes
2003-01-16 00:00:00THIS PERMIT WAS CLOSED 11/22/02, AND THE
 DATE ON THE SUBMITTAL IS 12/18/02.
 ALSO, THE DOORS SHOWN ON SHEET A6 AS
 3'-6" DO NOT COMPLY WITH SBC TABLE 1004
 FOR GROUP I OCCUPANCY UNRESTRAINED WHICH
 REQUIRES 44" CLEAR.THE CHANGES MUST
 BE BY THE DESIGNER OF RECORD AND BEAR
 HIS EMBOSSED SEAL AND ORIGINAL
 SIGNATURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2002-07-31 Cont ID  
Sent By hpiskura Date 2002-07-31 Time 09:40 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-07-31 00:00:00REVISION SHEET A17 DATED 5/30/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2002-05-13 Cont ID  
Sent By hpiskura Date 2002-05-13 Time 10:43 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-05-13 00:00:00LONGARC SHOP DWGS FOR STAIR # 159 GARAGE
  
 THE STAIRS DO NOT COMPLY WITH SBC 1003.7
 REQUIREMENTS FOR THE RISE TO RUN RATIO
 TO BETWEEN 24" AND 25".

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-05-08 Cont ID  
Sent By hpiskura Date 2002-05-08 Time 10:08 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-05-08 00:00:00REVISION #7 DATED 3/13/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-11-30 Cont ID  
Sent By lsmith Date 2001-11-30 Time 15:36 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2001-11-27 Cont ID  
Sent By hpiskura Date 2001-11-27 Time 15:55 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-11-27 00:00:00 
  
  
  
 THE FIRE PROTECTION PLANS ARE REQUIRED
 TO BE SIGNED AND SEALED
  
 IF SOMEONE HAS NOT SPECIFICALLY
 REQUESTED THAT "VOID" PAGES BE RETAINED
 IN THE PLANS AND SPECIFICTIONS, I
 SUGGEST THAT THEY BE REMOVED AS THEY
 ARE A SOURCE OF CONFUSION AND CLUTTER.
  
 SHEET LS-1 DATED 10/4/01 SHOWS A SMOKE
 BARRIER ALONG GRID LINE L AT THE
 EXISTING BUILDING.WILL THE TWO
 PROPOSED WINGS ON THE NORTH END SHOWN
 WITH "RESIDENTIAL ROOMS" BE REQUIRED TO
 TRAVEL TO THAT BEGINS NEAR GRID A AND
 4?WHAT IS THE DISTANCE?SEE SBC
 409.1.2.1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-10-16 Cont ID  
Sent By hpiskura Date 2001-10-16 Time 10:52 Rev Time 0.00
Received By hpiskura Date   Time   Sent To Z
Notes
2001-10-16 00:00:00THE FIRE SPRINKLER PROTECTION SYSTEM
 DESIGN IS REQUIRED BY FS 553.79 (2) TO
 BE SUBMITTED WITH THE PERMIT PLANS.
  
 THE SPECIFICATIONS BOOKS WERE RETURNED
 MARKED VOID AND WERE NOT REVIEWED.
 PROVIDE THREE COPIES OF SIGNED, SEALED
 AND DATED SPECIFICATIONS SO THAT CODE
 COMPLIANCE MAY BE DETERMINED.
  
 SHEET S1 STILL HAS NOTES LIKE "LATEST
 EDITION"SEE SBC 3502.
  
 THE ROOM SHOWN AS "SOILED UTILITY" IS
 THAT A SOILED LINEN ROOM?SEE SBC
 409.1.2.3.
  
 LS1 NOW SHOWS A SMOKE BARRIER NEAR GRID
 LINE A.IT APPEARS THAT THERE ARE
 NEITHR PATIENT TREATMENT OR SLEEPING
 FACILI
 TIES IN THE AREA CONTAINED IN GRID A - L
 AND IN THE EXISTING PATIENT AREA THE
 DISTANCE WOULD EXCEED THE 200' TRAVEL
 DISTANCE ALLOWED BY SBC 409.1.2.1.
 PLEASE CLARIFY THE DESIGN INTENT.
 LARIFY THE DESIGN INTENT.
  
 SEE THE 8/31/01 NOTES RE: IMPACT FEES,
 RESIDENT INSPECTOR, AND PRODUCT/TEST
 REPORTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-09-04 Cont ID  
Sent By hpiskura Date 2001-08-31 Time 15:28 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-08-31 00:00:00BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.CALL 233-5025 FOR MORE
 INFORMATION.
  
 AS PROVIDED FOR IN SBC 105.3 A RESIDENT
 INSPECTOR IS REQUIRED FOR A PROJECT OF
 THIS SCOPE.CONTACT DON NEELY AT
 561-659-8096 X 8333 FOR MORE
 INFORMATION.
  
