Plan Review Details - Permit 01080053
Plan Review Stops For Permit 01080053
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-11-26 Cont ID  
Sent By jwitmer Date 2001-11-26 Time 18:35 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2001-11-26 00:00:00REVISION DATED 9/10/01 REVIEWED JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-08-28 Cont ID  
Sent By jwitmer Date 2001-08-28 Time 15:13 Rev Time 2.50
Received By jwitmer Date 2001-08-28 Time 15:13 Sent To  
Notes
2001-08-28 00:00:00COUNTY IMPACT FEES PD WILD OATS 00-18598

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-08-17 Cont ID  
Sent By jwitmer Date 2001-08-17 Time 07:34 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-08-17 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01080053
 375 S ROSEMARY
 "PUBLIX"
  
 NOTE:FIRE DISTRICT
 EXISTING DOORS 1E,2E & 3E ARE HORIZONTAL
 SLIDING DOORS, THEY ARE TO COMPLY WITH
 SBC SEC 1012.4 FOR HORIZONTAL SLIDING
 DOORS.
  
 1)- ENERGY CALCULATIONS?
  
 2)- SBC104.2.2. MEZZANINE FLOOR PLAN,
 WHERE DOES THE DOORS 33-N LEAD TO? WHAT
 STOPS SOMEONE FROM OPENING THESE DOORS
 AND FALLING?
  
 3)- SHEET A-11 DOOR LEADING INTO THE
 MENS RESTROOM REQUIRES 18" ON THE LATCH
 SIDE OF THE DOOR PULL SIDE( FL ACC CODE
 4.13.6)
  
 4)- FL ACC CODE 4.5 GROUD & FLOOR SUR-
 FACES ALONG ACCESSIBLE ROUTES AND IN ACC
 ESSIBLE ROOMS AND SPACES INCLUDING
 FLOORS, WALKS, RAMPS, STAIRS AND CURB
 RAMPS, SHALL BE FIRM, SLIP RESISTANT &
 STABLE.A STATIC COEFFICIENT OF FRICTION
 OF 0.6 IS RECOMMENDED FOR ACCESSIBLE
 ROUTES & 0.8 FOR RAMPS.
  
 5)- SBC 803.3 MISSING IS A MINIMUM INTER
 IOR FINISH CLASSIFICATION SCHEDULE, SEE
 SBC TABLE 803.3. FOR MAX. SMOKE/ FLAME
 SPREAD.
 SBC 903.7.1 AN APPROVED AUTOMATIC SPRINK
 LER SYSTEM SHALL BE PROVIDED IN STORES
 AND SIMILAR OCCUPANCIES WHERE STTOCKS OF
 COMBUSTIBLE MATERIALS ARE ON DISPLAY FOR
 PUBLIC SALE AND WHERE THE STORY FLOOR
 AREA EXCEEDS 15,000 SQ. FT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-11-19 Cont ID  
Sent By dpalmer Date 2001-11-19 Time 19:02 Rev Time 0.00
Received By dpalmer Date 2001-11-19 Time 19:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-08-27 Cont ID  
Sent By dpalmer Date 2001-08-27 Time 09:53 Rev Time 0.00
Received By dpalmer Date 2001-08-27 Time 09:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-14 Cont ID  
Sent By dpalmer Date 2001-08-14 Time 19:34 Rev Time 0.00
Received By dpalmer Date 2001-08-14 Time 19:34 Sent To  
Notes
2001-08-14 00:00:00***************** UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT MEANS OF
 DISCONNECT WILL NEED TO MEET 230-72.
 PLEASE NOTE THAT RISER NOTES SHOWN AS
 #3 ON E-7 MENTIONS SHUNT TRIP FOR MAIN.
 PLEASE NOTE THAT A MANUAL MEANS OF
 DISCONNECT IS REQ`D PER 230-76 AND
 230-79.
  
 2)NOTE: PLEASE NOTE THAT PER NOTE FOR
 LOCATION OF GENERATOR SHUT DOWN,,,
 SHUT DOWN OF GEN. NEEDS TO BE GROUPED
 W/ MAIN.
  
 3)NOTE: PLEASE NOTE PROVIDE
 CLARIFICATION FOR FIRE PUMP AND FIRE
 PUMP FEED?
  
