Plan Review Details - Permit 01080248
Plan Review Stops For Permit 01080248
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-08-30 Cont ID  
Sent By hpiskura Date 2001-08-30 Time 11:30 Rev Time 0.00
Received By hpiskura Date 2001-08-30 Time 10:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-11-07 Cont ID  
Sent By dpalmer Date 2001-11-07 Time 19:28 Rev Time 0.00
Received By dpalmer Date 2001-11-07 Time 19:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-09-18 Cont ID  
Sent By dpalmer Date 2001-09-18 Time 17:45 Rev Time 0.00
Received By dpalmer Date 2001-09-18 Time 17:45 Sent To  
Notes
2001-09-18 00:00:00********** UNSAT ******
  
 1)NOTE: PLEASE NOTE THAT FIRE REVIEW
 STILL HAS COMMENTS TO BE ADDRESSED.
 PLEASE NOTE THAT 2X4 LAY IN FIXTURES
 SHOWN AS "NL" NIGHT LIGHTS, ARE THESE
 EM LTS ? PLEASE CLARIFY.
  
  
 PLEASE ADDRESS ANY FIRE COMMENTS AND
 SUBMIT CLARIFICATION ON "NL"? ARE THEY
 "EM"?
 PLEASE SUBMIT FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-21 Cont ID  
Sent By dpalmer Date 2001-08-21 Time 20:23 Rev Time 0.00
Received By dpalmer Date 2001-08-21 Time 20:18 Sent To  
Notes
2001-08-21 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE PROVIDE CLARIFICATION
 FOR EM LTS AND EXIT LTS. PLEASE NOTE
 THAT DUE TO COMMENTS FORM FIRE PLAN
 REVIEW. PLANS WILL HAVE CHANGES DONE TO
 THE ELECTRICAL SHEETS. PLEASE ADDRESS
 ABOVE AND FIRE REVIEW.
 ELECTRICAL PLANS ARE IN GOOD SHAPE
 OTHER THAN THE ABOVE CLARIFICATION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVOEW. IF THERE AREANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELELCTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-08-27 Cont ID  
Sent By lsmith Date 2001-08-27 Time 11:05 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-11-19 Cont ID  
Sent By mcarsill Date 2001-11-19 Time 13:58 Rev Time 0.00
Received By mcarsill Date 2001-11-19 Time 13:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-09-18 Cont ID  
Sent By mcarsill Date 2001-09-18 Time 13:20 Rev Time 0.00
Received By mcarsill Date 2001-09-18 Time 13:20 Sent To  
Notes
2001-09-18 00:00:001) SECURITY FEATURES PLANNED FOR EXIT
 DOOR IS TO BE FURTHER EXPLAINED. LOCKS
 ELECTRIC OR MAGNETIC MUST COMPLY WITH
 SPECIAL LOCKING ARRANGEMENTS. LOCKS
 ON EXIT DOORS MUST BE FAIL SAFE AND NOT
 FAIL SECURE. PLEASE EXPLAIN.
 2) NIGHT-LIGHTS ARE SHOWN AS EMERGENCY
 LIGHTING. NIGHT-LIGHTS ARE ACTIVATED
 HOW AND ARE THEY ON A TIMER. WHAT
 HAPPENS WHEN LOSS OF POWER OCCURS.
 PLEASE CORRECT EMERGENCY LIGHTING ISSUE
 UP.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-07 Cont ID  
Sent By mcarsill Date 2001-08-07 Time 15:48 Rev Time 0.00
Received By mcarsill Date 2001-08-07 Time 15:48 Sent To  
Notes
2001-08-07 00:00:001) DUST CONTROL METHODS SHALL NOT
 INCLUDE THE HANGING OF NON FIRE
 RATED VISQUEEN.
 2) PLEASE INDICATE LOCATIONS OF
 EXISTING FIRE ALARM EQUIPMENT.
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR NEW HOOD, DUCT AND EXTINGUISHING
 SYSTEM.
 4) GLASS AUTOMATIC DOORS TO COMPLY
 WITH POWERED OPERATED DOORS, PLEASE
 SEE NFPA 101, THE LIFE SAFETY CODE,
 1985 EDITION, SECTION 5-2.1.9.
 5) PLEASE INDICATE LOCATION OF
 CHAIN LINK FENCE.
 6) PLEASE CLEARLY INDICATE ILLUMINATED
 EXIT SIGNS AND EMERGENCY LIGHTS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-09-26 Cont ID  
Sent By pkrauss Date 2001-09-26 Time 10:22 Rev Time 0.35
Received By pkrauss Date 2001-09-26 Time 10:22 Sent To  
Notes
2001-09-26 00:00:00******************PROVISO***************
  
 REVIEW COMMENTS THE SAME AS 8-24-01.
  
 PRIOR TO CONNECTING TO ANY EXISTING
 DUCTWORK, CALL FOR AN INSPECTION.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION AND WALK-IN
 COOLER/FREEZER.PLEASE SUBMIT PLANS
 AND MANUFACTURER SUBMITTAL DATA WITH
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-08-24 Cont ID  
Sent By pkrauss Date 2001-08-24 Time 10:34 Rev Time 0.50
Received By pkrauss Date 2001-08-24 Time 09:52 Sent To  
Notes
2001-08-24 00:00:00*******************PROVISO**************
  
  
 PRIOR TO CONNECTING TO ANY EXISTING DUCT
 WORK, CALL FOR AN INSPECTION.
  
  
 ADDITIONAL PLANS AND PERMITS REQUIRED
 FOR HOOD, FIRE SUPRESSION AND WALK-IN
 COOLER.PLEASE SUBMIT MANUFACTURER
 SUBMITTAL DATA AND PLANS WITH PERMIT
 APPLICATION.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-08-25 Cont ID  
Sent By kstevens Date 2001-08-25 Time 09:36 Rev Time 0.00
Received By kstevens Date 2001-08-25 Time 09:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2001-08-27 Cont ID  
Sent By lsmith Date 2001-08-27 Time 11:05 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***