 THIS PROPERTY IS IN A FLOOD ZONE AH BFE
 17.0' NGVD.
  
 THE FIRE PROTECTION PLANS MUST BE
 INCLUDED WITH THE PERMIT PLANS.SEE FS
 553.79 (2).
  
 THE LS PAGES DO NOT CLEARLY INDICATE THE
 LOCATION OF EXISTING OR PROPOSED NEW
 SMOKE BARRIER WALLS REQUIRED BY SBC 409.
 1.2.INCLUDE THE EXISTING PORTION OF
 THE BUILDING. DEMONSTRATE ALSO THE
 REMAINING REQUIREMENTS OF SBC 409.
  
 THE MAINTENANCE AND STORAGE ROOMS IN THE
 VICINITY OF GRID LINES F,3 ARE REQUIRED
 TO HAVE FIRE RATED SEPARATION FROM THE
 BUILDING BY SBC 409.1.5.
  
 SHEET S1 CITES ASCE 7-98.THE CITY IS
 CURRENTLY USING THE 1997 SBC WHICH
 INVOKES ASCE 7-95.FURTHER THE
 OCCUPANCY CLASSIFICATION OF THIS
 BUILDING IS A CATGORY III AND AN
 IMPORTANCE FACTOR OF 1.15 NOT THE 1.0
 DECLARED.
  
 SHEET S10, "CABLE SIZE AND SPACING PER
 LOCAL BUILDING CODE REQUIREMENTS" IS
 NOT AN ACCEPTABLE SUBSTITUTE FOR
 SPECIFIC DESIGN INFORMATION.SEE SBC
 104.2.
  
 SHEET S1, CITE THE SPECIFIC DESIGN
 STANDARDS AND EDITIONS USED.SEE SBC
 3502
  
 SHOW HOW THE ONE HOUR FIRE RATED
 ASSEMBLY FOR THE ROOF WILL BE
 ACCOMPLISHED.SEE SBC TABLE 600.
  
 AT TIME OF PERMIT APPLICATION PROVIDE
 TEST REPORTS AND/OR PRODUCT NOTICE OF
 ACCEPTANCE REPORTS FOR THE DOORS,
 WINDOWS AND ROOF COVERING.
  
 SPECIFICATIONS 08800 CALL OUT A BROWARD
 COUNTY PRODUCT APPROVAL.THE CITY
 REQUIRES METRO-DADE OR TESTING FROM A
 NATIONAL EVALUATION SERVICE CERTIFYING
 COMPLIANCE WITH SSTD 12-97.

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2002-05-01 Cont ID  
Sent By dpalmer Date 2002-05-01 Time 18:53 Rev Time 0.00
Received By dpalmer Date 2002-05-01 Time 18:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2002-02-08 Cont ID  
Sent By dpalmer Date 2002-02-08 Time 11:32 Rev Time 0.00
Received By dpalmer Date 2002-02-08 Time 11:32 Sent To  
Notes
2002-02-08 00:00:00********************** UNSAT ***********
  
 1)NOTE: PLEASE NOET THAT LETTER OF
 METHOD PROPOSED OF SHUTTING DOWN EM
 MAIN WAS DECLINED BY FIRE AND THE BLDG
 OFFICIAL.
 CHIEF ELECTRICAL INSPECTOR AND ELEC.
 PLAN REVIEW HAS ALSO DECLINED OPT METHOD
  
  
 PLEASE SUBMIT REVISED RISER DIAGRAM AND
 SERVICE LOCATION FOR REVIEW. IF THERE
 ARE ANY QUESTIONS, PLEASE CALL.,
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2002-02-05 Cont ID  
Sent By dpalmer Date 2002-02-05 Time 06:47 Rev Time 0.00
Received By dpalmer Date 2002-02-05 Time 06:40 Sent To  
Notes
2002-02-05 00:00:00***************** UNSAT ***************
  
 PLEASE NOTE THAT PLANS ARE BACK IN FOR
 REVIEW. AS PER CONVERSATIONS ON PHONE
 WITH ENGINEER ALL MAINS WERE SAID TO BE
 GROUPED AND THE ONLY ISSUE WAS TO
 CLARIFY DOORS IN MAIN ELECTRICAL ROOM.
  
