Plan Review Details - Permit 01080159
Plan Review Stops For Permit 01080159
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-09-25 Cont ID  
Sent By lmartine Date 2001-09-25 Time 16:21 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-09-25 00:00:00PROVISO
 -------
  
 BUILDING INSPECTOR TO DO PRE-INSPECTION
 WITH OWNER TO VERIFY SCOPE OF WORK CAN
 BE DONE WITHOUT DETAILS.
  
 NOTICE OF COMMENCEMENT IS REQUIRED.
  
  
 L. MARTINEZ
 659-8096
 #8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-09-21 Cont ID  
Sent By lmartine Date 2001-09-21 Time 13:22 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2001-09-21 00:00:00 
 PROVISO
 -------
  
 NO INFORMATION PROVIDED WITH DRAWINGS.
 AREA INSPECTOR TO APPROVE SCOPE OF WORK
 WITHOUT DETAILS. [PRE-INSPECTION]
  
 L. MARTINEZ
 659-8096
 #8456

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-02-28 Cont ID  
Sent By dpalmer Date 2002-02-28 Time 07:30 Rev Time 0.00
Received By dpalmer Date 2002-02-28 Time 07:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2002-02-11 Cont ID  
Sent By dpalmer Date 2002-02-11 Time 08:45 Rev Time 0.00
Received By dpalmer Date 2002-02-11 Time 08:45 Sent To  
Notes
2002-02-11 00:00:00**************** UNSAT ***************
  
 PLEASE NOTE AS ASKED FOR ON PREVIOUS
 REVIEWS. IF THEREARE ANY QUESTIONS,
 PLEASE CALL.
  
 1)NOTE: PLEASE NOTE ANOTHER NEW RISER
 DIAGRAM WAS SUBMITTED FOR REVIEW.
 NOW PLANS ARE SHOWING FOUR MAIN MEANS
 OF DISCONNECT??
 PLEASE CLARIFY TWO MAIN DISCONNECTS AND
 THEN TWO MAIN BREAKERS? AND THEN TO THE
 TWO PANELS.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 AIC RATING SHOWN FOR BRKRS ONLY?
 NOTHING SUBMITTED FOR MAINS.
  
 3)NOTE: PLEASE NOTE NO EQUIPMENT
 GROUNDING SHOWN BETWEEN MAINS AND
 PANELS 250-122.
  
 PLEASE NOTE THAT ELECTRICAL RISER IS
 SHOWING 2/0 WIRE FROM GUTTER TO 100A
 PANELS. PLEASE NOTE THAT THIS IS OVER-
 SIZED, WHICH IS OK, BUT IF 2/0 IS SHOWN
 ON PLAN THEN THATS WHAT WILL BE REQ`D
 TO BE INSTALLED. PLEASE NOTE THAT PER
 310-16, #3 IS OK FOR 100AMPS. PLEASE
 NOTE THAT SOMETIMES A 2/0 WILL NOT FIT
 IN 100A BRKRS/ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-01-08 Cont ID  
Sent By dpalmer Date 2002-01-08 Time 05:25 Rev Time 0.00
Received By dpalmer Date 2002-01-08 Time 05:25 Sent To  
Notes
2002-01-08 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT SAME PLANS
 WERE RE-SUBMITTED FOR PLAN REVIEW WITH
 NO CHANGES OR CORRECTIONS MADE>??
 PLEASE CALL, IF THERE ARE ANY QUESTIONS,
 OR IF AN APPOINTMENT TO GO OVER COMMENTS
 IS NEEDED.
  
 PLEASE SEE COMMENTS FROM TWO PREVIOUS
 REVIEW ATTACHED AND SUBMIT INFORMATION
 FOR REVIEW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-12-24 Cont ID  
Sent By dpalmer Date 2001-12-24 Time 07:07 Rev Time 0.00
Received By dpalmer Date 2001-12-10 Time 17:01 Sent To P
Notes
2001-12-24 00:00:00****************** UNSAT ***********
  
 PLEASE NOTE NOT ALL NOTES FROM FIRST
 REVIEW WERE ADDRESSED.
  
 1)NOTE: PLEASE NOTE THAT NOW A COMPLETE-
 -LY NEW RSIER DIAGRAM IS BEING SUBMITTED
 AND THERE ARE NEW COMMENTS FOR THAT.
  
 A) PLEASE NOTE THAT NO AIC RATINGS WERE
 SUBMITTED FOR ANY OF THE NEWM EQUIPMENT
 SHOWN. 110-9 / 215-5
  
 B)NOTE: PLEASE NOTE THAT THERE IS NO
 GROUNDING SYSTEM SHOWN AT DETACHED BLDG
 PER 250-32.
  
