| Plan Review Stops For Permit 01080143 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2002-08-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-08-15 |
Time |
06:45 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
2002-08-15 |
Time |
06:45 |
Sent To |
|
|
| Notes |
| 2002-08-15 00:00:00 | THIS IS THE SAME COMMENTS AS FROM | | | REVIEW 05/28/02 PRODUCT APPROVALS: | | | PROVISO: | | | 1) COMMERCIAL PASS THROUGH : REQUIRES | | | HURRICANE PROTECTION!!!!!! | | | NO ADDITIONAL INFORMATION SUBMITTED | | | FOR LARGE MISSLE IMPACT RESISTANCE, | | | NO STORM SHUTTER INFORMATION!!!!! | | | | | | JIM WITMER | | | PLAN REVIEW | | | (561) 659-8096 X8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2002-05-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-05-28 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2002-05-28 |
Time |
06:38 |
Sent To |
|
|
| Notes |
| 2002-05-28 00:00:00 | PRODUCT APPROVALS: | | | 1) "PROVISO" COMMERCIAL PASS THROUGH; | | | REQUIRES HURRICANE PROTECTION SYSTEM | | | 2) 3000 SERIES ARCH ALUM DOOR: WILL NOT | | | REQUIRE HURRICANE PROTECTION SYSTEM | | | 3) 3000 SERIES ARCH FIXED WINDOWS: WILL | | | NOT REQUIRE HURRICANE PROTECTION | | | SYSEM | | | 4) GAF RUBEROID MODIFIED BITUMEN FOR | | | ANY QUESTIONS PLEASE CALL, | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | DEPARTMENT OF CONSTRUCTION SERVICES | | | CITY OF WEST PALM BEACH | | | (561) 659-8096 EXT. 8412 | | | EL |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2002-05-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-05-16 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2002-05-16 |
Time |
06:38 |
Sent To |
|
|
| Notes |
| 2002-05-16 00:00:00 | DENSITY REPORT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2002-04-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-04-04 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2002-04-04 |
Time |
06:37 |
Sent To |
|
|
| Notes |
| 2002-04-04 00:00:00 | *****BUILDING PROVISO***** | | | PERMIT # 01080143 | | | 2031 PALM BEACH LAKES BLVD | | | "KRISPY KREME" | | | | | | 1) SHEET A15 DETAILS 12 & 13 AWNING | | | ANCHORING DETAIL, INDICATES PER AWNING | | | MAN., THE AWNING MAN. SHALL PROVIDE | | | SUFFICIENT INFORMATION TO THEENGINEER | | | OF RECORD AS TO COMPLIANCE WITH THERE | | | PRODUCT BEING INSTALLED IN A 110 MPH | | | WIND ZONE. ENGINNER OF RECORD TO REVIEW | | | AND APPROVE INSTALLATION BY AN AFFIXED | | | SIGNED & SEALED AFFIDAVIT. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096X8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-12-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-12-10 |
Time |
08:19 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2001-12-10 |
Time |
06:37 |
Sent To |
|
|
| Notes |
| 2001-12-10 00:00:00 | PROVISO: COUNTY IMPACT FEES TO BE | | | PAID. 12/10/01JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-10-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-10-22 |
Time |
09:25 |
Rev Time |
3.00 |
| Received By |
jwitmer |
Date |
2001-10-22 |
Time |
07:00 |
Sent To |
|
|
| Notes |