 1)NOTE: PLEASE NOTE "MAIN" FOR EMDP IS
 SHOWN BEING IN GENERATOR ROOM. PLEASE
 NOTE THE MAIN COMING FROM NORMAL FPL
 POWER IS LOCATED IN MAIN ELEC ROOM. THIS
 IS FINE, BUT WHEN SYSTEM LOSES NORMAL
 POWER AND GENERATOR KICKS IN, THE POWER
 FROM GEN GOES DIRECTLY TO EMDP AND
 THROUGHOUT EM PANELS. PLEASE NOTE, MAINS
 ARE STILL NOTE GROUPED PER 230-72.
 ALL EM PANELS WOULD BE "HOT" EVEN AFTER
 SHUTTING DOWN MAINS.
 WHATEVER HAPPENED TO SERVICE COMING INTO
 NEW ELECTRICAL/GENERATOR ROOM AND THEN
 FEEDING EXISTING BLDG?
 PLEASE NOTE 230-76/230-79
 PLEASE ALSO NOTE "EMDO " IS SHOWN AS
 "MLO"? PLEASE NOTE THAT MAIN ON GEN.
 MUST BE ON OUTSIDE OF UNIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2001-12-31 Cont ID  
Sent By dpalmer Date 2001-12-31 Time 11:36 Rev Time 0.00
Received By dpalmer Date 2001-12-31 Time 11:36 Sent To  
Notes
2001-12-31 00:00:00****************** UNSAT ************
  
 1)NOTE: PLEASE NOTE, PLANS ARE NOW
 MOVING TWO OF THE THREE MAINS BACK TO
 ORIG ELECTRICAL ROOM? PLEASE CLARIFY
 HOW THE MAINS ARE NOW GROUPED PER 230-72
 ??
 PLEASE NOTE THAT THIS WAS AN ISSUE
 BEFORE AND PLANS WERE CORRECTED, WHY
 IS THIS BEING CHANGED BACK TO THE SAME
 COMMENTS AS BEFORE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRIAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-11-30 Cont ID  
Sent By dpalmer Date 2001-11-30 Time 14:58 Rev Time 0.00
Received By dpalmer Date 2001-11-30 Time 14:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-11-07 Cont ID  
Sent By dpalmer Date 2001-11-07 Time 19:05 Rev Time 0.00
Received By dpalmer Date 2001-11-07 Time 19:05 Sent To  
Notes
2001-11-07 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE AS PER LAST
 CONVERSATION, EITHER SERVICE WAS GOING
 TO BE GROUPED AND CIRCUITS BE ZONED SO
 NOT TO CROSS EXISTING WITH NEW, OR
 A NEW SERVICE LARGE ENOUGH TO BACK FEED
 EXISTING?
 PLEASE NOTE: 230-2 /230-72
  
 2)NOTE: PLEASE NOTE THAT SHUNT TRIPS
 ARE NOT RATED FOR PURPOSE SHOWN. NEEDS
 TO MEET 230-76 AND 230-79.
  
  
 PLEASE CALL TO SET UP A MEETING TO GO
 OVER ELECTRICAL SERVICE AND REQ`MENTS
 FOR PROJECT. PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 JAKE LEAHY
 CHIEF ELECTRICAL INSPECTOR
 561-659-8096 EXT 8451

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-10-09 Cont ID  
Sent By dpalmer Date 2001-10-09 Time 06:57 Rev Time 0.00
Received By dpalmer Date 2001-10-01 Time 21:31 Sent To  
Notes
2001-10-09 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SHOW HOW NEW SERVICE
 CIRCUITS ARE GOING TO BE"ZONED" FROM
 EXISTING CIRCUITS? RISER SHOWS NEW
 SERVICE FEEDING EXISTING PANELS IN THE
 EXISTING BLDG.
 IS IS NOTED ON THIS PLAN REVIEW, THAT
 THE NEW AND OLD SERVICE IS NOT GROUPED,
 THIS WILL BE ALLOWED DUE TO THE SIZE OF
 THE EXISTING SERVICE AND BLDG AS LONG
 AS SERVICES ARE LABELED WITH THE
 PLAGUESTHAT ARE NOTED ON PLANS.
 PLEASE SHOW HOW NEW AND OLD CIRCUITS
 AREGOING TO BE SEPARATED.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 THIS WAS SUBMITTED TO THE CHIEF
 ELECTRICAL INSPECTOR FOR REVIEW AND
 "ZONING"
 CLARIFICATIONS NEEDS TO BE SUBMITTED.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 JAKE LEAHY
 CHIEF ELECTRICAL INSPECTOR
 561-659-8096 EXT 8451

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-28 Cont ID  
Sent By dpalmer Date 2001-08-28 Time 19:58 Rev Time 0.00
Received By dpalmer Date 2001-08-28 Time 19:58 Sent To  
Notes
2001-08-28 00:00:00**************** UNSAT ***************
  
 PLEASE NOTE THAT ELECTRICAL PLANS ARE IN
 VERY GOOD SHAPE.
 PLEASE PLACE NOTE ON SHEET E-3 AND E-12
 FOR IDENTIFICATION OF MAINS ON DOORS
 ON OUTSIDE OF GENERATOR ROOM AND MAIN
 ELECTRICAL ROOM. PER 230-2E
  
