Plan Review Details - Permit 01071485
Plan Review Stops For Permit 01071485
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-06-28 Cont ID  
Sent By lmartine Date 2004-06-28 Time 14:31 Rev Time 2.00
Received By lmartine Date   Time   Sent To  
Notes
2004-06-28 00:00:00APPROVED GRAND STAIR RAIL REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-11-20 Cont ID  
Sent By csiegber Date 2003-12-19 Time 10:13 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2003-11-20 00:00:00APPROVAL FOR SUSPENDED CEILING LM

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-11-07 Cont ID  
Sent By csiegber Date 2003-10-22 Time 14:14 Rev Time 2.00
Received By lmartine Date   Time   Sent To  
Notes
2003-11-07 00:00:00 
 SUSPENDED CEILING SUBMITTAL
  
 IS DENIED FOR THE FOLLOWING REASONS:
  
 1]
 ALL CALCULATIONS AND ACCOMPANYING
 DRAWINGS SHALL BE SIGNED AND SEALED BY
 P.E. WARDEN.
  
 2]
 SUBMIT ANCHORING DETAILS FOR WIRE AT
 EXSISTING SUPPORTING STRUCTURE. SUBMIT
 SUPPORTING DOCUMENTATION TO CLARIFY #8
 WIRES CAPACITY,NOTE ON CALCULATION
 SHEET 'PROBABLY ADEQUATE' IS NOT
 SUFFICIENT.
  
 3]
 PROVIDE THICKNESS AND SPEC. ON WELD FOR
 ALUMINUM ANGLE.
  
  
  
  
 LUIS MARTINEZ
 805-6710
2003-01-09 00:00:00PROCESS SHOP DRAWINGS APPROVED ON 12/26

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2002-12-11 Cont ID  
Sent By lmartine Date 2002-12-11 Time 18:42 Rev Time 20.00
Received By lmartine Date   Time   Sent To  
Notes
2002-12-11 00:00:00 
 SHOP DRAWING REVIEWS
 --------------------
  
 FAILED SUBMITTALS:
  
 DUCTWORK-SHEARWALL PENETRATIONS
 SLIDING METAL FIRE DOORS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-10-29 Cont ID  
Sent By btrobaug Date 2002-12-06 Time 16:32 Rev Time 20.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-10-29 00:00:00 
 BUILDING COMMENTS
 -----------------
 :PROVISO:
 1]
 SHEET A1-4.1 AND A1-4.2, NUMBERS ON
 EGGRESS ARROWS FOR OCCUPANT EXITING
 COUNT ARE NOT CORRECT.
 2]
 CONTRACTOR SHALL SUBMIT FOR SEPERATE
 PERMITS FOR ALL EXTERIOR GLAZING, DOORS
 AND ROOF COVER.
 3]
 ARCHITECT HAS BEEN CONTACTED TO REVIEW
 REMAINING ACCESSIBITY ISSUES.
  
  
  
 PLAN REVIEWER:
 LUIS MARTINEZ
 561-659-8096
 #8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-09-12 Cont ID  
Sent By lmartine Date 2001-09-12 Time 16:10 Rev Time 50.00
Received By lmartine Date   Time   Sent To  
Notes
2001-09-12 00:00:00 
 BUILDING COMMENTS
 -----------------
  