  
 PLEASE PROVIDE THE ABOVE CLARIFICATION
 AND SUBMIT FOR REVIEW. PLEASE NOTE ALL
 FIRE DEPT COMMENTS AS THEY MAY PERTAIN
 TO ELECTRICAL AS WELL. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2001-11-21 Cont ID  
Sent By mcarsill Date 2001-11-21 Time 10:44 Rev Time 0.00
Received By mcarsill Date 2001-11-21 Time 10:44 Sent To  
Notes
2001-11-21 00:00:00COULD NOT FIRE REVISIONS ON THE PLAN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-08-27 Cont ID  
Sent By mcarsill Date 2001-08-27 Time 12:44 Rev Time 0.00
Received By mcarsill Date 2001-08-27 Time 12:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-02 Cont ID  
Sent By mcarsill Date 2001-08-02 Time 18:11 Rev Time 0.00
Received By mcarsill Date 2001-08-02 Time 18:11 Sent To  
Notes
2001-08-02 00:00:001) BUILDING ADDRESS REQUIRED PER CITY
 CODE 3343-00.
 2) EXIT REQUIREMENTS ON PAGE AB-1
 INDICATES 250 FEET TRAVEL DISTANCE
 PERMITTED. THE CURRENT FIRE CODE IS
 MORE RESTRICTIVE AT 150 FEET AND SHOULD
 BE NOTED ON THE PLANS.
 3) VERIFY EXISTING SLIDING DOORS MEET
 THE REQUIREMENTS FOR POWER OPERATED
 DOORS. PLEASE SEE 1985 EDITION OF THE
 LIFE SAFETY CODE SECTION 5-2.1.9.1.
 PLEASE EXPLAIN NOTE ON PLANS 105".
 4) PLEASE BE ADVISED THAT THIS BUILDING
 IS WITHIN THE CITY FIRE LIMITS. CERTAIN
 RESTRICTIONS APPLY TO THIS LOCATION.
 5) VERIFY IF A KNOX-BOX HAS BEEN
 INSTALLED FOR THE SHELL BUILDING.
 6) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 7) PROVIDE SEPARATE PLANS AND PERMITS
 FOR HOOD, DUCT AND EXTINGUISHING
 SYSTEMS.
 8) GAS INSTALLATION TO COMPLY WITH
 NFPA 54 AND SHOULD BE NOTED ON THE
 PLANS.
 9) PLEASE PROVIDE MORE DETAILS ON
 NATURAL GAS GENERATOR PLANNED FOR USE.
 10) KITCHEN EXHAUST DUCT TO BE AT LEAST
 40 INCHES ABOVE THE ROOF.
 11) PLEASE CLEARLY IDENTIFY ALL
 EMERGENCY LIGHT FIXTURE LOCATIONS.
 12) DUCT SMOKE DETECTORS TO CAUSE AIR
 HANDLER SHUT DOWN AND ACTIVATE FIRE
 ALARM SYSTEM.
 13) NO FIRE SPRINKLER SYSTEM DRAWINGS
 PROVIDED.
 14) WRITTEN PERMISSION NEEDED TO MOUNT
 FIRE ALARM SIGNALING DEVICES ON THE
 CEILING NEEDED FROM THIS OFFICE.
 15) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM INSTALLATION. CUT
 SHEETS, WIRING DIAGRAM AND BATTERY
 CALCULATIONS REQUIRED AT TIME OF
 SUBMITTAL.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-08-27 Cont ID  
Sent By pkrauss Date 2001-08-27 Time 16:07 Rev Time 0.40
Received By pkrauss Date 2001-08-27 Time 15:23 Sent To  
Notes
2001-08-27 00:00:00*****************PROVISO****************
  
  
 PRIOR COMMENTS ADDRESSED EXCEPT
 PERMISSIBLE REFRIGERANT QUANTITY,
 BUILDING VOLUME (CALC) SHALL BE THAT OF
 THE MEZZANINE NOT THE ENTIRE BUILDING
 AS PER 1997 SMC 1104.3.1.REPONSE -
 WILL BE ADDRESSED BY HILL PHOENIX DWGS
 TO BE SUBMITTED AT A LATER DATE.
 REFRIGERATION TO BE ON SEPARATE PERMIT.
  
 CALLED CONTRACTOR 8-27-01, LEFT MESSAGE,
 NEED A CONFIRMATION THAT REFRIG. WILL BE
 ON SEPARATE PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-17 Cont ID  
Sent By pkrauss Date 2001-08-16 Time 16:44 Rev Time 3.00
Received By pkrauss Date 2001-08-16 Time 15:29 Sent To  
Notes
2001-08-16 00:00:00********************DENIED**************
  
  
 PLAN SHEET R-1 PERMISSIBLE REFRIGERANT
 QUANTITY, BUILDING VOLLUME SHALL BE
 THAT OF THE MEZZANINE NOT THE ENTIRE
 BUILDING AS PER 1997 SMC 1104.3.1.
  