 PLEASE NOTE THAT PLANS WOULD HAVE BEEN
 REDLINED BUT WERE COMING BACK FOR OTHER
 COMMENTS AND WERE ONLY IN FOR PLAN
 REVIEW.
 PLEASE PLACE NOTE ON PLANS AND SUBMIT
 FOR FINAL REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-09-21 Cont ID  
Sent By mamini Date 2001-09-21 Time 16:40 Rev Time 0.00
Received By mamini Date 2001-09-21 Time 16:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2003-01-16 Cont ID  
Sent By nmccray Date 2003-01-16 Time 12:49 Rev Time 0.00
Received By nmccray Date 2003-01-16 Time 12:49 Sent To  
Notes
2003-01-16 00:00:001) PLANS ARE NOT STAMPED AND SEALED.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT. 8497
 8352910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-05-14 Cont ID  
Sent By mcarsill Date 2002-05-14 Time 10:30 Rev Time 0.00
Received By mcarsill Date 2002-05-14 Time 10:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-11-28 Cont ID  
Sent By mcarsill Date 2001-10-29 Time 10:49 Rev Time 0.00
Received By mcarsill Date 2001-10-29 Time 10:49 Sent To  
Notes
2001-10-29 00:00:001) NO FIRE SPRINKLER OR HYDRAULIC
 CALCULATIONS PROVIDED WITH PLANS.
 2) PROVIDE MORE DETAILS ON 2000
 GALLON ABOVEGROUND FUEL TANKS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-09-25 Cont ID  
Sent By mcarsill Date 2001-09-25 Time 08:35 Rev Time 0.00
Received By mcarsill Date 2001-09-25 Time 08:35 Sent To  
Notes
2001-09-25 00:00:001) NO FIRE SPRINKLER OR HYDRAULIC
 CALCULATIONS PROVIDED WITH PLANS. THESE
 ARE REQUIRED AT TIME OF PERMIT.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-27 Cont ID  
Sent By mcarsill Date 2001-08-27 Time 13:07 Rev Time 0.00
Received By mcarsill Date 2001-08-27 Time 13:07 Sent To  
Notes
2001-08-27 00:00:001) HOW IS FIRE ACCESS PROPOSED TO THE
 RESIDENCE ROOMS AND FUTURE TWO-STORY
 FUTURE EXPANSION.
 2) FIRE PROTECTION NOTE ON LS-1
 INDICATES ROOM 161 WILL BE PROTECTED
 BY AN FM 200 SYSTEM. FM 200 SYSTEM
 CANNOT BE USED IN LIEU OF FIRE
 SPRINKLERS.
 3) TABLE AND CHAIRS LOCATED DIRECTLY
 IN FRONT OF SINGLE EXIT DOORS IN STAFF
 DINING 2151.
 4) PLEASE EXPLAIN ROLL-DOWN NOTE ON
 PAGE LS-1, PATIENT RECEPTION 464, NEAR
 EXIT DOOR.
 5) PLEASE EXPLAIN FUTURE THERMAL STORAGE
 AREA, ON PAGE LS-1, WHAT IS THIS USED
 FOR.
 6) PLEASE PROVIDE MORE DETAILS ON
 EMERGENCY GENERATOR. IF EMERGENCY
 GENERATOR IS DIESEL FUEL SUPPLIED, IT
 MUST BE AT LEAST AT LEAST TWO-HOUR
 RATED.
 7) AUTOMOBILE PARKING GARAGE SHALL BE
 SEPARATED BY AT LEAST A TWO HOUR FIRE
 RATING NOT A ONE HOUR AS NOTED IN THE
 FIRE RESISTANCE SEPARATION NOTES ON
 PAGE LS-1.
 8) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY NEW HOOD,DUCT,AND SUPPRESSION
 SYSTEMS PLANNED FOR KITCHEN 700.
 9) DEMOLITION ACTIVITIES PLANNED SHALL
 NOT INTERFERE WITH ANY EXIT ACCESS,
 EXITING, OR EXIT DISCHARGE.
 10) IS THE EXISTING LIQUID OXYGEN TANK
 EXISTING OR NEW. HOW DOES THIS TANK
 AND APPURTENANT EQUIPMENT INTERFERE
 WITH ANY EXITING FROM THE CORRIDOR.
 11) PLEASE INDICATE EXIT CAPACITY FOR
 STAIR 159. THIS STAIR APPEARS TO
 PROVIDE EXITING FOR THE GARAGE AND
 BUILDING.
 12) CANVAS CANOPIES TO BE FIRE
 RETARDANT.
 13) FOLDING PARTITION WHEN USED IN STAFF
 DINING 138 LIMITS ACCESS TO EXIT DOOR
 138A.
 14) PLEASE INDICATE OCCUPANT LOADS FOR
 TRAINING ROOM 200 AND 200A.
 15) NO EXIT SIGNS DISPLAYED IN TRAINING
 ROOM 200 AND 200A.
 16) SINGLE MEANS OF EGRESS PROVIDED FROM
 CLERICAL 214. PLEASE EXPLAIN.
 17) FULL OXYGEN CYLINDERS SHOULD NOT
 BE STORED WITH EMPTY OXYGEN CYLINDERS
 IN 02 STORAGE G101. WHAT SAFETY
 PRECAUTIONS ARE PLANNED FOR 02 ROOM
 G101.
 18) NO FIRE SPRINKLER OR HYDRAULIC
 CALCULATIONS PROVIDED WITH PLANS.
 19) PLEASE INDICATE ON PLANS THAT
 GARAGE IS CONSIDERED OPEN AND DOCUMENT
 PERCENTAGE OF OPENINGS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-01-30 Cont ID  
Sent By btrobaug Date 2003-01-30 Time 15:07 Rev Time 0.00
Received By btrobaug Date 2003-01-28 Time 15:07 Sent To  
Notes
2003-01-30 00:00:00COMM. BOARD# 20./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-23 Cont ID  
Sent By dpalmer Date 2002-12-23 Time 10:48 Rev Time 0.00
Received By dpalmer Date 2002-12-23 Time 10:48 Sent To  
Notes
2002-12-23 00:00:00TO COMM BOARD. #44

