Plan Review Details - Permit 01080252
Plan Review Stops For Permit 01080252
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-09-12 Cont ID  
Sent By hpiskura Date 2001-09-11 Time 12:01 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-09-11 00:00:00BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 THIS BUILDING WILL BE LOCATED INSIDE THE
 DESIGNATED FIRE DISTRICT. F102.2.6
 REQUIRES 2 HOUR RATED EXTERIOR WALLS
 FOR TYPE IV BUILDINGS.F102.2.5 1HOUR
 PROTECTION FOR 2 STORY BUILDINGS.
  
 SHEET CS2 INCORRECTLY CITES THE SOUTH
 FLORIDA BUILDING CODE.PLEASE REVISE
 AS NECESSARY.
  
 INCLUDE A RECENT PROPERTY SURVEY AT THE
 TIME OF PERMIT APPLICATION.
  
 SHOW HOW VERTICAL ACCESSIBILITY TO THE
 SECOND FLOOR WILL BE PROVIDED FOR THE
 HANDICAP.
  
 SHOW THE NATURE AND CHARACTERISTICS OF
 THE EQUIPMENT TO BE INSTALLED IN THE
 BUILDING.
  
 SHEET S0 CITES ASCE 7-93,THE 1997 SBC
 INVOKES ASCE 7-95.SEE SBC 3502 FOR
 REFERENCE STANDARDS AND EDITIONS.
  
 PROVIDE SPECIFIC STRUCTURAL INFORMATION
 FOR THE EXTERIOR WALL CLADDING. THE
 NOTES ON SHEET S01 ARE NOT SUFFICIENT.
 SHOW THE LOCATION, NATURE, MAGNITUDE AND
 DIRECTION OF THE FORCES TO BE RESISTED.
  
 SHOW THE FIRE DESIGN NUMBER FOR THE
 FIRERATED WALLS.SEE SBC 701.5.1.
  
 PROVIDE FIRE DEPARTMENT ACCESS FOR THE
 SECOND FLOOR IN ACCORDANCE WITH SBC 1405
  
 INCLUDE THE TEST REPORTS FOR THE ROOF
 COVERING, WINDOWS AND DOORS FOR THEIR
 SUITABILITY TO RESIST WINDLOADS.
  
 PROVIDE THREE SETS OF SIGNED AND SEALED
 ENERGY CODE CALCULATIONS AT TIME OF
 PERMITTING.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-21 Cont ID  
Sent By dpalmer Date 2001-08-21 Time 21:44 Rev Time 0.00
Received By dpalmer Date 2001-08-21 Time 21:44 Sent To  
Notes
2001-08-21 00:00:00**************** UNSAT **************
  
 1) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC) PER 215-3 AND
 230-42. PLEASE SHOW LOAD CALCUALTIONS
 COMPLETED, INLCUDING FINAL AMPERAGES.
  
 2)NOTE: PLEASE PLACE NOTE ON PLANS FOR
 ALL EQUIPMENT DISCONNECTING MEANS TO
 BE LABELED.PLEASE PLACE ON RISER DIAGRAM
  
 3)NOTE: PLEASE CLARIFY MANUAL MEANS OF
 DISCONNECT PER 230-76 FOR MAINS.
 PLEASE NOTE 230-79
  
 4)NOTE: PLEASE NOTE THAT BUILDING FOOTER
 STEEL TO BE PART OF THE GROUNDING
 ELECTRODE SYSTEM. PER 250-50.
  
