Plan Review Details - Permit 01080143
Plan Review Stops For Permit 01080143
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2002-08-15 Cont ID  
Sent By jwitmer Date 2002-08-15 Time 06:45 Rev Time 0.75
Received By jwitmer Date 2002-08-15 Time 06:45 Sent To  
Notes
2002-08-15 00:00:00THIS IS THE SAME COMMENTS AS FROM
 REVIEW 05/28/02 PRODUCT APPROVALS:
 PROVISO:
 1) COMMERCIAL PASS THROUGH : REQUIRES
 HURRICANE PROTECTION!!!!!!
 NO ADDITIONAL INFORMATION SUBMITTED
 FOR LARGE MISSLE IMPACT RESISTANCE,
 NO STORM SHUTTER INFORMATION!!!!!
  
 JIM WITMER
 PLAN REVIEW
 (561) 659-8096 X8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2002-05-28 Cont ID  
Sent By jwitmer Date 2002-05-28 Time 14:50 Rev Time 0.00
Received By jwitmer Date 2002-05-28 Time 06:38 Sent To  
Notes
2002-05-28 00:00:00PRODUCT APPROVALS:
 1) "PROVISO" COMMERCIAL PASS THROUGH;
 REQUIRES HURRICANE PROTECTION SYSTEM
 2) 3000 SERIES ARCH ALUM DOOR: WILL NOT
 REQUIRE HURRICANE PROTECTION SYSTEM
 3) 3000 SERIES ARCH FIXED WINDOWS: WILL
 NOT REQUIRE HURRICANE PROTECTION
 SYSEM
 4) GAF RUBEROID MODIFIED BITUMEN FOR
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412
 EL

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-05-16 Cont ID  
Sent By jwitmer Date 2002-05-16 Time 15:15 Rev Time 0.00
Received By jwitmer Date 2002-05-16 Time 06:38 Sent To  
Notes
2002-05-16 00:00:00DENSITY REPORT

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-04-04 Cont ID  
Sent By jwitmer Date 2002-04-04 Time 09:48 Rev Time 0.00
Received By jwitmer Date 2002-04-04 Time 06:37 Sent To  
Notes
2002-04-04 00:00:00*****BUILDING PROVISO*****
 PERMIT # 01080143
 2031 PALM BEACH LAKES BLVD
 "KRISPY KREME"
  
 1) SHEET A15 DETAILS 12 & 13 AWNING
 ANCHORING DETAIL, INDICATES PER AWNING
 MAN., THE AWNING MAN. SHALL PROVIDE
 SUFFICIENT INFORMATION TO THEENGINEER
 OF RECORD AS TO COMPLIANCE WITH THERE
 PRODUCT BEING INSTALLED IN A 110 MPH
 WIND ZONE. ENGINNER OF RECORD TO REVIEW
 AND APPROVE INSTALLATION BY AN AFFIXED
 SIGNED & SEALED AFFIDAVIT.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-12-10 Cont ID  
Sent By jwitmer Date 2001-12-10 Time 08:19 Rev Time 0.00
Received By jwitmer Date 2001-12-10 Time 06:37 Sent To  
Notes
2001-12-10 00:00:00PROVISO: COUNTY IMPACT FEES TO BE
 PAID. 12/10/01JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-10-22 Cont ID  
Sent By jwitmer Date 2001-10-22 Time 09:25 Rev Time 3.00
Received By jwitmer Date 2001-10-22 Time 07:00 Sent To  
Notes
2001-10-22 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01080143
 2031 PALM BEACH LAKES
 KRISP KREME
 "2ND PLAN REVIEW"
 CONT PER: RICHARD SIDES
 TEL: (336) 725-2981
 FAX: (336) 733-3798
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 **** PLANS ARE BEING REVIEWED UNDER THE
 1997 STANDARD BUILDING CODE, IF APPLICA-
 TION FOR PERMIT HAS NOT BEEN MADE BEFORE
 DECEMBER 31,2001 THE PLANS WILL BE
 REVIEWED UNDER THE 2001 FLORIDA BUILDING
 CODE.****
  