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-19 Cont ID  
Sent By btrobaug Date 2002-12-19 Time 08:42 Rev Time 0.00
Received By btrobaug Date 2002-12-18 Time 08:42 Sent To  
Notes
2002-12-19 00:00:00COM BOARD #

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2003-02-08 Cont ID  
Sent By pkrauss Date 2003-02-08 Time 07:46 Rev Time 0.50
Received By pkrauss Date 2003-02-08 Time 07:29 Sent To  
Notes
2003-02-08 00:00:00MECHANICAL PERMIT 01100489 - AS BUILT
 DRAWINGS.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status N Date 2003-01-06 Cont ID  
Sent By pkrauss Date 2003-01-06 Time 15:46 Rev Time 0.30
Received By pkrauss Date 2003-01-06 Time 15:17 Sent To  
Notes
2003-01-06 00:00:00AS BUILT DRAWINGS ARE NOT STAMPED &
 SEALED BY ENGINEER OF RECORD.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2002-04-25 Cont ID  
Sent By pkrauss Date 2002-04-25 Time 15:23 Rev Time 1.30
Received By pkrauss Date 2002-04-25 Time 14:15 Sent To  
Notes
2002-04-25 00:00:00ADDED HEAT EXCHANGER, GLYCOL SYSTEM

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-01-04 Cont ID  
Sent By pkrauss Date 2002-01-04 Time 09:11 Rev Time 0.40
Received By pkrauss Date 2002-01-04 Time 07:53 Sent To  
Notes
2002-01-04 00:00:00MECH REV PERMIT 01100489 - RUNNING CHWS
 & R PIPING UNDERGROUND.
  
 UNDERGROUND PIPING SHALL HAVE A PRESSURE
 TEST PRIOR TO COVERING.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-11-30 Cont ID  
Sent By pkrauss Date 2001-11-28 Time 12:33 Rev Time 1.00
Received By pkrauss Date 2001-11-28 Time 12:33 Sent To  
Notes
2001-11-28 00:00:00 
  
 SEE FIRE DEPT COMMENTS ON FUEL TANK.
  
 PLEASE SUBMIT DETAILS
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-10-12 Cont ID  
Sent By pkrauss Date 2001-10-12 Time 13:03 Rev Time 3.00
Received By pkrauss Date 2001-10-08 Time 14:10 Sent To  
Notes
2001-10-12 00:00:00*******************DENIED***************
  
 1.FIRE DAMPERS REQUIRED FOR ROOM 186,
 PENETRATION THRU 3 HR WALL.ALSO
 ON PLAN SHEET M-5, ROOMS 241 AND
 237 REQUIRE FIRE DAMPERS.
  
 2.SMOKE DAMPERS REQUIRED FOR DUCTS
 PENETRATING SMOKE WALLS IN THE
 RESIDENTIAL AREAS (PLAN SHEET M-3).
 1997 SMC 610.3.1.
  
 3.AUXILIARY DRAIN PANS REQUIRED WITH
 OVERFLOW PROTECTION FOR FAN COIL
 UNITS.1997 SMC 304.8.6.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-27 Cont ID  
Sent By pkrauss Date 2001-08-27 Time 09:12 Rev Time 4.00
Received By pkrauss Date 2001-08-24 Time 13:54 Sent To  
Notes
2001-08-27 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS AS PER ASHRAE 62-89.
  
 2.PROVIDE AIR BALANCE SCHEDULE TO
 SHOW COMPLIANCE WITH 1997 SMC 501.2
  
 3.FIRE DAMPERS NOT INDICATED ON PLAN
 FOR THE FOLLOWING ROOMS - 111, 126,
 168.
  