 1]
 PLEASE ADDRESS COMMENTS #S,6,7 AND 8
 FROM THE FIRE REVIEW LIST.
 2]
 PROVIDE SIGNED AND SEALED FIRE
 SPRINKLER LAYOUT BY THE DESIGN
 PROFESSIONAL.
 3]
 WILL GUTTER SYSTEM BE PROVIDED FROM
 PITCHED ROOF PORTION OF THE DRIVE-UP
 ENTRY CANOPY.
 4]
 SUBMIT SPECIFICATIONS FOR THE 2-HR
 RATED FIRE SHUTTER AT BOARD ROOM.
 5]
 HAVE DESIGN ENGINEER LIST ON HIS
 DRAWINGS ALL POSITIVE AND NEGATIVE
 PRESSURES FOR ALL EXTERIOR OPENINGS.
 SUBMIT APPROVED TEST REPORTS FOR ALL
 EXTERIOR GLAZING AND DOORS. SHALL
 COMPLY WITH BOTH WIND LOADING AND
 IMPACT RESISTANCE.
 6]
 PROVIDE 2HR RATED WALL SEPERATING THE
 CHILLER PLANT FROM THE UNDERSIDE OF THE
 EXTERIOR STAIRCASE. SH. A1-5.1.
 7]
 DOOR SCHEDULES, PROVIDE SPECIFICATIONS
 ON THE HARDWARE GROUPS. SH8-1.1 AND 1.2
 8]
 PLEASE SHOW COMPLIANCE WITH SBC
 705.2.2, SHAFT ENCLOSURES FOR
 ESCALATORS.
 9]
 ATRIUMS, SBC 414.6 SMOKE DETECTORS AND
 414.10 INTERIOR FINISH, PLEASE IDENTIFY
 COMPLIANCE.
 10]
 SBC 1004.3.5, IDENTIFY AREAS OF REFUGE.
 11]
 SBC 1007.3, ALL STAIRWAYS SHALL COMPLY
 WITH THE RISE AND RUN RATIO.
 12]
 PLEASE COMPLETE THE SUBMITTED FLA.
 ENERGY FORMS. OWNER SHALL SIGN,AND ALL
 9 SETS SUBMITTED ARE FOR THE SAME AREA
 OF THE BUILDING???
 13]
 EXIT AT LOADING DOCK AREA IS TO BE
 CLEARLY MARKED WITH SIGNS AND PATH OF
 TRAVELIDENTIFIED.
 14]
 SHEET A1-5.2, EXPLAIN 2HR RATING BEHIND
 INTERIOR OFFICES AT KITCHEN AREA.
  
 PLEASE SEE ADDITIONAL COMMENTS PROVIDED
 FOR ACCESSIBILITY COMPLIANCE.
 SEPERATE PACKAGE SHEETS,1 THRU 9.
  
  
 PLAN REVIEWER:
 LUIS MARTINEZ
 561-659-8096
 #8456

Review Stop E ELECTRICAL
Rev No 30 Status P Date 2004-04-26 Cont ID  
Sent By jleahy Date 2004-04-26 Time 13:42 Rev Time 0.45
Received By jleahy Date 2004-04-26 Time 13:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 29 Status P Date 2004-01-13 Cont ID  
Sent By csiegber Date 2004-04-07 Time 16:51 Rev Time 0.33
Received By dpalmer Date 2004-01-13 Time 12:04 Sent To FIRE
Notes
2004-01-13 00:00:00*** REV FOR EMT LTS . TO BE SENT TO
 FIRE DUE TO EM LTS REV.
 E1.103, 1.104

Review Stop E ELECTRICAL
Rev No 28 Status P Date 2003-12-05 Cont ID  
Sent By csiegber Date 2004-01-09 Time 09:12 Rev Time 2.00
Received By dpalmer Date 2003-12-05 Time 16:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 27 Status P Date 2003-11-03 Cont ID  
Sent By csiegber Date 2003-11-26 Time 09:02 Rev Time 2.00
Received By dpalmer Date 2003-11-03 Time 15:34 Sent To  
Notes
2003-11-03 00:00:00REV FOR HIGH BAY TYPE OF LT FIXTURES AND
 LOAD..

Review Stop E ELECTRICAL
Rev No 26 Status F Date 2003-11-03 Cont ID  
Sent By dpalmer Date 2003-11-03 Time 14:25 Rev Time 1.00
Received By dpalmer Date 2003-11-03 Time 14:25 Sent To  
Notes
2003-11-03 00:00:00**** UNSAT **********
  