 1)- THIS BUILDING WILL BE LOCATED IN THE
 FIRE FISTRICT, TYPE VI BUILDINGS ARE NOT
 ALLOWED IN A FIRE DISRICT.
 SBC 607 TYPE V BUILDING: EXTERIOR
 WALLS BEARING & NONBEARING ARE OF NON-
 COMBUSTIBLE MATERIALS.
 BY DEFINITION EXTERIOR WALLS,A WALL,
 BEARING OR NON BEARING WHICH IS USED AS
 AN ENCLOSING WALL FOR A BUILDING, OTHER
 THAN A PARTY WALL OR FIRE WALL.
 SHEET A-6 DETAIL#3 INDICATES COMBUST
 IBLE ELEMENTS WITHIN THE EXTERIOR WALL,
 (OSB BOARD, 2X6 FURRING & EFIS SYSTEM).
 EFIS SYSTEMS PROVIDE PRODUCT TESTING
 REPORT MEETING THE REQUIREMENTS OF
 NONCOMBUSTIBLE BUILDING MATERIAL,AS SET
 FORTH IN ASTM E 136.
  
 2)- SBC 1606.2.6.2 A SKETCH SHOWING THE
 VARIOUS WIND PRESSURE ZONES FOR WALLS,
 ROOF AND END ZONES.
  
 3)- 1606.4.1/ 1707.4.1* SBC. THE CITY
 CODE INTERPRETATION FOR LARGE MISSLE
 HURRICANE RESISTANT GLAZING OR STORM
 SHUTTERS. SEE CITY INTERPRETATION,
 FOR STORM SHUTTERS A INSTALATION SCHED-
 ULE & KEY PLAN WILL BE REQUIRED.
 THE CITY ACCEPTS PRODUCT TESTING
 REPORTS FROM S.B.C.C.I. OR DADE COUNTY
 PRODUCT APPROVAL REPORTS.(2 COPIES)
  
 4)- ROOF ASSEMBLIES SBC 1503.3.2.
 SHOW PRODUCT ACCEPTANCE FOR 110 MPH WIND
 ZONE. SBCCI OR DADE COUNTY REPORT,
 2 COPIES.
  
 5)- SBC: F102.2.4. ROOF COVERINGS IN A
 FIRE DISTRICT SHALL CONFORM TO THE
 REQUIREMENTS OF A CLASS A OR B ROOF.
 PROVIDE MANUFACTURES SPECIFICATION.
  
 6)- DOOR 115A SWING DOOR & DOOR 115
 OVERHEAD ARE MISSING PRODUCT APPROVAL
 REPORTS.SBC 1606.2.6.2.
  
 7)- PLANS ARE TO HAVE COUNTY IMPACT FEE
 STAMP BEFORE THE ISSUANCE OF PERMIT.
 CONTTRACTOR RESPONSIBLIITY.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-09-05 Cont ID  
Sent By hpiskura Date 2001-09-05 Time 08:24 Rev Time 0.00
Received By mamini Date 2001-10-04 Time 08:35 Sent To  
Notes
2001-09-05 00:00:00THIS BUILDING WILL BE LOCATED IN THE
 DESIGNATED FIRE DISTRICT AND TYPE VI
 CONSTRUCTION (WOOD FRAME) IS NOT
 ALLOWED.SEE SBC F102.1.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PERMIT PLANS STAMPED
 BY THAT OFFICE AND A COPY OF THE
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 A SITE PLAN AND SURVEY WERE NOT INCLUDED
 SO A COMPLETE PLAN REVIEW WAS NOT
 POSSIBLE.
  
 SHEET S2CALLS OUT A WIND UPLIFT THE
 ROOF TRUSSES OF 90 MPH.THE DESIGNER
 OF RECORD SHOULD INDICATE THE LOCATION,
 DIRECTION, MAGNITUDE AND NATURE OF THE
 FORCES TO BE RESISTED WHEN DELEGATING
 DESIGN TO A SPECIALTY ENGINEER. INCLUDED
 COMPLETE STRUCTURAL CALCULATIONS WITH
 THE PERMIT APPLICATION.SEE SBC 104.2.
  
  
 THE CITY CURRENTLY INVOKES THE 1997
 STANDARD BUILDING CODE WHICH IS NOT
 INDICATED ON SHEET T1.ALSO INDICATE
 THE EDITIONS OF THE DESIGN STANDARDS
 USED.SEE SBC 3502.
  
