Plan Review Details - Permit 01071546
Plan Review Stops For Permit 01071546
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-08-16 Cont ID  
Sent By hpiskura Date 2001-08-16 Time 13:11 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-08-08 Cont ID  
Sent By dpalmer Date 2001-08-08 Time 22:15 Rev Time 0.00
Received By dpalmer Date 2001-08-08 Time 22:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-08-02 Cont ID  
Sent By mcarsill Date 2001-08-02 Time 19:27 Rev Time 0.00
Received By mcarsill Date 2001-08-02 Time 19:27 Sent To  
Notes
2001-08-02 00:00:001) EXIT SIGN LOCATED IN BATHROOM NOT
 REQUIRED.
 2) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE HOOD, DUCT, AND SUPPRESSION
 SYSTEMS.
 3) WALL DETAIL ON PAGE A-1 INDICATES
 5X8 DRYWALL. IT SHOULD READ 5X8 TYPE X
 DRYWALL.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-10-12 Cont ID  
Sent By pkrauss Date 2001-10-12 Time 07:10 Rev Time 0.40
Received By pkrauss Date 2001-10-12 Time 07:07 Sent To  
Notes
2001-10-12 00:00:00*******************PROVISO**************
  
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION AND WALK-IN COOLERS.
 PLEASE PROVIDE PLANS WITH PERMIT
 APPLICATION.
  
 TERMINATION FOR HOOD EXHAUST SHALL
 COMPLY WITH 1997 SMC 506.1.
  
 1.SHALL BE LOCATED 10' FROM ANY
 ADJACENT BUILDING, PARKING AREA,
 ADJACENT PROPERTY LINE, AS WELL AS
 ANY WINDOW DOOR OR AIR INTAKE.
  
 2.EVERY EXHAUST OUTLET WHICH IS
 LOCATED ABOVE THE ROOF SHALL
 TERMINATE AT LEAST 40" ABOVE THE
 ROOF SURFACE.
  
 THE DISTANCE FROM THE FLOOR TO THE
 BOTTOM EDGE OF THE HOOD IS NOT LEGIBLE
 ON PLAN.AS PER 1997 SMC 504.2 #2 THIS
 DISTANCE SHALL BE A MAXIMUM OF 7'.
  
 NOTE:REFERENCE THE CONDENSER UNIT
 STANDS.COMMENTS FROM 8/20/01
 WERE NOT ADDRESSED IN THE
 RESUBMITTAL.A MINIMUM OF 18"
 IS REQUIRED BETWEEN THE ROOF
 SURFACE TO THE BOTTOM OF THE
 SUPPORT RAIL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-20 Cont ID  
Sent By ndenmark Date 2001-08-20 Time 08:24 Rev Time 0.33
Received By ndenmark Date 2001-08-20 Time 08:24 Sent To  
Notes
2001-08-20 00:00:00DENIED:
 1. HOOD EXHAUST TERMINATION DOES NOT
 COMPLY WITH 1997 SMC 506.1 PROVIDE
 INFORMATION SHOWING MINIMUM 10' FROM
 ANY ADJACENT PROPERTY LINE PARKING
 AREA, AIR INTAKE, WINDOW, OR DOOR.
 2. NO INFORMATION PROVIDED FORAIR
 CONDITIONING SYSTEM.
 3. NOTE SEPARATE PERMITS WILL BE
 REQUIRED FOR HOOD, SUPPRESSION SYSTEM
 AND WALK IN COOLERS. PROVIDE PLANS AT
 TIME OF PERRMIT APPLICATION FOR THIS
 WORK.
 4. MINIMUM CLEARANCE FROM BOTTOM OF
 SUPPORT BEAM OF STAND TO FINISHED ROOF
 SURFACE TO BE 18".

