| Plan Review Stops For Permit 01080116 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2003-10-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-10-28 |
Time |
10:54 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-10-28 |
Time |
10:54 |
Sent To |
|
|
| Notes |
| 2003-10-28 00:00:00 | REDLINED PLANS. | | | TO BE FIELD VERIFIED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2003-08-08 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-27 |
Time |
14:28 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2003-08-07 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2003-08-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE THAT REDLINES FROM | | | ORIG REVIEW TWO YEARS AGO HAVE NOT BEEN | | | CHANGED. PLEASE SEE GROUNDING ELECTRODE | | | SYSTEM STILL REF'S 96 NEC. THIS WAS | | | PERMITTED UNDER THE 99 NEC. PLEASE | | | CHANGE ALLNEC CODE ARTS ACCORD. | | | | | | 2)NOTE: PLEASE SEE 220 FOR MIN KW FOR | | | RANGE. PLEASE ADJUST LOAD CALCULATIONS. | | | | | | 3)NOTE: PLEASE SEE MISSING RECEPTS PER | | | 210-52. SEEMS TO HAVE AN OLD DOORWAY | | | CLOSED UP WHICH BRINGS ON NEXT COMMENT | | | FOR BDEROOM #4. | | | | | | 4)NOTE: PLEASE SEE MISSING SD REQ'D | | | OUTSIDE BEDRM #4 | | | | | | 5)NOTE: PLEASE SEE 210-52C, 1,2,3,4,5 | | | FOR KITCHEN COUNTER RECEPTS. PLEASE | | | SEE PENINSULAR AND SEPARATE SPACES. | | | | | | 6)NOTE: PLEASE SEE 210-8 FOR ALL REQ'D | | | GFI/GFI PROTECTED RECEPTS. GARAGE/ OUT- | | | -SIDE ETC. | | | | | | 7)NOTE: PLEASE SEE 210-70 FOR CONTROL | | | OF EGRESS LIGHTING TO BCAK PORCH AREA. | | | PLEASE SHOW HOW AND WHERE LTS ARE | | | TURNED ON AND OFF??? | | | | | | 8)NOTE: PLEASE SEE RISER DIAGRAM, | | | SHOWS PANEL AS BEING A 8/16 CIRCUIT | | | PANEL AND YET PANEL SCHEDULE SHOWS A | | | 44-45 CIRCUIT PANEL?? PLEASE NOTE, PANEL | | | DO NOT AND ARE NOT MADE W/ MORE THAN | | | 42 CIRCUITS? 384-15 | | | PLEASE SHOW REVISED RISER DIAGRAM AND | | | PLEASE SHOW LOCATION OF SERVICE AND | | | METER ON PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REIVEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2003-07-14 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2003-08-04 |
Time |
13:07 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-07-14 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2003-07-14 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE; PLANS MUST RE-DONE BY THE | | | ENGINEER OF RECORD. PLANS ALSO MUST BE | | | SIGNED DATED AND SEALED BY ENG. | | | PER FS 471.025. | | | | | | 2)NOTE: PLEASE HAVE CORRECTIONS DONE | | | AS ORIG REDLINED IN OCT 2001 | | | | | | PLEASE SUBMIT THE ABOVE INFOMATION FOR | | | REVIEW. IF THERE ARE NAY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-10-09 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-01 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-09 |
Time |
19:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-08-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-23 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-23 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2001-08-23 00:00:00 | ****************** UNSAT ************** | | | | | | 1) NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210-8-A-6. | | | | | | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 3) NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | PLEASE NOTE SOME MISSING LOCATIONS. | | | | | | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | SHOWN FOR PANEL BUT NOT FOR MAIN. | | | | | | 5) PLEASE NOTE MISSING OUTLET FOR A/C | | | EQUIPMENT PER 210-63 OF NEC AND 309.1 | | | MECHANICAL CODE. | | | | | | 6) PLEASE CLARIFY EQUIPMENT GROUNDING | | | METHOD BETWEEN FIRST MEANS OF DISCONNECT | | | AND PANEL(S). EQUIPMENT GROUNDING | | | CONDUCTORS ARE TO BE SIZED BY 250-122. | | | | | | 7)NOTE:PLEASE SHOW GARAGE OUTLET AS | | | GFI. PER 210-8 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE QUESTIONS, PLEASE | | | CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2003-11-12 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-12 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-11-12 |
Time |
14:51 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2003-10-27 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-27 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-10-27 |
Time |
14:28 |
Sent To |
E |
|
| Notes |
| 2003-10-27 00:00:00 | TO DP DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2003-10-27 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-27 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-10-27 |
Time |
14:25 |
Sent To |
P |
|
| Notes |
| 2003-10-27 00:00:00 | TO KS BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-08-04 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2003-08-04 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2003-08-04 |
Time |
13:07 |
Sent To |
E |
|
| Notes |