 SHOW HOW THE GLAZED PORTIONS OF THE
 BUILDING WILL RESIST HURRICANE MISSILE
 IMPACT.SEE THE ATTACHED "CODE
 INTERPRETATION"
  
 AT TIME OF PERMIT APPLICATION PROVIDE
 COPIES OF TEST REPORTS FROM A
 RECOGNIZED EVALUATION SERVICE OR
 METRO-DADE NOTICE OF ACCEPTANCE REPORTS
 FOR THE DOORS, WINDOWS AND ROOF
 COVERING.
  
 AT TIME OF PERMIT APPLICATION LINCLUDE A
 SKETCH OF THE BUILDING SHOWING THE WIND
 PRESSURE ZONES.SEE SBC 1606.2.6.2
 ANDSBC 1606.3.
  
 PROVIDE A SEATING PLAN, SEE SBC
 1003.1.2.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-07-15 Cont ID  
Sent By dpalmer Date 2002-07-15 Time 09:37 Rev Time 0.00
Received By dpalmer Date 2002-07-15 Time 09:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2002-06-26 Cont ID  
Sent By dpalmer Date 2002-06-26 Time 06:27 Rev Time 0.00
Received By dpalmer Date 2002-06-26 Time 06:27 Sent To  
Notes
2002-06-26 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE GROUNDING ELECTRODE
 SYSTEM HAS BEEN REVISED AND IS MISSING
 BLDG/FOOTER STEEL. PER 250-50. PLEASE
 NOTE THIS WAS ON FIRST SET OF PLANS AND
 WAS AVAILABLE AT TIME OF CONSTRUCTION!!
  
 2)NOTE: PLEASE ALSO NOTE THAT SHEET E-6
 IS NOT SIGNED,DATED OR SEALED ON EITHER
 SET. REQ`D PER FS/FAC 61G15-23.002, 471.
 .025.
  
 PLEASE SUBMIT THE ABOVE REVISED PLANS
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-03-15 Cont ID  
Sent By dpalmer Date 2002-03-15 Time 06:19 Rev Time 0.00
Received By dpalmer Date 2002-03-15 Time 06:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-10 Cont ID  
Sent By dpalmer Date 2001-10-10 Time 20:10 Rev Time 0.00
Received By dpalmer Date 2001-10-10 Time 20:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-22 Cont ID  
Sent By dpalmer Date 2001-08-22 Time 15:49 Rev Time 0.00
Received By dpalmer Date 2001-08-22 Time 15:49 Sent To  
Notes
2001-08-22 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE NOTE THAT NO LOAD
 CALCULATIONS WERE SUBMITTED FOR REVIEW.
 PLEASE SUBMIT. 215-5
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
  
 4) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
  
 5)NOTE: PLEASE NOTE THAT OUTLET SPACING
 IS TO MEET LOCAL CODE 210-50. EVERY 20`
 OF WALL SPACE SEATING/LOBBY, HALL,
 BREAK ROOM.
  
