| Plan Review Stops For Permit 01080159 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-09-25 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-09-25 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-25 00:00:00 | PROVISO | | | ------- | | | | | | BUILDING INSPECTOR TO DO PRE-INSPECTION | | | WITH OWNER TO VERIFY SCOPE OF WORK CAN | | | BE DONE WITHOUT DETAILS. | | | | | | NOTICE OF COMMENCEMENT IS REQUIRED. | | | | | | | | | L. MARTINEZ | | | 659-8096 | | | #8456 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2001-09-21 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-09-21 |
Time |
13:22 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-21 00:00:00 | | | | PROVISO | | | ------- | | | | | | NO INFORMATION PROVIDED WITH DRAWINGS. | | | AREA INSPECTOR TO APPROVE SCOPE OF WORK | | | WITHOUT DETAILS. [PRE-INSPECTION] | | | | | | L. MARTINEZ | | | 659-8096 | | | #8456 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2002-02-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-02-28 |
Time |
07:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-02-28 |
Time |
07:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2002-02-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-02-11 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-02-11 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2002-02-11 00:00:00 | **************** UNSAT *************** | | | | | | PLEASE NOTE AS ASKED FOR ON PREVIOUS | | | REVIEWS. IF THEREARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | 1)NOTE: PLEASE NOTE ANOTHER NEW RISER | | | DIAGRAM WAS SUBMITTED FOR REVIEW. | | | NOW PLANS ARE SHOWING FOUR MAIN MEANS | | | OF DISCONNECT?? | | | PLEASE CLARIFY TWO MAIN DISCONNECTS AND | | | THEN TWO MAIN BREAKERS? AND THEN TO THE | | | TWO PANELS. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | AIC RATING SHOWN FOR BRKRS ONLY? | | | NOTHING SUBMITTED FOR MAINS. | | | | | | 3)NOTE: PLEASE NOTE NO EQUIPMENT | | | GROUNDING SHOWN BETWEEN MAINS AND | | | PANELS 250-122. | | | | | | PLEASE NOTE THAT ELECTRICAL RISER IS | | | SHOWING 2/0 WIRE FROM GUTTER TO 100A | | | PANELS. PLEASE NOTE THAT THIS IS OVER- | | | SIZED, WHICH IS OK, BUT IF 2/0 IS SHOWN | | | ON PLAN THEN THATS WHAT WILL BE REQ`D | | | TO BE INSTALLED. PLEASE NOTE THAT PER | | | 310-16, #3 IS OK FOR 100AMPS. PLEASE | | | NOTE THAT SOMETIMES A 2/0 WILL NOT FIT | | | IN 100A BRKRS/ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | | REVIEW. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2002-01-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-01-08 |
Time |
05:25 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-01-08 |
Time |
05:25 |
Sent To |
|
|
| Notes |
| 2002-01-08 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT SAME PLANS | | | WERE RE-SUBMITTED FOR PLAN REVIEW WITH | | | NO CHANGES OR CORRECTIONS MADE>?? | | | PLEASE CALL, IF THERE ARE ANY QUESTIONS, | | | OR IF AN APPOINTMENT TO GO OVER COMMENTS | | | IS NEEDED. | | | | | | PLEASE SEE COMMENTS FROM TWO PREVIOUS | | | REVIEW ATTACHED AND SUBMIT INFORMATION | | | FOR REVIEW. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-12-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-24 |
Time |
07:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-10 |
Time |
17:01 |
Sent To |
P |
|
| Notes |