| 2003-08-04 00:00:00 | TO DP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-07-01 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-01 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-01 |
Time |
16:03 |
Sent To |
E |
|
| Notes |
| 2003-07-01 00:00:00 | DP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-07-01 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-01 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-01 |
Time |
16:02 |
Sent To |
B |
|
| Notes |
| 2003-07-01 00:00:00 | STHYNG DESK, PRODUCT APPROVALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-02-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-11 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2003-02-11 |
Time |
11:56 |
Sent To |
M |
|
| Notes |
| 2003-02-11 00:00:00 | TO MECH INBOX. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2003-02-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-02-14 |
Time |
16:04 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2003-02-14 |
Time |
16:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-10-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-11 |
Time |
11:56 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-10-08 |
Time |
08:12 |
Sent To |
|
|
| Notes |
| 2001-10-08 00:00:00 | PROVISO ON PLAN. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-08-21 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2001-08-21 |
Time |
17:01 |
Rev Time |
0.33 |
| Received By |
hmoser |
Date |
2001-08-21 |
Time |
17:01 |
Sent To |
|
|
| Notes |
| 2001-08-21 00:00:00 | PLAN DENIED | | | #1 10 IN. DUCT IS TO SMALL | | | TO SUPPLY 1144 CFM OFF | | | TRINGAL | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [561]659-8096 EXT.8390 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2003-11-24 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2003-11-24 |
Time |
17:00 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2003-11-24 |
Time |
17:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2003-11-01 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-12 |
Time |
14:51 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-11-01 |
Time |
07:15 |
Sent To |
|
|
| Notes |
| 2003-11-01 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) NEW RISER DIAGRAM DOES NOT REFLECT | | | THE FLOOR PLAN. THE NEW SINK ON THE SANT | | | RISER DIAGRAM SHALL BE SHOWN ON THE | | | FLOOR PLAN. PLEASE SUBMIT A REVISION FOR | | | THE FLOOR PLAN ALSO. SECTION 104.2.1 | | | 2) ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR NAME, ADDRESS, AND LICENSE NUMBER | | | ON EACH SHEET. LICENSE NUMBER NOT SHOWN | | | PLEASE SEE THIS HAS BEEN THE SAME | | | COMMENT ON MANY PREVIOUS REVIEWS. WE ARE | | | NOW RETAINING ONE SET OF PLANS TO BE | | | FILED AND TURNED INTO THE FBPE FOR THIS | | | VIOLATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-11-09 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-27 |
Time |
14:25 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-10-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-12 |
Time |
09:25 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-10-12 |
Time |
09:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-08-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-08-15 |
Time |
18:21 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-08-15 |
Time |
18:21 |
Sent To |
|
|
| Notes |
| 2001-08-15 00:00:00 | DENIED | | | | | | SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS OR REFLECT THE FLOOR | | | PLAN. | | | PLEASE SUBMIT A RISER DIAGRAM THAT RE- | | | FLECTS THE FLOOR PLAN AND MEETS CODE | | | REQUIREMENTS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2001-11-14 |
|
|
Cont ID |
|
| Sent By |
lhatten |
Date |
2001-11-14 |
Time |
18:02 |
Rev Time |
1.00 |
| Received By |
lhatten |
Date |
2001-11-14 |
Time |
18:01 |
Sent To |
|
|
| Notes |
| 2001-11-14 00:00:00 | PLANS OK 11/14/2001 PER LOU HATTEN | | | PLANS OK 11/14/2001 PER LOU HATTEN |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2001-10-26 |
|
|
Cont ID |
|
| Sent By |
lhatten |
Date |
2001-10-26 |
Time |
15:30 |
Rev Time |
1.00 |
| Received By |
lhatten |
Date |
2001-10-26 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2001-10-26 00:00:00 | MISSING WINDOW PRESSURES AND STILL | | | SOME PRODUCT APPR. NOT UP TO DATE | | | 10/26/2001 | | | SAME AS ABOVE 10/26/2001 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2001-09-06 |
|
|
Cont ID |
|
| Sent By |
lhatten |
Date |
2001-09-06 |
Time |
15:26 |
Rev Time |
3.00 |
| Received By |
lhatten |
Date |
2001-09-06 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2001-10-26 00:00:00 | NEED UP TO DATE PRODUCT APPROVALS & | | | WINDOW /DOOR PRESSURES | | | OWNER TO PICK-UP TO FIX PLANS 09/06/2001 | | | OWNER TO PICK-UP AND FIX AND RETURN TO | | | BUILDING DEPT. 09/06/2001 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-08-07 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-08-07 |
Time |
12:12 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|