 4.INDICATE MAKE-UP AIR FOR GAS FIRED
 WATER HEATERS.
  
  
 NOTE:EXHAUST DUCTS CONVEYING NOXIOUS
 GASES, FLAMMABLE/CORROSIVE VAPORS
 AND DUCTS SERVING COMMERCIAL FOOD
 COOKING AND PROCESSING EQUIPMENT
 SHALL TERMINATE OUTSIDE OF THE
 BUILDING AND LOCATED 10' FROM ANY
 ADJACENT BUILDING, PARKING AREA,
 ADJACENT PROPERTY LINE, WINDOW,
 DOOR OR AIR INTAKE AND AT LEAST
 10' ABOVE THE ADJOINING GRADE
 LEVEL.EXHAUST OUTLET WHICH IS
 LOCATED ABOVE THE ROOF SHALL
 TERMINATE AT LEAST 40" ABOVE THE
 ROOF SURFACE.
  
 ADDITIONAL PLANS AND PERMITS REQUIRED
 FOR HOOD, FIRE SUPRESSION, AND WALK-IN
 COOLERS.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 10 Status P Date 2003-02-05 Cont ID  
Sent By kstevens Date 2003-02-05 Time 17:08 Rev Time 0.50
Received By kstevens Date 2003-02-05 Time 17:08 Sent To  
Notes
2003-02-05 00:00:00AS BUILTS 0K

Review Stop P PLUMBING
Rev No 9 Status F Date 2003-01-14 Cont ID  
Sent By kstevens Date 2003-01-14 Time 10:55 Rev Time 0.50
Received By kstevens Date 2003-01-14 Time 10:55 Sent To  
Notes
2003-01-14 00:00:00DENIED
  
 AS-BUILTS SHALL BE SIGNED AND SEALED BY
 ENGINEER OF RECORD.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 8 Status F Date 2002-07-20 Cont ID  
Sent By kstevens Date 2002-07-20 Time 12:57 Rev Time 0.00
Received By kstevens Date 2002-07-20 Time 12:57 Sent To  
Notes
2002-07-20 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SHT P-4 GAS RISER DIAGRAM, MANUAL
 SHUT OFF VALVE SHALL BE NEXT TO UNION
 AND AUTOMATIC SHUT OFF VALVE NOT APPROX.
 15' AS SHOWN.
  
 2) SHT SHT P-11 PLEASE SHOW TYPE OF PIPE
 INSTALLED UNDERGROUND.
  
 3) SHT P-11 SHOWS 3" SCHED 40 PIPE SUPP-
 LYING 1,670,000 @ 520 FEET. MAX IS
 1,514,000 BTU,S. MINIMUM 4" PIPE SHALL
 RUN FROM METER TO EXISTING GAS LINE FOR
 EXISTING HEATER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 7 Status F Date 2002-07-20 Cont ID  
Sent By kstevens Date 2002-07-20 Time 13:11 Rev Time 0.00
Received By kstevens Date 2002-07-19 Time 20:25 Sent To  
Notes
2002-07-20 00:00:00SEE NEXT REVIEW.

Review Stop P PLUMBING
Rev No 6 Status P Date 2002-05-11 Cont ID  
Sent By kstevens Date 2002-05-11 Time 08:27 Rev Time 0.00
Received By kstevens Date 2002-05-11 Time 08:27 Sent To  
Notes
2002-05-11 00:00:00REVISION OK - SECONDARY ROOF DRAINS,
 MOVE RWL - MOVE BULK OXYGEN, ADD DROPS
 FOR OXYGEN - AIR IN PATIENT ROOMS -

Review Stop P PLUMBING
Rev No 5 Status P Date 2001-12-07 Cont ID  
Sent By pschmitz Date 2001-12-07 Time 14:42 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-12-07 00:00:00PROVISO MEDICAL GAS COMPLY W/ 99-C,CH-4
 LEVEL-I, FOR OXYGEN,VACUM.PES