 RFI'S
 1085
 1075
 1070
 1068
 1015
 1022
 1069
 1155
  
 PLEASE REMOVE ALL SHEETS THAT ARE NOT
 SIGNED DATED AND SEALED. THESE CAN NOT
 BE SUBMITTED FOR RECORD UNLESS. S/D/S
 BY ENGINEER OF RECORD. IF THESE REV'S
 HAVE ALREADY COME IN, PLEASE DO NOT
 SUBMIT.
 PLEASE FILL OUT COVER SHEET AND APPLY
 HOW MANY SHEETS ARE BEING REVISED.
 THESE ARE REV'S AND NOT SUBMITTALS.
 PLEASE NOTE; IF PANEL SCHEDULES THAT
 ARE ON 8 1/2 X 11'S ARE ON ONE SHEET
 ON PLANS. IT WOULD BE COST EFFECTIVE'
 IF LESS REVISED SHEETS WERE SUBMITTED.
 JUST AN FYI.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 25 Status N Date 2003-11-03 Cont ID  
Sent By dpalmer Date 2003-11-03 Time 13:54 Rev Time 0.25
Received By dpalmer Date 2003-11-03 Time 13:54 Sent To  
Notes
2003-11-03 00:00:00GENERATOR /WALL LOUVER REV TO INCOMING
 TO PUT ON COM BOARD. NEEDS FIRE AND BLDG
 .

Review Stop E ELECTRICAL
Rev No 24 Status N Date 2003-11-03 Cont ID  
Sent By dpalmer Date 2003-11-03 Time 13:53 Rev Time 0.25
Received By dpalmer Date 2003-11-03 Time 13:53 Sent To  
Notes
2003-11-03 00:00:00N/A BACK TO H MOSER. (1 SET)

Review Stop E ELECTRICAL
Rev No 23 Status P Date 2003-11-03 Cont ID  
Sent By dpalmer Date 2003-11-03 Time 13:47 Rev Time 0.33
Received By dpalmer Date 2003-11-03 Time 13:47 Sent To  
Notes
2003-11-03 00:00:00E-2.101

Review Stop E ELECTRICAL
Rev No 22 Status P Date 2003-05-12 Cont ID  
Sent By hmoser Date 2003-10-29 Time 17:20 Rev Time 0.25
Received By dpalmer Date 2003-05-12 Time 07:36 Sent To M
Notes
2003-05-12 00:00:00RFI SUBMITTALS OK, NO PLANS.

Review Stop E ELECTRICAL
Rev No 21 Status P Date 2003-05-09 Cont ID  
Sent By btrobaug Date 2003-05-09 Time 15:16 Rev Time 0.50
Received By btrobaug Date 2003-05-09 Time 15:15 Sent To M
Notes
2003-05-09 00:00:00THIS REVIEW WAS SUBMITTALS CONTAINING
 RFI'S ONLY,NO PLANS INVOLVED./WRT.

Review Stop E ELECTRICAL
Rev No 20 Status F Date 2003-04-30 Cont ID  
Sent By dpalmer Date 2003-04-30 Time 14:06 Rev Time 4.00
Received By dpalmer Date 2003-04-30 Time 14:06 Sent To  
Notes
2003-04-30 00:00:00***************** UNSAT *************
  
 PLEASE SUBMIT THREE COMPLETE SETS FOR
 REVIEW.
 PLEASE INSERT ALL DATED SHEETS FROM
 REV DATED 3/5/03 INTO SHEETS DATED
 4/3/03
  
 PLEASE NOTE, ELECTRICAL REVISIONS, OK
 TO COME BACK IN W/OUT FEE.
 IF THERE ARE ANY QUESTIONS,PLEASE SEE
 DV PALMER
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 19 Status F Date 2003-04-15 Cont ID  
Sent By dpalmer Date 2003-04-15 Time 07:47 Rev Time 0.75
Received By dpalmer Date 2003-04-15 Time 07:47 Sent To  
Notes
2003-04-15 00:00:00*********** HOLD WAITING**********
  
 ELECTRICAL REVISIONS BROUGHT IN ON 4/11
 WERE NOT COMPLETE WITH REVS FROM LAST
 SUBMITTAL FROM 3/10/03.
 PLANS SHOULD BE MADE INTO COMPLETE SETS
 FOR STAMPING AND REVIEW.
 REVISIONS 67/67A&B DATED FROM 9/20/02
 12/02, 1/03 ETC
  
 CALLED BOB RILING AND SPOKE W/ HIM
 ABOUT GETTING SETS BACK AND PUT
 TOGETHER. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 PLANS ON HOLD. DO NOT RELEASE
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 18 Status P Date 2003-04-10 Cont ID  
Sent By shernand Date 2003-04-11 Time 14:54 Rev Time 1.00
Received By btrobaug Date 2003-04-10 Time 17:34 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 17 Status I Date 2003-03-21 Cont ID  
Sent By dpalmer Date 2003-03-20 Time 16:43 Rev Time 4.00
Received By dpalmer Date 2003-03-20 Time 16:43 Sent To  
Notes
2003-03-21 00:00:00PLANS ARE UP FRONT UNDER "T" WAITING
 FOR OTHER SHEETS. SEE DV PALMER
 OTHER SHEETS OK TO COME IN W/OUT FEE.
  