| 2001-12-24 00:00:00 | ****************** UNSAT *********** | | | | | | PLEASE NOTE NOT ALL NOTES FROM FIRST | | | REVIEW WERE ADDRESSED. | | | | | | 1)NOTE: PLEASE NOTE THAT NOW A COMPLETE- | | | -LY NEW RSIER DIAGRAM IS BEING SUBMITTED | | | AND THERE ARE NEW COMMENTS FOR THAT. | | | | | | A) PLEASE NOTE THAT NO AIC RATINGS WERE | | | SUBMITTED FOR ANY OF THE NEWM EQUIPMENT | | | SHOWN. 110-9 / 215-5 | | | | | | B)NOTE: PLEASE NOTE THAT THERE IS NO | | | GROUNDING SYSTEM SHOWN AT DETACHED BLDG | | | PER 250-32. | | | | | | C) PLEASE NOTE THAT NO EQUIPMENT GROUND- | | | -ING CONDUCTORS ARE SHOWN FROM MAIN | | | PANEL TO EITHER, HOUSE PANEL OR COTTAGE | | | 250-122. | | | | | | D) PLEASE NOTE THEREIS NO INDICATION | | | ON COTTAGE PANEL IF THERE IS A MAIN | | | BRKR? PLEASE SHOW 225-31 | | | | | | E) PLEASE NOTE THAT THERE IS NO PANEL | | | SCHEDULE FOR MAIN PANEL, PLEASE SHOW | | | WITH THE SIZE OF OCP GOING TO EACH PANEL | | | PLEASE CLARIFY, IF THERE IS 100 OCP, | | | PLEASE NOTE 2/0 CONDUCTORS GOING TO A | | | 100 BRKR. PLEASENOTE IF THEY'LL FIT? | | | PLEASE NOTE PER 310-16 #3 IS ALL THAT | | | IS REQ`D FOR 100A`S. | | | | | | F) PLEASE NOTE THAT NO MIN LAUNDRY | | | CIRCUIT IS SHOWN. 210-52 F. | | | | | | 2)NOTE: PLEASE NOTE THAT OUTLET SPACING | | | NEEDS TO MEET 210-52.CHIEF BLDG INSPECT- | | | -OR HAS NOTED HOUSE IS BEING COMPLETETLY | | | RE-DONE. | | | | | | 3) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | | | | 4)NOTE: PLEASE NOTE THAT THERE IS A NEW | | | SHEET 1 ATTACHED AND SHOWS LOCATION OF | | | METER AT DETACHED BLDG? PLEASE NOTE THAT | | | LOCATION OF SERVICE NEEDS TO BE CLARIFIE | | | -D. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-09-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-09-27 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-09-27 |
Time |
08:07 |
Sent To |
|
|
| Notes |
| 2001-09-27 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT REAR APT/ | | | IS NOT ALLOWED BY ZONING. | | | | | | 2)NOTE: PLEASE NOTE THAT IF ALLOWED TO | | | BE GARAGE/APT THE SERVICES WOULD STILL | | | HAVE TO BE GROUPED ON ONE BLDG WITH | | | MAINS GROUPED AND THEN SUB FEEDING | | | DETACHED BLDG, WHEATHER SERVICE IS ON | | | MAIN HOUSE OR APT.230-2/230-72 | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 4) NOTE: PLEASE SHOW ALL OUTLETS | | | SERVINGKITCHEN COUNTERSPACE AS GFI/GFI | | | PROTECT--ED PER 210-8-A-6. | | | | | | 5)NOTE: PLEASE NOTE THAT MAIN HOUSE | | | KITCHEN COUNTERSPACE IS NOT | | | SHOWN,PLEASESHOW AND SHOW OUTLET | | | SPACING TO MEET 210-52 C | | | | | | 6) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | | | | 7)NOTE: PLEASE NOTE THAT OVERHEAD | | | SERVICE IS SHOWN WITH A 10' MIN CLEARENC | | | E FROM GROUND TO THE TOP OF THE WEATHER | | | HEAD. PLEASE NOTE THAT THE CLEARENCE | | | IS FROM THE GROUND TO THE BOTTOM OF THE | | | DRIP LOOP. 230-24 | | | | | | 8)NOTE: PLEASE SHOW LOAD CALCULATIONS TO | | | MEET ART 220. | | | | | | 9)NOTE: PLEASE INDICATE MCB FOR PANEL(S) | | | OR MAIN DISC WHEN GOING WITH SERVICE ON | | | ONE BLDG., | | | | | | 10)NOTE: PLEASE NOTE THAT ALL GEN LT | | | PER PANEL SCHEDULE SHOW #14, 15A, PLEASE | | | NOTE THAT DING ROOMTO BE #12,20A PER | | | 210-52 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-09-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-27 |
Time |
13:43 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-09-27 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2001-09-27 00:00:00 | PROVISO ON PLAN. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2001-09-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-24 |
Time |
08:54 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2001-09-29 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2001-09-29 00:00:00 | PROVISO; FIXTURE CHANGE OUT ONLY. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2001-12-05 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-12-05 |
Time |
15:38 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2001-09-27 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-09-27 |
Time |
07:13 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-27 00:00:00 | THIS BLDG WAS BUILT AS A GAR-APT, THE | | | BLDG MUST HAVE A GARAGE TO PARK A CAR. | | | A PORTION OF THE BLDG WAS CONVERTEDTO | | | MORE LIVING SPACE.IT MUST BE CONVERTED | | | BACK TO A GARAGE. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | A |
|
|