| 2001-10-22 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01080143 | | | 2031 PALM BEACH LAKES | | | KRISP KREME | | | "2ND PLAN REVIEW" | | | CONT PER: RICHARD SIDES | | | TEL: (336) 725-2981 | | | FAX: (336) 733-3798 | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | SBC*= AMENDMENTS/ STANDARD BUILDING CODE | | | | | | **** PLANS ARE BEING REVIEWED UNDER THE | | | 1997 STANDARD BUILDING CODE, IF APPLICA- | | | TION FOR PERMIT HAS NOT BEEN MADE BEFORE | | | DECEMBER 31,2001 THE PLANS WILL BE | | | REVIEWED UNDER THE 2001 FLORIDA BUILDING | | | CODE.**** | | | | | | 1)- THIS BUILDING WILL BE LOCATED IN THE | | | FIRE FISTRICT, TYPE VI BUILDINGS ARE NOT | | | ALLOWED IN A FIRE DISRICT. | | | SBC 607 TYPE V BUILDING: EXTERIOR | | | WALLS BEARING & NONBEARING ARE OF NON- | | | COMBUSTIBLE MATERIALS. | | | BY DEFINITION EXTERIOR WALLS,A WALL, | | | BEARING OR NON BEARING WHICH IS USED AS | | | AN ENCLOSING WALL FOR A BUILDING, OTHER | | | THAN A PARTY WALL OR FIRE WALL. | | | SHEET A-6 DETAIL#3 INDICATES COMBUST | | | IBLE ELEMENTS WITHIN THE EXTERIOR WALL, | | | (OSB BOARD, 2X6 FURRING & EFIS SYSTEM). | | | EFIS SYSTEMS PROVIDE PRODUCT TESTING | | | REPORT MEETING THE REQUIREMENTS OF | | | NONCOMBUSTIBLE BUILDING MATERIAL,AS SET | | | FORTH IN ASTM E 136. | | | | | | 2)- SBC 1606.2.6.2 A SKETCH SHOWING THE | | | VARIOUS WIND PRESSURE ZONES FOR WALLS, | | | ROOF AND END ZONES. | | | | | | 3)- 1606.4.1/ 1707.4.1* SBC. THE CITY | | | CODE INTERPRETATION FOR LARGE MISSLE | | | HURRICANE RESISTANT GLAZING OR STORM | | | SHUTTERS. SEE CITY INTERPRETATION, | | | FOR STORM SHUTTERS A INSTALATION SCHED- | | | ULE & KEY PLAN WILL BE REQUIRED. | | | THE CITY ACCEPTS PRODUCT TESTING | | | REPORTS FROM S.B.C.C.I. OR DADE COUNTY | | | PRODUCT APPROVAL REPORTS.(2 COPIES) | | | | | | 4)- ROOF ASSEMBLIES SBC 1503.3.2. | | | SHOW PRODUCT ACCEPTANCE FOR 110 MPH WIND | | | ZONE. SBCCI OR DADE COUNTY REPORT, | | | 2 COPIES. | | | | | | 5)- SBC: F102.2.4. ROOF COVERINGS IN A | | | FIRE DISTRICT SHALL CONFORM TO THE | | | REQUIREMENTS OF A CLASS A OR B ROOF. | | | PROVIDE MANUFACTURES SPECIFICATION. | | | | | | 6)- DOOR 115A SWING DOOR & DOOR 115 | | | OVERHEAD ARE MISSING PRODUCT APPROVAL | | | REPORTS.SBC 1606.2.6.2. | | | | | | 7)- PLANS ARE TO HAVE COUNTY IMPACT FEE | | | STAMP BEFORE THE ISSUANCE OF PERMIT. | | | CONTTRACTOR RESPONSIBLIITY. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096X8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-09-05 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-09-05 |
Time |
08:24 |
Rev Time |
0.00 |
| Received By |
mamini |
Date |
2001-10-04 |
Time |
08:35 |
Sent To |
|
|
| Notes |
| 2001-09-05 00:00:00 | THIS BUILDING WILL BE LOCATED IN THE | | | DESIGNATED FIRE DISTRICT AND TYPE VI | | | CONSTRUCTION (WOOD FRAME) IS NOT | | | ALLOWED.SEE SBC F102.1. | | | | | | BEFORE A PERMIT TO CONSTRUCT MAY BE | | | ISSUED IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, THE PERMIT PLANS STAMPED | | | BY THAT OFFICE AND A COPY OF THE | | | RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION.CALL 561-233-5025 FOR | | | MORE INFORMATION. | | | | | | A SITE PLAN AND SURVEY WERE NOT INCLUDED | | | SO A COMPLETE PLAN REVIEW WAS NOT | | | POSSIBLE. | | | | | | SHEET S2CALLS OUT A WIND UPLIFT THE | | | ROOF TRUSSES OF 90 MPH.THE DESIGNER | | | OF RECORD SHOULD INDICATE THE LOCATION, | | | DIRECTION, MAGNITUDE AND NATURE OF THE | | | FORCES TO BE RESISTED WHEN DELEGATING | | | DESIGN TO A SPECIALTY ENGINEER. INCLUDED | | | COMPLETE STRUCTURAL CALCULATIONS WITH | | | THE PERMIT APPLICATION.SEE SBC 104.2. | | | | | | | | | THE CITY CURRENTLY INVOKES THE 1997 | | | STANDARD BUILDING CODE WHICH IS NOT | | | INDICATED ON SHEET T1.ALSO INDICATE | | | THE EDITIONS OF THE DESIGN STANDARDS | | | USED.SEE SBC 3502. | | | | | | SHOW HOW THE GLAZED PORTIONS OF THE | | | BUILDING WILL RESIST HURRICANE MISSILE | | | IMPACT.SEE THE ATTACHED "CODE | | | INTERPRETATION" | | | | | | AT TIME OF PERMIT APPLICATION PROVIDE | | | COPIES OF TEST REPORTS FROM A | | | RECOGNIZED EVALUATION SERVICE OR | | | METRO-DADE NOTICE OF ACCEPTANCE REPORTS | | | FOR THE DOORS, WINDOWS AND ROOF | | | COVERING. | | | | | | AT TIME OF PERMIT APPLICATION LINCLUDE A | | | SKETCH OF THE BUILDING SHOWING THE WIND | | | PRESSURE ZONES.SEE SBC 1606.2.6.2 | | | ANDSBC 1606.3. | | | | | | PROVIDE A SEATING PLAN, SEE SBC | | | 1003.1.2. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2002-07-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-07-15 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-07-15 |