 PLEASE PROVIDE MANUFACTURER INFORMATION
 ON EMERGENCY GENERATOR.
  
 PLEASE PROVIDE AIR BALANCE SCHEDULE TO
 SHOW COMPLIANCE WITH 1997 SMC 501.2.
  
  
 ADDITIONAL PLANS AND PERMITS REQUIRED
 FOR HOOD, FIRE SUPRESSION AND WALK-IN
 COOLER/FREEZER SUBMIT PLANS AND
 MANUFACTURER SUBMITTAL DATA WITH PERMIT
 APPLICATION.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-11-16 Cont ID  
Sent By kstevens Date 2001-11-16 Time 13:25 Rev Time 0.50
Received By kstevens Date 2001-11-16 Time 13:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-08-25 Cont ID  
Sent By kstevens Date 2001-08-25 Time 09:27 Rev Time 0.00
Received By pschmitz Date 2001-08-25 Time 09:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-17 Cont ID  
Sent By kstevens Date 2001-08-17 Time 15:12 Rev Time 0.00
Received By kstevens Date 2001-08-17 Time 15:12 Sent To  
Notes
2001-08-17 00:00:00DENIED
  
 1) PAGE PM-5, SECTION 15400 # 1.1.1.8,
 HUB DRAINS NOT APPROVED. FLOOR SINKS ARE
 REQUIRED FOR INDIRECT WASTE.
  
 2) PAGE PM-5, SECTION 15400 # 1.1.1.6
 GREASE TRAPS TO BE SIZED AND LOCATED BY
 R. COMPO (561) 837-4074.
  
 3) PAGE PM-5, 3.4.1 HORIZONTAL SANITARY
 PIPE 2" AND SMALLER TO BE GRADED AT 1/4"
 PER FT.
  
 4) PAGE PM-5, 3.5.13, WATER HAMMER ARRES
 TORS TO BE SIZED AND LOCATED PER MANU-
 FACTURES INSTALLATION INSTRUCTIONS.
  
 5) PAGE PM-5, 3.5.14, AIR CHAMBERS TO
 COMPLY WITH SPC-94 607.8.2/607.8.3 PDI-
 WH 201. ACCESSABLE AND RECHARGEABLE.
  
 6) PAGE A-7, VTR UNDER REFRIG. CONDENSER
 STAND TO BE MOVED. (COL LINE C-2)
  
 7) PAGE A-7, ALL VTR TO BE MINIMUM OF 10
 FEET FROM FRESH AIR INTAKES.
  
 8) SEPARATE GAS PERMIT REQUIRED. SEPAR-
 ATE GREASE TRAP REQUIRED. SEPARATE IRR-
 AGATION PERMIT REQUIRED IF NOT INSTALLED
  
 9) PAGE P-1 #14 MECH. SHUT OFF VALVES TO
 BE UPSTREAM FROM UNIONS.
  
 10) 140 DEGREE WATER NOT ALLOWED TO BE
 PIPED TO LAVS, HAND SINKS ECT. ONLY 2, 3
 COMPARTMENT SINKS FOR WASHING DISHES,
 POTS, AND PAN ECT.
  
 11) PAGE #5 WATER FILTRATION SYSTEMS
 SHALL BE NSF APPROVED PER SPC-94 615.1
 & 615.2. SUBMIT MANUF. INFO.
  
 12) PAGE#5 3 & 23 SUPPLY INFORMATION ON
 BACKFLOW.
  
 13) SANITIZER SUPPLIES SHALL BE BY
 PLUMBING CONTRACTOR. VALVES AND ADAPTORS
 FOR SANITIZER INSTALLER TO TIE INTO
  
 14) PAGE 3 #15, EMPLOYEE LOUNGE SINK TO
 COMPLY WITH FACBC 1997, SEC 4.24
  
 15) PAGE P-3 #8, NO SAFE WASTES ALLOWED
 FLOOR SINK REQUIRED.
  
 16) PAGE P-4, MEZZANINE, WHY IS THE
 GREASE LINE SEPARATED AND TWO LINES RUN
 IN BAKERY AREA. PLEASE EXPLAIN.
  
 17) PAGE P-5, DETAIL #5 NO HUB DRAINS
 ALLOWED.
  
 18) PAGE P-6, CAN WASH DETAIL, INFORMAT-
 ION NOT CLEAR. HOW DOES HOT AND COLD MIX
  
 19) SEE ATTACHED GAS PERMIT APPLICATION
 REQUIREMENTS SHEET. PLEASE SUBMIT INFOR-
 MATION REQUIRED FOR GAS PERMIT.
  
 REVIEW BY KEN STEVENS
 (561) 659 8096 EXT. 8377