 C) PLEASE NOTE THAT NO EQUIPMENT GROUND-
 -ING CONDUCTORS ARE SHOWN FROM MAIN
 PANEL TO EITHER, HOUSE PANEL OR COTTAGE
 250-122.
  
 D) PLEASE NOTE THEREIS NO INDICATION
 ON COTTAGE PANEL IF THERE IS A MAIN
 BRKR? PLEASE SHOW 225-31
  
 E) PLEASE NOTE THAT THERE IS NO PANEL
 SCHEDULE FOR MAIN PANEL, PLEASE SHOW
 WITH THE SIZE OF OCP GOING TO EACH PANEL
 PLEASE CLARIFY, IF THERE IS 100 OCP,
 PLEASE NOTE 2/0 CONDUCTORS GOING TO A
 100 BRKR. PLEASENOTE IF THEY'LL FIT?
 PLEASE NOTE PER 310-16 #3 IS ALL THAT
 IS REQ`D FOR 100A`S.
  
 F) PLEASE NOTE THAT NO MIN LAUNDRY
 CIRCUIT IS SHOWN. 210-52 F.
  
 2)NOTE: PLEASE NOTE THAT OUTLET SPACING
 NEEDS TO MEET 210-52.CHIEF BLDG INSPECT-
 -OR HAS NOTED HOUSE IS BEING COMPLETETLY
 RE-DONE.
  
 3) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
  
 4)NOTE: PLEASE NOTE THAT THERE IS A NEW
 SHEET 1 ATTACHED AND SHOWS LOCATION OF
 METER AT DETACHED BLDG? PLEASE NOTE THAT
 LOCATION OF SERVICE NEEDS TO BE CLARIFIE
 -D.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-09-27 Cont ID  
Sent By dpalmer Date 2001-09-27 Time 08:07 Rev Time 0.00
Received By dpalmer Date 2001-09-27 Time 08:07 Sent To  
Notes
2001-09-27 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT REAR APT/
 IS NOT ALLOWED BY ZONING.
  
 2)NOTE: PLEASE NOTE THAT IF ALLOWED TO
 BE GARAGE/APT THE SERVICES WOULD STILL
 HAVE TO BE GROUPED ON ONE BLDG WITH
 MAINS GROUPED AND THEN SUB FEEDING
 DETACHED BLDG, WHEATHER SERVICE IS ON
 MAIN HOUSE OR APT.230-2/230-72
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4) NOTE: PLEASE SHOW ALL OUTLETS
 SERVINGKITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210-8-A-6.
  
 5)NOTE: PLEASE NOTE THAT MAIN HOUSE
 KITCHEN COUNTERSPACE IS NOT
 SHOWN,PLEASESHOW AND SHOW OUTLET
 SPACING TO MEET 210-52 C
  
 6) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 7)NOTE: PLEASE NOTE THAT OVERHEAD
 SERVICE IS SHOWN WITH A 10' MIN CLEARENC
 E FROM GROUND TO THE TOP OF THE WEATHER
 HEAD. PLEASE NOTE THAT THE CLEARENCE
 IS FROM THE GROUND TO THE BOTTOM OF THE
 DRIP LOOP. 230-24
  
 8)NOTE: PLEASE SHOW LOAD CALCULATIONS TO
 MEET ART 220.
  
 9)NOTE: PLEASE INDICATE MCB FOR PANEL(S)
 OR MAIN DISC WHEN GOING WITH SERVICE ON
 ONE BLDG.,
  
 10)NOTE: PLEASE NOTE THAT ALL GEN LT
 PER PANEL SCHEDULE SHOW #14, 15A, PLEASE
 NOTE THAT DING ROOMTO BE #12,20A PER
 210-52
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-09-27 Cont ID  
Sent By pkrauss Date 2001-09-27 Time 13:43 Rev Time 0.40
Received By pkrauss Date 2001-09-27 Time 13:43 Sent To  
Notes
2001-09-27 00:00:00PROVISO ON PLAN.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-09-29 Cont ID  
Sent By dpalmer Date 2001-12-24 Time 08:54 Rev Time 0.33
Received By jleech Date 2001-09-29 Time 11:16 Sent To  
Notes
2001-09-29 00:00:00PROVISO; FIXTURE CHANGE OUT ONLY.

Review Stop Z ZONING
Rev No 2 Status P Date 2001-12-05 Cont ID  
Sent By sgraham Date 2001-12-05 Time 15:38 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2001-09-27 Cont ID  
Sent By sgraham Date 2001-09-27 Time 07:13 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-09-27 00:00:00THIS BLDG WAS BUILT AS A GAR-APT, THE
 BLDG MUST HAVE A GARAGE TO PARK A CAR.
 A PORTION OF THE BLDG WAS CONVERTEDTO
 MORE LIVING SPACE.IT MUST BE CONVERTED
 BACK TO A GARAGE.
  
  
  
  
  
  
  
  
  
 A