Time |
09:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2002-06-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-06-26 |
Time |
06:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-06-26 |
Time |
06:27 |
Sent To |
|
|
| Notes |
| 2002-06-26 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE GROUNDING ELECTRODE | | | SYSTEM HAS BEEN REVISED AND IS MISSING | | | BLDG/FOOTER STEEL. PER 250-50. PLEASE | | | NOTE THIS WAS ON FIRST SET OF PLANS AND | | | WAS AVAILABLE AT TIME OF CONSTRUCTION!! | | | | | | 2)NOTE: PLEASE ALSO NOTE THAT SHEET E-6 | | | IS NOT SIGNED,DATED OR SEALED ON EITHER | | | SET. REQ`D PER FS/FAC 61G15-23.002, 471. | | | .025. | | | | | | PLEASE SUBMIT THE ABOVE REVISED PLANS | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-03-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-15 |
Time |
06:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-15 |
Time |
06:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-10-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-10 |
Time |
20:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-10 |
Time |
20:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-08-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-22 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-22 |
Time |
15:49 |
Sent To |
|
|
| Notes |
| 2001-08-22 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLEASE NOTE THAT NO LOAD | | | CALCULATIONS WERE SUBMITTED FOR REVIEW. | | | PLEASE SUBMIT. 215-5 | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 3) NOTE: PLEASE SHOW ALL CONTINUOUS AT | | | 125%. (LIGHTING ETC) | | | | | | 4) NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | GOING TO BUILDING STEEL AND COLD WATER | | | PER 250-50. | | | | | | 5)NOTE: PLEASE NOTE THAT OUTLET SPACING | | | IS TO MEET LOCAL CODE 210-50. EVERY 20` | | | OF WALL SPACE SEATING/LOBBY, HALL, | | | BREAK ROOM. | | | | | | 6)NOTE: PLEASE NOTE OUTLET SPACING FOR | | | SHOW WINDOWS PER 210-62 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2001-11-28 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-11-28 |
Time |
08:08 |
Rev Time |
2.00 |
| Received By |
mamini |
Date |
2001-11-28 |
Time |
08:08 |
Sent To |
|
|
| Notes |
| 2001-11-28 00:00:00 | PASSED : | | | 1. PLEASE NOTE THAT A SEPARATE PERMIT | | | FOR UNDERGROUND/SITE WORKS AT THE TIME | | | OF ACTUAL PERMITTING WILL BE REQUIRED. | | | 2. PLEASE CONTACT RODNEY COMPO,837-4051 | | | EXT. 4074 FOR INSTALLATIONS / INSPECTION | | | OF GREASE/WATER SEPARATOR. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2001-10-15 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-10-15 |
Time |
14:58 |
Rev Time |
3.00 |
| Received By |
mamini |
Date |
2001-10-15 |
Time |
14:58 |
Sent To |
|
|
| Notes |