 5)NOTE: PLEASE NOTE THAT COLOR CODING
 IS NOTED ON E1-1. PLEASE NOTE LOCAL
 AMENDMENTS FOR 277/480. BR/PURP/YELLOW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-08-29 Cont ID  
Sent By mamini Date 2001-08-29 Time 15:47 Rev Time 5.00
Received By mamini Date 2001-08-29 Time 15:47 Sent To  
Notes
2001-08-29 00:00:00FAILED:
 1. ANY NEW CONNECTION TO CITY SERVICES
 WILL REQUIRE A SEPARATE PERMIT FROM
 PUBLIC UTILITIES ENGINEERING SERVICES,
 ATTENTION, MANUAL GONZALEZ 659-8040,
 PLEASE SUBMIT TWO SETS OF CIVIL PLANS
 ONLY FOR THEIR REVIEW AND APPROVAL.
 2. ALL PVC PIPES USED FOR MAINS ON
 PRIVATE PROPERTY SHOULD BE AT MINIMUM
 SDR 26.
 3. ALL OFF STREET PARKING STALLS SHOULD
 BE PAINTED BY DOUBLE 4" WIDE.
 4. CITY'S STANDARD AND DETAILS MAY BE
 OBTAINS FROM PUBLIC UTILITIES ENGINEER-
 ING SERVICES DEPARTMENT, 659-8040.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-07 Cont ID  
Sent By mcarsill Date 2001-08-07 Time 13:48 Rev Time 0.00
Received By mcarsill Date 2001-08-07 Time 13:48 Sent To  
Notes
2001-08-07 00:00:001) PLEASE INDICATE ANTICIPATED OCCUPANT
 LOADS FOR THE BUILDING.
 2) PLEASE INDICATE FIRE AND PARAMEDICAL
 ACCESS TO THE BUILDING. GATES SHALL
 PROVIDE AT LEAST 20 FEET IN CLEAR
 WIDTH.
 3) NEW FIRE HYDRANT TO COMPLY WITH
 UTILITY AND FIRE RESCUE STANDARDS.
 4) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE EMERGENCY GENERATOR AND ANY
 FUEL SUPPLIES ASSOCIATED WITH IT.
 5) BUILDING ADDRESS REQUIRED PER CITY
 CODE REQUIREMENTS.
 6) BUILDING APPEARS TO BE WINDOWLESS. IF
 WINDOWS ARE NOT PROVIDED FOR RESCUE OR
 VENTILATION PURPOSES, THE BUILDING WILL
 HAVE TO BE FIRE SPRINKLER PROTECTED.
 PLEASE SEE NFPA 101, THE LIFE SAFETY
 CODE, 1985 EDTION, SECTION 30-1.3.5.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status C Date 2001-08-23 Cont ID  
Sent By ndenmark Date 2001-08-23 Time 09:58 Rev Time 0.50
Received By ndenmark Date 2001-08-23 Time 09:58 Sent To  
Notes
2001-08-23 00:00:00PROVISO:
 1. DUCT SMOKE DETECTORS TO BE TIED TO
 BUILDING FIRE ALARM SYSTEM OR TO HORN
 AND STROBE FOR NOTIFICATION IF NO
 BUILDING FIRE ALARM SYTEM.
 2. PROVIDE SEPARATE PLANS AND PERMIT FOR
 GENERATORS (FUEL PERMIT REQUIRED FOR
 FUEL SUPPLY EVEN IF PART OF GENERATOR).
 DO NOT LOAD FUEL INTO GENERATOR PRIOR TO
 FUEL PERMIT BEING ISSUED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-23 Cont ID  
Sent By kstevens Date 2001-08-23 Time 18:24 Rev Time 0.00
Received By kstevens Date 2001-08-23 Time 18:24 Sent To  
Notes
2001-08-23 00:00:00DENIED
  
 REFERENCE SPC-94 AND FACBC-97
  
 1) PAGE MP-1 PLUMBING NOTES. #11 PLEASE
 INSTALL WATER HAMMER ARRESTORS PER MAN-
 UFACTURE'S INSTALLATION INSTRUCTIONS AND
 PDI WH 201.
  
 2) PAGE MP-1 PLUMBING NOTES #12 DIELECT-
 RIC UNIONS NOT APPROVED FOR WATER DIS-
 TRIBUTION PIPE.
  
 3) PAGE MP-1 GENERAL NOTES #1 STANDARD
 PLUMBING CODE 1994 WILL BE USED.
  
 4) PAGE P-2 SANITARY RISER DIAGRAM. W/C
 NOT VENTED PROPERLY. SPC-94 SEC. 914.1
 FIXTURES FROM AN UPPER FLOOR SHALL NOT
 DISCHARGE INTO A BATTERY VENTED BRANCH.
  
 5) PLEASE SUBMIT BACKFLOW INFORMATION
 FOR PLAN REVIEW AND APPROVAL.
  
 6) BACKFLOWS ARE REQUIRED FOR WATER TIED
 INTO INTO CRAC'S. PLEASE SUBMIT MANUFAC-
 TURE'S SPEC. SHEETS FOR THESE UNITS.
 PAGES P-1 AND P-2.
  
 7) PLEASE PROVIED CALCULATIONS FOR MIN-
 IMUM FACILITIES FOR REVIEW. TABLE 407
  
 8) PLEASE PROVIDE CALCULATIONS FOR ROOF
 DRAINAGE. SIZE DOWNSPOUTS AND ALSO SIZE
 SCUPPERS PER SPC-94 SECTION 1108
  
 9) SHOW ACCESSABLE LIFT TO 2ND FLOOR.
 FACBC-97
  
 10) IRRIGATION PERMIT REQUIRED. PLUMBING
 CONTRACTOR TO TIE INTO WATER SERVICE AND
 INSTALL BACKFLOW FOR IRRIGATION CONTRA-
 CTOR.
  
 11) HDCP RESTROOMS 104 & 204. PER FACBC-
 97 SECTION 4.22.2 DOORS SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE REQUIRED FOR
 ANY FIXTURE.
  
 12) DRINKING FOUNTAINS TO COMPLY WITH
 FACBC-97 SECTION 4.15.2
  
 13) SHUTOFF VALVES FOR WATER DISTRIBUT-
 ION TO COMPLY WITH SPC-94 SECTION 610,
 INCLUDING 610.1, 610.4.1 AND 610.4.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***