Plan Review Details - Permit 01080132
| Plan Review Stops For Permit 01080132 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-09-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-09-25 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-09-25 |
Time |
08:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-09-17 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-09-17 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-09-17 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2001-09-17 00:00:00 | 1) PRODUCT APPROVAL IS FOR GREASE HOOD | | | DUCTS NOT DUCTS USED FOR SPRAYING OF | | | FLAMMABLE OR COMBUSTIBLE LIQUIDS. | | | DUCT WRAP IS TO COMPLY WITH NFPA 33 NOT | | | NFPA 96. THEY ARE TWO DIFFERENT | | | STANDARDS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-08-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-28 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-28 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2001-08-28 00:00:00 | 1) NO DETAILS PROVIDED FOR ANY FIRE | | | SUPPRESSION SYSTEM PLANNED FOR BOOTH. | | | A FIRE SUPPRESSION SYSTEM IS REQUIRED. | | | SEPARATE PLANS AND PERMITS REQUIRED. | | | 2) HOW IS SPRAY BOOTH GROUNDED. | | | 3) MORE DETAILS NEEDED ON FILTER PLANNED | | | FOR USE. FILTERS ARE REQUIRED TO COMPLY | | | WITH CERTAIN CRITERIA. | | | 4) NO DETAILS PROVIDED ON FIREWRAP | | | MATERIAL NOTED ON DUCT DIAGRAM. | | | 5) PLEASE CLEARLY NOTE ON THE PLANS | | | THAT THE EXHAUST DUCT EXTENDS AT LEAST | | | SIX FEET ABOVE THE ROOF. | | | 6) CLEARLY NOTE THE REQUIRED 3 FEET | | | LOCATED FOR AROUND THE SPRAY BOOTH. | | | 7) WHAT WILL THE SPRAY BOOTH BE USED | | | FOR. | | | 8) ARE THERE ANY FLAMMABLE LIQUID | | | CABINETS PLANNED FOR THE AREA. | | | | | | MIKE CARSILLO, CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-09-25 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-25 |
Time |
13:01 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2001-09-25 |
Time |
13:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-08-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-28 |
Time |
14:47 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-08-28 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2001-08-28 00:00:00 | ******************DENIED**************** | | | | | | | | | ADDRESS FIRE DEPT COMMENTS. | | | | | | SHOW COMPLIANCE WITH NFPA 33 CHAPTER 5. | | | | | | ADDITIONAL PLANS AND PERMIT REQUIRE FOR | | | FIRE SUPRESSION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-08-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-06 |
Time |
09:14 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-08-06 |
Time |
09:14 |
Sent To |
|
|
| Notes |
|
|
|