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-12-11 Cont ID  
Sent By pschmitz Date 2001-12-11 Time 09:30 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-12-11 00:00:00REVISION, RE-LOCATE GREASE TRAP.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-10-11 Cont ID  
Sent By kstevens Date 2001-10-11 Time 17:50 Rev Time 0.50
Received By kstevens Date 2001-10-11 Time 17:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-10-04 Cont ID  
Sent By kstevens Date 2001-10-04 Time 13:25 Rev Time 1.55
Received By kstevens Date 2001-10-04 Time 13:25 Sent To  
Notes
2001-10-04 00:00:00DENIED
  
 GREASE TRAP TO BE SIZED BY WPB UTILITIES
 PLEASE CALL RODNEY COMPO (561) 837-4074.
  
 A VAULT IS REQUIRED WITH A TRAFFIC LID.
 ALARMS REQUIRED- ONE FOR TANK AND ONE
 FOR THE SUMP PUMP.
  
 GREASE TRAP WILL HAVE TO HAVE 3" INTAKE
 AND OUTLET.
  
 MOP SINK - 3 COMP SINK - FLOOR DRAINS TO
 GREASE, ALL OTHER TO SANITARY.
  
 PLEASE PROVIDE LETTER FROM R COMPO AND
 DETAILS OF GREASE TRAP WITH ALARMS, SUMP
 ECT. INDICATED.
  
 PLEASE PROVIDE NEW GREASE AND SANITARY
 RISER DIAGRAMS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-15 Cont ID  
Sent By jleech Date 2001-08-15 Time 18:10 Rev Time 2.00
Received By jleech Date 2001-08-15 Time 18:10 Sent To  
Notes
2001-08-15 00:00:00DENIED;
 1.GREASE TRAP TO BE SIZED BY WEST PALM
 BEACH UTILITYS DEPARTMENT. CONTACT
 RODNEY COMPO AT 837-4074.
 2.SHOW COMPLIANCE WITH 94 SPC TABLE 407
 MINIMUM PLUMBING FACILITIES. SEE SEC.
 407.1.3 FOR DEDUCTABLE AREA.
 3.PAGE P-1 WATER RISER DIAGRAM, SIZE
 PIPES.
 4.SHOW ON WATER RISER WHERE WATER HAMMER
 ARRESTERSARE TO BE INSTALLED.SPECIFY
 TYPE AND SIZE. TO BE INSTALLED PER
 MANUFACTORS RECOMMENDATIONS AND SPC
 SEC. 607.8.2 AND 607.8.3.
 5.NOTE 13 WASTE PIPING LESS THAN 3" TO
 HAVE A PITCH OF 1/4" PER FOOT PER. SEC
 705.2
 6.NOTE 14 DIELECTRIC COUPLINGS ARE NOT
 PERMITED IN CITY WATER SYSTEM.
 7.NOTE 8 GALVANIZED WATER PIPE IS NOT
 PERMITED IN CITY WATER SYSTEM.
 8.THREE COMPARTMENT SINK SHALL DISCHARGE
 INDIRECTLY INTO A FLOOR SINK. SEC.
 804.1.
 9.( SANITARY RISER DIAGRAM)
 A.SHOW 3" VENT TO OUT SIDE.
 B.2 FLOOR SINKS ARE MISSING FROM
 DIAGRAM.
 C.WHAT DO DOTTED LINES MEAN? (STEAM
 TABLE TO FLOOR DRAIN. FLOOR SINK
 TO FLOOR DRAIN)
 10.GAS RISER DIAGRAM. NOT ENOUGH INFOR-
 MATION. AUTOMATIC SHUTOFF VALVE TO
 BE INSTALLED WITH HOOD SYSTEM. SHOW
 ON DRAWINGS AND ON RISER DIAGRAM. SEE
 INFORMATION SHEET. PLEASE COMPLY WITH
 NUMBER HIGHLIGHTED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 1 Status N Date 2001-10-12 Cont ID  
Sent By kstevens Date 2001-10-12 Time 12:41 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
***NONE***