| Plan Review Stops For Permit 01080053 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-11-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-11-26 |
Time |
18:35 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-11-26 00:00:00 | REVISION DATED 9/10/01 REVIEWED JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-08-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-08-28 |
Time |
15:13 |
Rev Time |
2.50 |
| Received By |
jwitmer |
Date |
2001-08-28 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2001-08-28 00:00:00 | COUNTY IMPACT FEES PD WILD OATS 00-18598 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-08-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-08-17 |
Time |
07:34 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-08-17 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01080053 | | | 375 S ROSEMARY | | | "PUBLIX" | | | | | | NOTE:FIRE DISTRICT | | | EXISTING DOORS 1E,2E & 3E ARE HORIZONTAL | | | SLIDING DOORS, THEY ARE TO COMPLY WITH | | | SBC SEC 1012.4 FOR HORIZONTAL SLIDING | | | DOORS. | | | | | | 1)- ENERGY CALCULATIONS? | | | | | | 2)- SBC104.2.2. MEZZANINE FLOOR PLAN, | | | WHERE DOES THE DOORS 33-N LEAD TO? WHAT | | | STOPS SOMEONE FROM OPENING THESE DOORS | | | AND FALLING? | | | | | | 3)- SHEET A-11 DOOR LEADING INTO THE | | | MENS RESTROOM REQUIRES 18" ON THE LATCH | | | SIDE OF THE DOOR PULL SIDE( FL ACC CODE | | | 4.13.6) | | | | | | 4)- FL ACC CODE 4.5 GROUD & FLOOR SUR- | | | FACES ALONG ACCESSIBLE ROUTES AND IN ACC | | | ESSIBLE ROOMS AND SPACES INCLUDING | | | FLOORS, WALKS, RAMPS, STAIRS AND CURB | | | RAMPS, SHALL BE FIRM, SLIP RESISTANT & | | | STABLE.A STATIC COEFFICIENT OF FRICTION | | | OF 0.6 IS RECOMMENDED FOR ACCESSIBLE | | | ROUTES & 0.8 FOR RAMPS. | | | | | | 5)- SBC 803.3 MISSING IS A MINIMUM INTER | | | IOR FINISH CLASSIFICATION SCHEDULE, SEE | | | SBC TABLE 803.3. FOR MAX. SMOKE/ FLAME | | | SPREAD. | | | SBC 903.7.1 AN APPROVED AUTOMATIC SPRINK | | | LER SYSTEM SHALL BE PROVIDED IN STORES | | | AND SIMILAR OCCUPANCIES WHERE STTOCKS OF | | | COMBUSTIBLE MATERIALS ARE ON DISPLAY FOR | | | PUBLIC SALE AND WHERE THE STORY FLOOR | | | AREA EXCEEDS 15,000 SQ. FT. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-11-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-19 |
Time |
19:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-19 |
Time |
19:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-08-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-27 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-27 |
Time |
09:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-08-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-14 |
Time |
19:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-14 |
Time |
19:34 |
Sent To |
|
|
| Notes |
| 2001-08-14 00:00:00 | ***************** UNSAT ************ | | | | | | 1)NOTE: PLEASE NOTE THAT MEANS OF | | | DISCONNECT WILL NEED TO MEET 230-72. | | | PLEASE NOTE THAT RISER NOTES SHOWN AS | | | #3 ON E-7 MENTIONS SHUNT TRIP FOR MAIN. | | | PLEASE NOTE THAT A MANUAL MEANS OF | | | DISCONNECT IS REQ`D PER 230-76 AND | | | 230-79. | | | | | | 2)NOTE: PLEASE NOTE THAT PER NOTE FOR | | | LOCATION OF GENERATOR SHUT DOWN,,, | | | SHUT DOWN OF GEN. NEEDS TO BE GROUPED | | | W/ MAIN. | | | | | | 3)NOTE: PLEASE NOTE PROVIDE | | | CLARIFICATION FOR FIRE PUMP AND FIRE | | | PUMP FEED? | | | | | | | | | PLEASE PROVIDE THE ABOVE CLARIFICATION | | | AND SUBMIT FOR REVIEW. PLEASE NOTE ALL | | | FIRE DEPT COMMENTS AS THEY MAY PERTAIN | | | TO ELECTRICAL AS WELL. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2001-11-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-21 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-21 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2001-11-21 00:00:00 | COULD NOT FIRE REVISIONS ON THE PLAN. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-08-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-27 |