| 2001-10-15 00:00:00 | FAILED : | | | 1. PLEASE CALL-OUT THE GREASE/WATER | | | SEPARATOR AND REFER TO PLUMBING PLAN FOR | | | DETAILS, PLUMBING PLAN SHOWS TWO. | | | PLEASE CALL RODNEY COMPO 873-4051 EXT. | | | 4074 FOR QUESTIONS, INSTALLATION AND | | | INSPECTIONS. | | | 2. ANY NEW CONNECTIONS TO CITY SERVICES | | | WOULD REQUIRE A SEPARATE PERMIT FROM | | | PUBLIC UTILITIES AND ANY WORK WITHIN | | | PUBLIC R.O.W ALSO, REQUIRES A PERMIT | | | FROM CITY ENGINEER, 659-8040. | | | 3. SHEET 3 OF 4 " WATER METER DETAILS" | | | REFERS TO METER AND METER BOX BY CITY, | | | PLEASE BE ADVISE THAT CITY PROVIDES | | | METERS ONLY.NOTE 1 REFER TO "K" COPPER | | | TUBING OR POLYETHYLENE TUBING, PLRASE | | | USE TYPE "K" COPPER TUBING. | | | 3. PLEASE PROVIDE STOP BARS AND STOP | | | SIGNS AT ALL DRIVEWAYS. | | | 4. PLEASE PROVIDE PERVIOUS AND | | | IMPERVIOUS CALCULATIONS FOR ENTIRE SITE, | | | SIGNED AND SEALED. | | | 5. WE RECOMMEND A SEPARATE PERMIT | | | APPLICATION FOR SITE AND UNDERGROUND | | | UTILITIES WORK. | | | | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2001-08-15 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-08-15 |
Time |
14:44 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2001-08-15 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2001-08-15 00:00:00 | FAILED: | | | 1. INSUFFICENT INFORMATION FOR CIVIL | | | ENGINEERING REVIEW, PLEASE SUBMIT CIVIL | | | PLANS FOR OUR REVIEW AND APPROVAL WHEN | | | SAID PLANS ARE COMPLETELY DEVELOPED. | | | 2. CIVIL PLANS SUBMITTAL SHOULD INCLUDE | | | STORM WATER CALCULATIONS, PERVIOUS & | | | IMPERVIOUS CALCULATIONS FOR ENTIRE SITE | | | AND POLLUTION CONTROL PLANS. | | | | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2002-07-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-07-19 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-07-19 |
Time |
10:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2002-03-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-03-26 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-03-26 |
Time |
09:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-10-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-10 |
Time |
17:04 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-10 |
Time |
17:04 |
Sent To |
|
|
| Notes |
| 2001-10-10 00:00:00 | 1) INTERIOR FINISH IN EXITS SHALL BE | | | CLASS A OR B ON THE WALLS AND CEILINGS. | | | 2) COULD NOT LOCATE THE ADDITIONAL | | | EMERGENCY LIGHT LOCATED IN INGREDIENT | | | ROOM. | | | 3) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM SYSTEM INSTALLATION. | | | | | | APPROVED PROVISO: | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-08-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-07 |
Time |
08:06 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-07 |
Time |
08:06 |
Sent To |
|
|
| Notes |
| 2001-08-07 00:00:00 | 1) BUILDING ADDRESS REQUIRED PER CITY | | | CODE 3343-00. | | | 2) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE HOOD, DUCT, AND EXTINGUISHING | | | SYSTEM PLANNED FOR USE. | | | 3) ELEVATION DRAWINGS DISPLAYS FIRE | | | ALARM EQUIPMENT BUT THE BUILDING CODE | | | SUMMARY INDICATES THAT NO FIRE ALARM | | | SYSTEM WILL BE PRESENT. | | | 4) ANOTHER EMERGENCY LIGHT FIXTURE | | | APPEARS TO BE NEEDED IN THE INGREDIENT | | | ROOM. | | | 5) PRODUCT APPROVALS ARE REQUIRED TO | | | BE SUBMITTED FOR THE ONE HOUR FIRE | | | SHIELDING WHEN THE HOOD PERMIT IS | | | SUBMITTED. | | | 6) DUCT SMOKE DETECTORS ARE REQUIRED | | | IN AIR HANDLING EQUIPMENT OVER 2000 CFM. | | | 7) PROVISIONS ARE TO BE MADE FOR AT | | | LEAST TWO HANDICAPPED PERSONS. | | | 8) GAS INSTALLATION TO COMPLY WITH | | | NFPA 54. | | | 9) NO INTERIOR FINISH INFORMATION | | | PROVIDED FOR WALLS AND CEILINGS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2002-06-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-22 |
Time |