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-11-14 Cont ID  
Sent By kstevens Date 2001-11-14 Time 12:41 Rev Time 0.50
Received By kstevens Date 2001-11-14 Time 12:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-11-03 Cont ID  
Sent By kstevens Date 2001-11-03 Time 11:39 Rev Time 1.50
Received By kstevens Date 2001-11-03 Time 11:39 Sent To  
Notes
2001-11-03 00:00:00DENIED
 REFERENCE: SPC-94 - SGC-97 - FABCB-97
 1) PERMIT WILL NOT BE ISSUED UNTIL THE
 LETTER FROM PALM BEACH COUNTY HEALTH
 UNIT DIVISION OF ENVIRONMENTAL HEALTH IS
 RECIEVED FOR PLAN REVIEW AS REQUESTED.
 2) PAGE P-7 WATER RISER DIAGRAM. WATER
 HAMMER ARRESTORS IN KITCHEN AREA AND IN
 PUBLIC RESTROOMS (HOT) ARE REQUIRED TO
 BE CLOSE TO FIXTURES NOT AT TOP OF DROP
 AS SHOWN. PLEASE COMPLY
 3) PAGE P-10 HUMIDIFIER DETAIL. FLOOR
 DRAIN TO BE CHANGED TO FLOOR SINK AS RE-
 QUESTED IN PREVIOUS COMMENTS.
 4) LETTER FROM RODNEY COMPO STILL NOT
 RECIEVED. LETTER REQUIRED FOR SIZING &
 LOCATING GREASE TRAP.
 5) PAGE A-11 HDCP SHOWER DETAIL. NEW DE-
 TAIL ADD IN FOR 60" SHOWER. HDCP SHOWERS
 SHOWN ARE NOT 60" SHOWERS AND SHALL COM-
 PLY WITH FIGURE 35(A) FACBC-97. PLEASE
 SHOW COMPLIANCE WITH SEC 4.21.
 6) PLEASE SUBMIT CALCULATION FOR CONFIN-
 ED SPACE FOR WATER HEATERS. RESPONSE
 SHOWS VENTING BY NOT CALCULATIONS FOR
 COMBUSTION AIR. LOUVERS SHOWN ON PAGE
 A-5 ARE NOT A LARGE ENOUGH AREA FOR
 EITHER ROOM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-10-09 Cont ID  
Sent By kstevens Date 2001-10-09 Time 15:52 Rev Time 0.00
Received By kstevens Date 2001-10-09 Time 15:52 Sent To  
Notes
2001-10-09 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97 - SGC-97
  
 NOTE: LETTER FROM PALM BEACH COUNTY
 HEALTH UNIT DIVISION OF ENVIRONMENTAL
 REQUIRED FOR PERMIT PLAN REVIEW.
  
 1) PLEASE PROVIDE A WATER RISER DIAGRAM
 FOR PLAN REVIEW. SHOW SIZE AND LOCATION
 OF WATER HAMMER ARRESTORS PER MANUFACT-
 URE INSTALLATION INSTRUCTION AND WH-PDI
 201.
 2) STORM RISER DIAGRAM STILL REQUIRED
 FOR ROOF DRAINS AND SECONDARY DRAINS
 FOR ROOF ABOVE KITCHEN AND ADJOINING NEW
 ROOFS AND FOR ROOFS ABOVE NEW RESIDENT-
 IAL AREAS. SUBMIT CALCULATIONS FOR ROOF
 DRAINS AND SECONDARY DRAINS. SHOW ALL
 PIPE SIZES.
 3) PAGE P-10 HUMIDIFIER DETAIL SHOWS THE
 INDIRECT WASTE TO FLOOR DRAIN. FLOOR
 SINK IS REQUIRED, PLEASE CHANGE DETAIL.
 4) LETTER FROM R. COMPO REQUIRED FOR
 GREASE TRAP SIZING AND LOCATION. PLEASE
 HAVE INFORMATION FOR PLAN REVIEW. (FROM
 PREVIOUS REVIEW ITEM #6.)
 5) PAGE A-11 HDCP SHOWER DETAIL. PLEASE
 SHOW ALL DETAILS REQUESTED ON PREVIOUS
 PLAN REVIEW. SEAT, CURB TO BE 1/2" PER
 FACBC-97. AND SEC 6 BACKING.
 6) MY PREVIOUS COMMENTS #12 NOT ADDRESS-
 ED FOR DIRECT VENT FOR WATER HEATER.
 PLEASE PROVIDE DETAILS.
 7) ALL CONDENSATE TO DRAIN SEPARATE FROM
 BLDG. PLEASE PROVIDE CONDENSATE RISER
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-28 Cont ID  
Sent By kstevens Date 2001-08-28 Time 08:14 Rev Time 0.00
Received By kstevens Date 2001-08-25 Time 15:41 Sent To  
Notes
2001-08-28 00:00:00DENIED
 REFERENCES SPC-94/FACBC-97
  
 NOTE: ROUTE PLANS TO PALM BEACH COUNTY
 HEALTH UNIT DIVISION OF ENVIRONMENTAL
 HEALTH, 901 EVERNIA STREET WPB FL 33401
 (561) 355-3018, BEFORE CITY OF WPB PLAN
 REVIEW.
  
 1) PLEASE PROVIDE A WATER RISER DIAGRAM
 FOR PLAN REVIEW. FOR SIZE AND PLACEMENT
 OF WATER HAMMER ARRESTORS, PLEASE SEE
 MANUFACTURES INSTALLATION INSTRUCTION &
 PDI WH 201. PAGES P-3, P-4, AND P-5.
  
 2) PAGES P-2 & P-7, W/C'S NOT VENTED
 PROPERLY ON MAIN BLDG DRAIN. W/C'S SHALL
 BE WET VENTED PER SPC-94, SECT. 911.
  