Time |
12:44 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-27 |
Time |
12:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-08-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-02 |
Time |
18:11 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-02 |
Time |
18:11 |
Sent To |
|
|
| Notes |
| 2001-08-02 00:00:00 | 1) BUILDING ADDRESS REQUIRED PER CITY | | | CODE 3343-00. | | | 2) EXIT REQUIREMENTS ON PAGE AB-1 | | | INDICATES 250 FEET TRAVEL DISTANCE | | | PERMITTED. THE CURRENT FIRE CODE IS | | | MORE RESTRICTIVE AT 150 FEET AND SHOULD | | | BE NOTED ON THE PLANS. | | | 3) VERIFY EXISTING SLIDING DOORS MEET | | | THE REQUIREMENTS FOR POWER OPERATED | | | DOORS. PLEASE SEE 1985 EDITION OF THE | | | LIFE SAFETY CODE SECTION 5-2.1.9.1. | | | PLEASE EXPLAIN NOTE ON PLANS 105". | | | 4) PLEASE BE ADVISED THAT THIS BUILDING | | | IS WITHIN THE CITY FIRE LIMITS. CERTAIN | | | RESTRICTIONS APPLY TO THIS LOCATION. | | | 5) VERIFY IF A KNOX-BOX HAS BEEN | | | INSTALLED FOR THE SHELL BUILDING. | | | 6) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR WALLS | | | AND CEILINGS. | | | 7) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR HOOD, DUCT AND EXTINGUISHING | | | SYSTEMS. | | | 8) GAS INSTALLATION TO COMPLY WITH | | | NFPA 54 AND SHOULD BE NOTED ON THE | | | PLANS. | | | 9) PLEASE PROVIDE MORE DETAILS ON | | | NATURAL GAS GENERATOR PLANNED FOR USE. | | | 10) KITCHEN EXHAUST DUCT TO BE AT LEAST | | | 40 INCHES ABOVE THE ROOF. | | | 11) PLEASE CLEARLY IDENTIFY ALL | | | EMERGENCY LIGHT FIXTURE LOCATIONS. | | | 12) DUCT SMOKE DETECTORS TO CAUSE AIR | | | HANDLER SHUT DOWN AND ACTIVATE FIRE | | | ALARM SYSTEM. | | | 13) NO FIRE SPRINKLER SYSTEM DRAWINGS | | | PROVIDED. | | | 14) WRITTEN PERMISSION NEEDED TO MOUNT | | | FIRE ALARM SIGNALING DEVICES ON THE | | | CEILING NEEDED FROM THIS OFFICE. | | | 15) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM SYSTEM INSTALLATION. CUT | | | SHEETS, WIRING DIAGRAM AND BATTERY | | | CALCULATIONS REQUIRED AT TIME OF | | | SUBMITTAL. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-08-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-27 |
Time |
16:07 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-08-27 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2001-08-27 00:00:00 | *****************PROVISO**************** | | | | | | | | | PRIOR COMMENTS ADDRESSED EXCEPT | | | PERMISSIBLE REFRIGERANT QUANTITY, | | | BUILDING VOLUME (CALC) SHALL BE THAT OF | | | THE MEZZANINE NOT THE ENTIRE BUILDING | | | AS PER 1997 SMC 1104.3.1.REPONSE - | | | WILL BE ADDRESSED BY HILL PHOENIX DWGS | | | TO BE SUBMITTED AT A LATER DATE. | | | REFRIGERATION TO BE ON SEPARATE PERMIT. | | | | | | CALLED CONTRACTOR 8-27-01, LEFT MESSAGE, | | | NEED A CONFIRMATION THAT REFRIG. WILL BE | | | ON SEPARATE PERMIT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-08-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-16 |
Time |
16:44 |
Rev Time |
3.00 |
| Received By |
pkrauss |
Date |