09:33 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-06-22 |
Time |
09:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2002-03-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-12 |
Time |
12:55 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-03-12 |
Time |
12:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-12-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-05 |
Time |
14:26 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-12-05 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2001-12-05 00:00:00 | | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPRESSION, AND WALK-IN COOLERS. | | | PLEASE PROVIDE PLANS AND MANUFACTURER | | | SUBMITTAL DATA WITH MECHANICAL PERMIT | | | APPLLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-10-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-13 |
Time |
10:54 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2001-10-13 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2001-10-13 00:00:00 | *******************PROVISO************** | | | | | | | | | CONDENSER UNIT STANDS SHALL BE A MINIMUM | | | OF 18" FROM THE ROOF SURFACE TO THE | | | BOOTOM OF THE SUPPORT RAIL AS PER THE | | | COUNTYWIDE AMENDMENTS 1997 SMC 304.2.5. | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPRESSION AND WALK-IN COOLERS. | | | PLEASE PROVIDE PLANS AND MANUFACTURER | | | SUBMITTAL DATA WITH PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS 659-8096 EXT. 8388 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-08-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-23 |
Time |
10:44 |
Rev Time |
2.20 |
| Received By |
pkrauss |
Date |
2001-08-23 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2001-08-23 00:00:00 | *******************DENIED*************** | | | | | | | | | PLAN SHEET P3, BUILDING WASTE WATER - | | | CONDENSATE SHALL GO TO STORM DRAIN OR | | | APPROVED DRYWELL AS PER AMENDED 1997 | | | SPC 804.3 #2 & 3. | | | | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER ASHRAE 62-89. | | | | | | ADDITIONAL PLANS AND PERMITS REQUIRED FO | | | FOR HOOD, FIRE SUPRESSION AND WALK-IN | | | COOLER/FREEZERS.PLEASE PROVIDE PLANS | | | AND MANUFACTURER SUBMITTAL DATA WITH | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2002-07-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-07-17 |
Time |
18:19 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-07-17 |
Time |
18:19 |
Sent To |
|
|
| Notes |
| 2002-07-17 00:00:00 | REVISIONS TO SHTS P-1,P-2,P-3,&P-4 OK |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2002-04-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-04-02 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-04-02 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2002-04-02 00:00:00 | REVISION OK - CHANGES TO FLOOR PLAN - | | | CHANGES TO SANT AND WATER RISER DIAGRAMS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-12-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-12-01 |
Time |
10:31 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2001-12-01 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2001-12-01 00:00:00 | PASSED - PROVISO | | | | | | NEW IRRIGATION BACKFLOW SHALL BE IN- | | | STALLED BY PLUMBING CONTRACTOR. CIVIL | | | PLANS CALL FOR NEW IRRIGATION RPZ BACK- | | | FLOW. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-10-21 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-10-21 |
Time |
11:30 |
Rev Time |
