Plan Review Details - Permit 01080132
Plan Review Stops For Permit 01080132
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-09-25 Cont ID  
Sent By mcarsill Date 2001-09-25 Time 08:17 Rev Time 0.00
Received By mcarsill Date 2001-09-25 Time 08:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-09-17 Cont ID  
Sent By mcarsill Date 2001-09-17 Time 11:16 Rev Time 0.00
Received By mcarsill Date 2001-09-17 Time 11:16 Sent To  
Notes
2001-09-17 00:00:001) PRODUCT APPROVAL IS FOR GREASE HOOD
 DUCTS NOT DUCTS USED FOR SPRAYING OF
 FLAMMABLE OR COMBUSTIBLE LIQUIDS.
 DUCT WRAP IS TO COMPLY WITH NFPA 33 NOT
 NFPA 96. THEY ARE TWO DIFFERENT
 STANDARDS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-28 Cont ID  
Sent By mcarsill Date 2001-08-28 Time 14:08 Rev Time 0.00
Received By mcarsill Date 2001-08-28 Time 14:08 Sent To  
Notes
2001-08-28 00:00:001) NO DETAILS PROVIDED FOR ANY FIRE
 SUPPRESSION SYSTEM PLANNED FOR BOOTH.
 A FIRE SUPPRESSION SYSTEM IS REQUIRED.
 SEPARATE PLANS AND PERMITS REQUIRED.
 2) HOW IS SPRAY BOOTH GROUNDED.
 3) MORE DETAILS NEEDED ON FILTER PLANNED
 FOR USE. FILTERS ARE REQUIRED TO COMPLY
 WITH CERTAIN CRITERIA.
 4) NO DETAILS PROVIDED ON FIREWRAP
 MATERIAL NOTED ON DUCT DIAGRAM.
 5) PLEASE CLEARLY NOTE ON THE PLANS
 THAT THE EXHAUST DUCT EXTENDS AT LEAST
 SIX FEET ABOVE THE ROOF.
 6) CLEARLY NOTE THE REQUIRED 3 FEET
 LOCATED FOR AROUND THE SPRAY BOOTH.
 7) WHAT WILL THE SPRAY BOOTH BE USED
 FOR.
 8) ARE THERE ANY FLAMMABLE LIQUID
 CABINETS PLANNED FOR THE AREA.
  
 MIKE CARSILLO, CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-09-25 Cont ID  
Sent By pkrauss Date 2001-09-25 Time 13:01 Rev Time 0.25
Received By pkrauss Date 2001-09-25 Time 13:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-08-28 Cont ID  
Sent By pkrauss Date 2001-08-28 Time 14:47 Rev Time 0.45
Received By pkrauss Date 2001-08-28 Time 14:45 Sent To  
Notes
2001-08-28 00:00:00******************DENIED****************
  
  
 ADDRESS FIRE DEPT COMMENTS.
  
 SHOW COMPLIANCE WITH NFPA 33 CHAPTER 5.
  
 ADDITIONAL PLANS AND PERMIT REQUIRE FOR
 FIRE SUPRESSION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-28 Cont ID  
Sent By pkrauss Date 2001-08-06 Time 09:14 Rev Time 0.45
Received By pkrauss Date 2001-08-06 Time 09:14 Sent To  
Notes
***NONE***