 6)NOTE: PLEASE NOTE OUTLET SPACING FOR
 SHOW WINDOWS PER 210-62
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2001-11-28 Cont ID  
Sent By mamini Date 2001-11-28 Time 08:08 Rev Time 2.00
Received By mamini Date 2001-11-28 Time 08:08 Sent To  
Notes
2001-11-28 00:00:00PASSED :
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 FOR UNDERGROUND/SITE WORKS AT THE TIME
 OF ACTUAL PERMITTING WILL BE REQUIRED.
 2. PLEASE CONTACT RODNEY COMPO,837-4051
 EXT. 4074 FOR INSTALLATIONS / INSPECTION
 OF GREASE/WATER SEPARATOR.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2001-10-15 Cont ID  
Sent By mamini Date 2001-10-15 Time 14:58 Rev Time 3.00
Received By mamini Date 2001-10-15 Time 14:58 Sent To  
Notes
2001-10-15 00:00:00FAILED :
 1. PLEASE CALL-OUT THE GREASE/WATER
 SEPARATOR AND REFER TO PLUMBING PLAN FOR
 DETAILS, PLUMBING PLAN SHOWS TWO.
 PLEASE CALL RODNEY COMPO 873-4051 EXT.
 4074 FOR QUESTIONS, INSTALLATION AND
 INSPECTIONS.
 2. ANY NEW CONNECTIONS TO CITY SERVICES
 WOULD REQUIRE A SEPARATE PERMIT FROM
 PUBLIC UTILITIES AND ANY WORK WITHIN
 PUBLIC R.O.W ALSO, REQUIRES A PERMIT
 FROM CITY ENGINEER, 659-8040.
 3. SHEET 3 OF 4 " WATER METER DETAILS"
 REFERS TO METER AND METER BOX BY CITY,
 PLEASE BE ADVISE THAT CITY PROVIDES
 METERS ONLY.NOTE 1 REFER TO "K" COPPER
 TUBING OR POLYETHYLENE TUBING, PLRASE
 USE TYPE "K" COPPER TUBING.
 3. PLEASE PROVIDE STOP BARS AND STOP
 SIGNS AT ALL DRIVEWAYS.
 4. PLEASE PROVIDE PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR ENTIRE SITE,
 SIGNED AND SEALED.
 5. WE RECOMMEND A SEPARATE PERMIT
 APPLICATION FOR SITE AND UNDERGROUND
 UTILITIES WORK.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-08-15 Cont ID  
Sent By mamini Date 2001-08-15 Time 14:44 Rev Time 1.00
Received By mamini Date 2001-08-15 Time 14:44 Sent To  
Notes
2001-08-15 00:00:00FAILED:
 1. INSUFFICENT INFORMATION FOR CIVIL
 ENGINEERING REVIEW, PLEASE SUBMIT CIVIL
 PLANS FOR OUR REVIEW AND APPROVAL WHEN
 SAID PLANS ARE COMPLETELY DEVELOPED.
 2. CIVIL PLANS SUBMITTAL SHOULD INCLUDE
 STORM WATER CALCULATIONS, PERVIOUS &
 IMPERVIOUS CALCULATIONS FOR ENTIRE SITE
 AND POLLUTION CONTROL PLANS.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-07-19 Cont ID  
Sent By mcarsill Date 2002-07-19 Time 10:56 Rev Time 0.00
Received By mcarsill Date 2002-07-19 Time 10:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-03-26 Cont ID  
Sent By mcarsill Date 2002-03-26 Time 09:43 Rev Time 0.00
Received By mcarsill Date 2002-03-26 Time 09:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-10-10 Cont ID  
Sent By mcarsill Date 2001-10-10 Time 17:04 Rev Time 0.00
Received By mcarsill Date 2001-10-10 Time 17:04 Sent To  
Notes
2001-10-10 00:00:001) INTERIOR FINISH IN EXITS SHALL BE
 CLASS A OR B ON THE WALLS AND CEILINGS.
 2) COULD NOT LOCATE THE ADDITIONAL
 EMERGENCY LIGHT LOCATED IN INGREDIENT
 ROOM.
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM INSTALLATION.
  
 APPROVED PROVISO:
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-07 Cont ID  
Sent By mcarsill Date 2001-08-07 Time 08:06 Rev Time 0.00
Received By mcarsill Date 2001-08-07 Time 08:06 Sent To  
Notes
2001-08-07 00:00:001) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE HOOD, DUCT, AND EXTINGUISHING
 SYSTEM PLANNED FOR USE.
 3) ELEVATION DRAWINGS DISPLAYS FIRE
 ALARM EQUIPMENT BUT THE BUILDING CODE
 SUMMARY INDICATES THAT NO FIRE ALARM
 SYSTEM WILL BE PRESENT.
 4) ANOTHER EMERGENCY LIGHT FIXTURE
 APPEARS TO BE NEEDED IN THE INGREDIENT
 ROOM.
 5) PRODUCT APPROVALS ARE REQUIRED TO
 BE SUBMITTED FOR THE ONE HOUR FIRE
 SHIELDING WHEN THE HOOD PERMIT IS
 SUBMITTED.
 6) DUCT SMOKE DETECTORS ARE REQUIRED
 IN AIR HANDLING EQUIPMENT OVER 2000 CFM.
 7) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 8) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 9) NO INTERIOR FINISH INFORMATION
 PROVIDED FOR WALLS AND CEILINGS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2002-06-22 Cont ID  
Sent By pkrauss Date 2002-06-22 Time 09:33 Rev Time 0.35
Received By pkrauss Date 2002-06-22 Time 09:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-03-12 Cont ID  
Sent By pkrauss Date 2002-03-12 Time 12:55 Rev Time 0.40
Received By pkrauss Date 2002-03-12 Time 12:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-12-05 Cont ID  
Sent By pkrauss Date 2001-12-05 Time 14:26 Rev Time 0.50
Received By pkrauss Date 2001-12-05 Time 13:58 Sent To  
Notes
2001-12-05 00:00:00 
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION, AND WALK-IN COOLERS.
 PLEASE PROVIDE PLANS AND MANUFACTURER
 SUBMITTAL DATA WITH MECHANICAL PERMIT
 APPLLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-10-13 Cont ID  
Sent By pkrauss Date 2001-10-13 Time 10:54 Rev Time 1.00
Received By pkrauss Date 2001-10-13 Time 10:19 Sent To  
Notes
2001-10-13 00:00:00*******************PROVISO**************
  