3.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-21 00:00:00 | PLUMBING PLAN REVIEW DENIED, PLEASE | | | ADDRESS PREVIOUS NOTES DATED 08-21-01. | | | (1) DEPT OF HOTEL BUSINESS REGULATION | | | PLAN REVIEW, REQUIRED BEFORE A PLUMBING | | | PLAN REVIEW CAN BE COMPLETED.SEC 101.4.7 | | | (2) SHT P-3,4 GREASE TRAP SIZE, W PALM | | | BEACH ENVIROMENTAL COMPLIANCE, CONTACT | | | RODNEY COMPO 561-837-4074. | | | (8) SHT P2 CONSTRUCTION NOTE #2, LOCAL | | | ORDINANCE FOR BACKFLOW PREVTERS #2853-95 | | | TYPE AND LOCATION, CONTACT 561-659-8000 | | | EXT 2008. W. PALM BCH WATER DEPT. | | | (13) SHT AI, MENS RM #107 URINAL SHALL | | | BE SCREENED FOR PRIVACY,SEC 404.3ALSO | | | CLEAR FLOOR SPACE, FACBC-97 SEC 4.18.3 | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-08-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-08-21 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2001-08-21 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2001-08-21 00:00:00 | DENIED | | | | | | REFERENCES- SPC-94 - SGC-97 - FACBC-97 | | | | | | 1) PLANS SHALL BE ROUTED TO DEPT. OF | | | BUSINESS REGULATION FOR REVIEW AND APP- | | | ROVAL. COUNTY WIDE AMENDMENTS TO SPC | | | SEC. 101.4.7. | | | | | | 2) GREASE TRAPS TO BE LOCATED & SIZED BY | | | UTILITY DEPT. PLEASE CONTACT RODNEY | | | COMPO (561) 837-4074. SEPARATE PERMIT | | | FOR GREASE TRAP, PROVIDER TO PULL PERMIT | | | APPROVED GREASE TRAP DETAIL (SEE ATTACH- | | | ED). | | | | | | 3) PAGE P-1 GENERAL NOTE #9, WATER HAM- | | | MER ARRESTORS TO BE LOCATED & SIZED PER | | | MANUFACTURES INSTALLATION INSTRUCTIONS. | | | | | | 4) SEARATE PERMIT FOR GAS. SEE ATTACHED | | | SHEET FOR GAS PERMIT REQUIREMENTS. ADD- | | | RESS ALL SECTIONS IN RED FOR PLAN REVIEW | | | | | | 5) PAGE P-1, CONST. NOTES #5. RESTROOM | | | SOIL PIPING TO TIE INTO SANITARY DOWN- | | | STREAM OF GREASE TRAP. | | | | | | 6) PAGE P-1, CONST. NOTES #'S 2,3 & 7, | | | CONDENSATE FROM A/C NOT ALLOWED TO TIE | | | INTO SANITARY. MUST GO TO STORM OR DRY- | | | WELL. | | | | | | 7) PAGE P-1, CONST NOTES #'S 4,13 & 14. | | | HUB DRAINS NOT ALLOWED. FLOOR SINK REQ- | | | UIRED FOR ALL INDIRECT WASTE. | | | | | | 8) PAGE P-2, CONST. NOTES #2. BACKFLOW | | | TO BE INSTALLED HORIZONTALLY, MAXIMUM OF | | | 4'0" OFF FLOOR FOR SERVICING. DRAIN TO | | | FLOOR SINK. | | | | | | 8) PAGE P-2, CONST. NOTES #3. WATER | | | FILTRATION SYSTEM SHALL BE NSF APPROVED | | | PER SPC-94 615.1 & 615.2. SUBMIT MANU- | | | FACTURE SPEC./INFORMATION SHEETS. | | | | | | 9) PAGE PME1, GENERAL NOTES #8. ROOF | | | DRAINS TO BE INSTALLED BY PLUMBING CON- | | | TRACTOR. | | | | | | 10) PAGE PME1, GENERAL NOTES #12. CONDEN | | | SATE TO BE RUN TO STORM OR DRYWELL. | | | | | | 11) PAGE SP4, NOTE 3.02 L. AIR CHAMBERS | | | TO COMPLY WITH SPC-94 607.8.2 & 607.8.3, | | | ACCESSABLE AND RECHARGABLE. MUST MEET | | | PDI WH 201 REQUIREMENTS FOR RECHARGING. | | | | | | 12) PAGE A1, EMPLOYEE TOILET RM 119. | | | DOOR SHALL NOT OPEN INTO CLEAR FLOOR | | | SPACE OR TURNING RADIUS. FACBC-97 4.22.2 | | | | | | 13) PAGE A1, RM 107 MEN'S RESTROOM. PER | | | SPC-94 TABLE 407 - FOOTNOTE #3, A URNAL | | | IS REQUIRED. | | | | | | 14) PLEASE SUBMIT INFORMATION/DETAILS | | | FOR ROOF DRAINAGE. COMPLY WITH SPC-94 | | | SEC. 1108.1, 1108.2. ALSO SEE FIGURE | | | 1108.4. INCLUDE INFO FOR SECONDARY DRAIN | | | AGE PER SPC SEC. 1109. | | | | | | 15) PAGE P2, WATER SUPPLY SYSTEM IS | | | LACKING CONTROL VALVES. COMPLY WITH SPC | | | SEC. 610.4.1 | | | | | | 16) PAGE P2, WATER SUPPLY CONTROL VALVES | | | REQUIRED ON BRANCH LINES PER SPC SEC | | | 610.4.2. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-12-10 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-12-10 |
Time |
09:52 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|