2001-08-16 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2001-08-16 00:00:00 | ********************DENIED************** | | | | | | | | | PLAN SHEET R-1 PERMISSIBLE REFRIGERANT | | | QUANTITY, BUILDING VOLLUME SHALL BE | | | THAT OF THE MEZZANINE NOT THE ENTIRE | | | BUILDING AS PER 1997 SMC 1104.3.1. | | | | | | PLEASE PROVIDE MANUFACTURER INFORMATION | | | ON EMERGENCY GENERATOR. | | | | | | PLEASE PROVIDE AIR BALANCE SCHEDULE TO | | | SHOW COMPLIANCE WITH 1997 SMC 501.2. | | | | | | | | | ADDITIONAL PLANS AND PERMITS REQUIRED | | | FOR HOOD, FIRE SUPRESSION AND WALK-IN | | | COOLER/FREEZER SUBMIT PLANS AND | | | MANUFACTURER SUBMITTAL DATA WITH PERMIT | | | APPLICATION. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-11-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-16 |
Time |
13:25 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-11-16 |
Time |
13:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-08-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-08-25 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2001-08-25 |
Time |
09:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-08-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-08-17 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2001-08-17 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2001-08-17 00:00:00 | DENIED | | | | | | 1) PAGE PM-5, SECTION 15400 # 1.1.1.8, | | | HUB DRAINS NOT APPROVED. FLOOR SINKS ARE | | | REQUIRED FOR INDIRECT WASTE. | | | | | | 2) PAGE PM-5, SECTION 15400 # 1.1.1.6 | | | GREASE TRAPS TO BE SIZED AND LOCATED BY | | | R. COMPO (561) 837-4074. | | | | | | 3) PAGE PM-5, 3.4.1 HORIZONTAL SANITARY | | | PIPE 2" AND SMALLER TO BE GRADED AT 1/4" | | | PER FT. | | | | | | 4) PAGE PM-5, 3.5.13, WATER HAMMER ARRES | | | TORS TO BE SIZED AND LOCATED PER MANU- | | | FACTURES INSTALLATION INSTRUCTIONS. | | | | | | 5) PAGE PM-5, 3.5.14, AIR CHAMBERS TO | | | COMPLY WITH SPC-94 607.8.2/607.8.3 PDI- | | | WH 201. ACCESSABLE AND RECHARGEABLE. | | | | | | 6) PAGE A-7, VTR UNDER REFRIG. CONDENSER | | | STAND TO BE MOVED. (COL LINE C-2) | | | | | | 7) PAGE A-7, ALL VTR TO BE MINIMUM OF 10 | | | FEET FROM FRESH AIR INTAKES. | | | | | | 8) SEPARATE GAS PERMIT REQUIRED. SEPAR- | | | ATE GREASE TRAP REQUIRED. SEPARATE IRR- | | | AGATION PERMIT REQUIRED IF NOT INSTALLED | | | | | | 9) PAGE P-1 #14 MECH. SHUT OFF VALVES TO | | | BE UPSTREAM FROM UNIONS. | | | | | | 10) 140 DEGREE WATER NOT ALLOWED TO BE | | | PIPED TO LAVS, HAND SINKS ECT. ONLY 2, 3 | | | COMPARTMENT SINKS FOR WASHING DISHES, | | | POTS, AND PAN ECT. | | | | | | 11) PAGE #5 WATER FILTRATION SYSTEMS | | | SHALL BE NSF APPROVED PER SPC-94 615.1 | | | & 615.2. SUBMIT MANUF. INFO. | | | | | | 12) PAGE#5 3 & 23 SUPPLY INFORMATION ON | | | BACKFLOW. | | | | | | 13) SANITIZER SUPPLIES SHALL BE BY | | | PLUMBING CONTRACTOR. VALVES AND ADAPTORS | | | FOR SANITIZER INSTALLER TO TIE INTO | | | | | | 14) PAGE 3 #15, EMPLOYEE LOUNGE SINK TO | | | COMPLY WITH FACBC 1997, SEC 4.24 | | | | | | 15) PAGE P-3 #8, NO SAFE WASTES ALLOWED | | | FLOOR SINK REQUIRED. | | | | | | 16) PAGE P-4, MEZZANINE, WHY IS THE | | | GREASE LINE SEPARATED AND TWO LINES RUN | | | IN BAKERY AREA. PLEASE EXPLAIN. | | | | | | 17) PAGE P-5, DETAIL #5 NO HUB DRAINS | | | ALLOWED. | | | | | | 18) PAGE P-6, CAN WASH DETAIL, INFORMAT- | | | ION NOT CLEAR. HOW DOES HOT AND COLD MIX | | | | | | 19) SEE ATTACHED GAS PERMIT APPLICATION | | | REQUIREMENTS SHEET. PLEASE SUBMIT INFOR- | | | MATION REQUIRED FOR GAS PERMIT. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659 8096 EXT. 8377 |
|
|