  
 CONDENSER UNIT STANDS SHALL BE A MINIMUM
 OF 18" FROM THE ROOF SURFACE TO THE
 BOOTOM OF THE SUPPORT RAIL AS PER THE
 COUNTYWIDE AMENDMENTS 1997 SMC 304.2.5.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION AND WALK-IN COOLERS.
 PLEASE PROVIDE PLANS AND MANUFACTURER
 SUBMITTAL DATA WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS 659-8096 EXT. 8388

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-23 Cont ID  
Sent By pkrauss Date 2001-08-23 Time 10:44 Rev Time 2.20
Received By pkrauss Date 2001-08-23 Time 09:49 Sent To  
Notes
2001-08-23 00:00:00*******************DENIED***************
  
  
 PLAN SHEET P3, BUILDING WASTE WATER -
 CONDENSATE SHALL GO TO STORM DRAIN OR
 APPROVED DRYWELL AS PER AMENDED 1997
 SPC 804.3 #2 & 3.
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89.
  
 ADDITIONAL PLANS AND PERMITS REQUIRED FO
 FOR HOOD, FIRE SUPRESSION AND WALK-IN
 COOLER/FREEZERS.PLEASE PROVIDE PLANS
 AND MANUFACTURER SUBMITTAL DATA WITH
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388

Review Stop P PLUMBING
Rev No 5 Status P Date 2002-07-17 Cont ID  
Sent By kstevens Date 2002-07-17 Time 18:19 Rev Time 0.00
Received By kstevens Date 2002-07-17 Time 18:19 Sent To  
Notes
2002-07-17 00:00:00REVISIONS TO SHTS P-1,P-2,P-3,&P-4 OK

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-04-02 Cont ID  
Sent By kstevens Date 2002-04-02 Time 11:19 Rev Time 0.00
Received By kstevens Date 2002-04-02 Time 11:19 Sent To  
Notes
2002-04-02 00:00:00REVISION OK - CHANGES TO FLOOR PLAN -
 CHANGES TO SANT AND WATER RISER DIAGRAMS

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-12-01 Cont ID  
Sent By kstevens Date 2001-12-01 Time 10:31 Rev Time 1.00
Received By kstevens Date 2001-12-01 Time 10:31 Sent To  
Notes
2001-12-01 00:00:00PASSED - PROVISO
  
 NEW IRRIGATION BACKFLOW SHALL BE IN-
 STALLED BY PLUMBING CONTRACTOR. CIVIL
 PLANS CALL FOR NEW IRRIGATION RPZ BACK-
 FLOW.

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-10-21 Cont ID  
Sent By pschmitz Date 2001-10-21 Time 11:30 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-10-21 00:00:00PLUMBING PLAN REVIEW DENIED, PLEASE
 ADDRESS PREVIOUS NOTES DATED 08-21-01.
 (1) DEPT OF HOTEL BUSINESS REGULATION
 PLAN REVIEW, REQUIRED BEFORE A PLUMBING
 PLAN REVIEW CAN BE COMPLETED.SEC 101.4.7
 (2) SHT P-3,4 GREASE TRAP SIZE, W PALM
 BEACH ENVIROMENTAL COMPLIANCE, CONTACT
 RODNEY COMPO 561-837-4074.
 (8) SHT P2 CONSTRUCTION NOTE #2, LOCAL
 ORDINANCE FOR BACKFLOW PREVTERS #2853-95
 TYPE AND LOCATION, CONTACT 561-659-8000
 EXT 2008. W. PALM BCH WATER DEPT.
 (13) SHT AI, MENS RM #107 URINAL SHALL
 BE SCREENED FOR PRIVACY,SEC 404.3ALSO
 CLEAR FLOOR SPACE, FACBC-97 SEC 4.18.3
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-21 Cont ID  
Sent By kstevens Date 2001-08-21 Time 13:29 Rev Time 0.00
Received By kstevens Date 2001-08-21 Time 13:29 Sent To  
Notes
2001-08-21 00:00:00DENIED
  
 REFERENCES- SPC-94 - SGC-97 - FACBC-97
  
 1) PLANS SHALL BE ROUTED TO DEPT. OF
 BUSINESS REGULATION FOR REVIEW AND APP-
 ROVAL. COUNTY WIDE AMENDMENTS TO SPC
 SEC. 101.4.7.
  
