Plan Review Details - Permit 01080021
Plan Review Stops For Permit 01080021
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-09-10 Cont ID  
Sent By dpalmer Date 2001-09-10 Time 17:50 Rev Time 0.00
Received By dpalmer Date 2001-09-10 Time 17:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-07 Cont ID  
Sent By dpalmer Date 2001-08-07 Time 10:59 Rev Time 0.00
Received By dpalmer Date 2001-08-07 Time 10:59 Sent To  
Notes
2001-08-07 00:00:00***************UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT THERE IS NO
 BRKR SIZE SHOWN FOR "MAIN" OF PANEL "B".
  
 2)NOTE: PLEASE NOTE THAT CODE ART SHOWN
 FOR GROUNDING ELECTRODE SYSTEM IS SHOWN
 FORM THE "96" NEC. WE ARE UNDER THE
 "99" NEC . PLEASE CORRECT.
 PLEASE SUBMIT CLARIFICATION ON
 REINFORCING STEEL? PLEASE CLARIFY WHERE
 THE BLDGSTEEL IS? PLANS SHOW SERVICES
 ON STAND
 ALONE RISERS.
  
 3)NOTE: PLEASE CLARIFY LOAD SHOWN AT
 250%? AND LOAD IS 125%. MUST BE A
 MISPRINT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-08-29 Cont ID  
Sent By sgraham Date 2001-08-29 Time 15:25 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-08-29 00:00:00APPROVEC BY MS


Account Summary | Usage Policy | Privacy Policy