Plan Review Details - Permit 01080151
Plan Review Stops For Permit 01080151
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-09-24 Cont ID  
Sent By hpiskura Date 2001-09-24 Time 13:52 Rev Time 0.00
Received By hpiskura Date 2001-09-04 Time 13:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-09-24 Cont ID  
Sent By hpiskura Date 2001-09-24 Time 13:53 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-21 Cont ID  
Sent By dpalmer Date 2001-08-21 Time 17:06 Rev Time 0.00
Received By dpalmer Date 2001-08-21 Time 16:58 Sent To  
Notes
2001-08-21 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT SERVICE IS
 SHOWING TAPPED CONDUCTORS FROM METERCAN
 INTO GUTTER AND THEN TAPPING THE TAP???
 PLEASE NOTE THAT TAPPING A TAPPED
 CONDUCTOR IS NOT PERMITTED UNDER 240-21.
 PLEASE NOTE THATINDIVIDUAL RUNS
 FROM METERCAN TO EACH DISCONNECT IS
 PERMITTED. PLAN ONLY SHOWS ONE SET OF
 CONDUCTORS.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT AIC RATINGS WERE SUB-
 -MITTED FOR PANELS BUT NOT FOR MAIN
 DISCONNECTS. PLEASE SUBMIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-09-07 Cont ID  
Sent By lsmith Date 2001-09-07 Time 12:58 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-08-06 Cont ID  
Sent By mcarsill Date 2001-08-06 Time 14:09 Rev Time 0.00
Received By mcarsill Date 2001-08-06 Time 14:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-09-24 Cont ID  
Sent By hpiskura Date 2001-09-24 Time 13:52 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-09-24 Cont ID  
Sent By hpiskura Date 2001-09-24 Time 13:52 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2001-09-07 Cont ID  
Sent By lsmith Date 2001-09-07 Time 12:58 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***