 2) GREASE TRAPS TO BE LOCATED & SIZED BY
 UTILITY DEPT. PLEASE CONTACT RODNEY
 COMPO (561) 837-4074. SEPARATE PERMIT
 FOR GREASE TRAP, PROVIDER TO PULL PERMIT
 APPROVED GREASE TRAP DETAIL (SEE ATTACH-
 ED).
  
 3) PAGE P-1 GENERAL NOTE #9, WATER HAM-
 MER ARRESTORS TO BE LOCATED & SIZED PER
 MANUFACTURES INSTALLATION INSTRUCTIONS.
  
 4) SEARATE PERMIT FOR GAS. SEE ATTACHED
 SHEET FOR GAS PERMIT REQUIREMENTS. ADD-
 RESS ALL SECTIONS IN RED FOR PLAN REVIEW
  
 5) PAGE P-1, CONST. NOTES #5. RESTROOM
 SOIL PIPING TO TIE INTO SANITARY DOWN-
 STREAM OF GREASE TRAP.
  
 6) PAGE P-1, CONST. NOTES #'S 2,3 & 7,
 CONDENSATE FROM A/C NOT ALLOWED TO TIE
 INTO SANITARY. MUST GO TO STORM OR DRY-
 WELL.
  
 7) PAGE P-1, CONST NOTES #'S 4,13 & 14.
 HUB DRAINS NOT ALLOWED. FLOOR SINK REQ-
 UIRED FOR ALL INDIRECT WASTE.
  
 8) PAGE P-2, CONST. NOTES #2. BACKFLOW
 TO BE INSTALLED HORIZONTALLY, MAXIMUM OF
 4'0" OFF FLOOR FOR SERVICING. DRAIN TO
 FLOOR SINK.
  
 8) PAGE P-2, CONST. NOTES #3. WATER
 FILTRATION SYSTEM SHALL BE NSF APPROVED
 PER SPC-94 615.1 & 615.2. SUBMIT MANU-
 FACTURE SPEC./INFORMATION SHEETS.
  
 9) PAGE PME1, GENERAL NOTES #8. ROOF
 DRAINS TO BE INSTALLED BY PLUMBING CON-
 TRACTOR.
  
 10) PAGE PME1, GENERAL NOTES #12. CONDEN
 SATE TO BE RUN TO STORM OR DRYWELL.
  
 11) PAGE SP4, NOTE 3.02 L. AIR CHAMBERS
 TO COMPLY WITH SPC-94 607.8.2 & 607.8.3,
 ACCESSABLE AND RECHARGABLE. MUST MEET
 PDI WH 201 REQUIREMENTS FOR RECHARGING.
  
 12) PAGE A1, EMPLOYEE TOILET RM 119.
 DOOR SHALL NOT OPEN INTO CLEAR FLOOR
 SPACE OR TURNING RADIUS. FACBC-97 4.22.2
  
 13) PAGE A1, RM 107 MEN'S RESTROOM. PER
 SPC-94 TABLE 407 - FOOTNOTE #3, A URNAL
 IS REQUIRED.
  
 14) PLEASE SUBMIT INFORMATION/DETAILS
 FOR ROOF DRAINAGE. COMPLY WITH SPC-94
 SEC. 1108.1, 1108.2. ALSO SEE FIGURE
 1108.4. INCLUDE INFO FOR SECONDARY DRAIN
 AGE PER SPC SEC. 1109.
  
 15) PAGE P2, WATER SUPPLY SYSTEM IS
 LACKING CONTROL VALVES. COMPLY WITH SPC
 SEC. 610.4.1
  
 16) PAGE P2, WATER SUPPLY CONTROL VALVES
 REQUIRED ON BRANCH LINES PER SPC SEC
 610.4.2.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-12-10 Cont ID  
Sent By sgraham Date 2001-12-10 Time 09:52 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***