 3) PAGES P-2 & P-7, W/C'S NOT VENTED
 PROPERLY. PER SPC-94 SECT. 914, RELIEF
 VENT CONNECTED IN FRONT OF THE FIRST
 FIXTURE CONNECTION.
  
 4) STORM RISER DIAGRAM REQUIRED. SUBMIT
 CALCULATIONS FOR ROOF DRAINS AND SECOND-
 ARY DRAINS/SCUPPERS PER SPC-94 SECT.1108
 AND 1109. PAGES P-6, P-8, AND P-9.
  
 5) PAGE P-4, BACKFLOW REQUIRED FOR 1/2"
 CW HOOKUP TO HUMIDIFIER AT A/C IN ROOM
 161. SUBMIT DETAIL FOR BACKFLOW AND
 FLOOR SINK TO DRAIN INTO. SPC-94 SECT.
 606.1& SECT. 807
  
 6) GREASE TRAP TO BE LOCATED AND SIZED
 BY UTILITY DEPT. PLEASE CONTACT RODNEY
 COMPO AT (561) 837-4074 FOR APPROVED
 GREASE TRAP DETAIL SEE ATTACHED SHEET.
  
 7) PAGES P-4 & P-5. ELECTRIC WATER COOL-
 ERS SHALL COMPLY WITH FACBC-97 SECT. 415
 ALSO SECT. 4.1.3 (10) FOR PEOPLE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
  
 8) PAGE A-11, PLEASE SHOW DETAILS THAT
 BATHROOMS IN PATIENTS RESIDENTAL ROOMS
 COMPLY WITH FACBC-97. SECT. 6, (2). NO
 CURB ON SHOWER, SEAT & GRAB BARS IN
 SHOWER.
  
 9) SEPARATE PERMIT REQUIRED FOR GAS.
 SEE ATTACHED SHEET FOR GAS PERMIT APPLI-
 CATION REQUIREMENTS. ALL INFORMATION
 TO BE SUBMITTED WITH APPLICATION.
 PAGES P-4 & P-10
  
 10) SEPARATE PERMIT REQUIRED FOR MED-GAS
 PLEASE PROVIDE CONTRACTOR CERTIFICATION,
 BRAZER CERTIFICATION PER NFC99 SECT.
 4-3.1.2.12, AND 4-3.1.2.10. CHAPTER 17
 SECT. 17.3.4, SPECIFY A LEVEL FOR PIPING
 REQUIREMENTS, SOURCE EQUIPMENT, AND
 ALARM REQUIREMENTS. PER 99 NFC REF. CHAP
 TER 13. PAGES MP-1 AND MP-2.
  
 11) PLEASE SUBMIT A VACUUM SYSTEM DETAIL
 FOR PLAN REVIEW. SUBMIT MANUFACTURE'S
 INFORMATION ON PUMPS. MP-1 & MP-2.
  
 12) PLEASE SUBMIT DETAILS ON DIRECT VENT
 FOR WATER HEATER. N-36 VACUUM BREAKER
 REQUIRED ON BOTTOM FEED WATER HEATER,
 PLEASE SHOW DETAIL. 507.1.2 SPC-94
 PAGE P-10 W/HEATER DETAIL NOTE 15-2,
 110 DEGREE TO HAND SINKS ALSO. PAGE P-3
  
 13) PAGE FS-1 #16, VAC. BREAKER INSTALL-
 ED 6" ABOVE FLOOD RIM LEVEL.
  
 14) PAGE FS-1 #65 DISHWASHER TO SANITARY
 PER UTILITY DEPT. ALSO #'S 16 & 64, GAR-
 BAGE DISPOSALS TO DISCHARGE INTO SANIT-
 ARY, DIRECT HOOK UP.
  
 15) PAGE P-7, KITCHEN RISER DIAGRAM. DIA
 GRAM SHOWS RISER AS "SS", SHOULD BE "GW"
 ALSO GREASE WASTE AND SANITARY LINES CAN
 NOT TIE TOGETHER AS SHOWN AT NOTE 15-2
  
 16) PAGE FS-3, PLUMBING CONNECTION SCHED
 P-2 FUNNEL FLOOR DRAINS NOT APPROVED,
 PLEASE PROVIDE FLOOR SINKS. SPC-94 804.1
 AND SECT. 807.
  
 17) PAGE FS-3, PLUMBING CONN. SCHED.
 P-24 THRU P-29 SHALL COMPLY WITH GAS
 PERMIT APPLICATION REQUIREMENTS ( SEE
 ATTACHED).
  
 18) PAGE FS-3, PLUMB. CONN. SCHED. P-40
 AND P-42, SUBMIT BACKFLOW INFORMATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-10-18 Cont ID  
Sent By hpiskura Date 2002-04-30 Time 07:36 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***