 IF THERE ARE ANY QUESTIONS,
 SEE DV PALMER.
2003-03-20 00:00:00PLANS ARE ON HOLD WAITING FOR ADDITIONAL
 SHEETS FROMISSUE #67

Review Stop E ELECTRICAL
Rev No 16 Status F Date 2003-02-19 Cont ID  
Sent By sthyng Date 2003-03-12 Time 16:34 Rev Time 1.00
Received By dpalmer Date 2003-02-19 Time 13:09 Sent To  
Notes
2003-02-19 00:00:00****************** UNSAT **************
  
  
 1)NOTE: PLEASE SEE NOTE FROM REVIEW #13
 ATTACHED. PLEASE ADDRESS THOSE COMMENTS
 AND SUBMIT ALL REVISED PLANS AND CHANGES
 TO DATE.
  
 2)NOTE:PLEASE NOTE, AFTER A FIELD
 INSPECTION WITH ELECTRICAL INPECTOR,
 IT HAS COME TO OUR ATTENTION HE IS DOING
 INSPECTION OFF A SET OF PLANS FROM 2001?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 15 Status P Date 2003-02-14 Cont ID  
Sent By dpalmer Date 2003-02-14 Time 15:39 Rev Time 0.50
Received By dpalmer Date 2003-02-14 Time 15:39 Sent To  
Notes
2003-02-14 00:00:00LT SPECS.

Review Stop E ELECTRICAL
Rev No 14 Status P Date 2002-12-11 Cont ID  
Sent By dpalmer Date 2002-12-11 Time 07:29 Rev Time 0.25
Received By dpalmer Date 2002-12-11 Time 07:29 Sent To M
Notes
2002-12-11 00:00:00RFI FOR CHANGE OF SYMBOL FOR STROBE.
  
 REVISION FOR COMMENST FROM 13TH REV NOT
 ADDRESSED AT THIS TIME.

Review Stop E ELECTRICAL
Rev No 13 Status F Date 2002-11-25 Cont ID  
Sent By dpalmer Date 2002-11-25 Time 07:10 Rev Time 2.00
Received By dpalmer Date 2002-11-25 Time 07:10 Sent To FIRE
Notes
2002-11-25 00:00:00REVISIONS, LTG CONTROLS#4 &5
  
 ********** UNSAT **************
  
 1)NOTE: PLEASE NOTE, LOADS SHOWN FOR
 REVISED PANELS/RISERS NEED TO CORRELATE.
 PLEASE NOTE WHEN LOAD CHANGES FOR "HP"
 PANELS, PLEASE ADJUST FOR DPH`S THAT
 FEED THOSE PANELS.
 PLEASE ALSO NOTE, LOADS ON MSB-1 NEED TO
 CORRELATE WITH DPH`S LOADS SHOWN.
 PLEASE NOTE SOME DO AND SOME DON'T.
  
 PLEASE NOTE,LOADS ON MSB-2 AND
 EMDP-1 NEED TO CORRELATE ALSO WITH
 OTHER PANELS AND LOADS THEY SHOW.
  
 PLEASE SUBMIT THE ABOVE INFROAMTION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 12 Status N Date 2002-11-19 Cont ID  
Sent By dpalmer Date 2002-11-19 Time 15:31 Rev Time 1.00
Received By dpalmer Date 2002-11-19 Time 15:31 Sent To M
Notes
2002-11-19 00:00:00SUBMITTALS FOR BLDG ENERGY MANG CONTROLS
 NOT FOR ELECTRICAL REVIEW.

Review Stop E ELECTRICAL
Rev No 11 Status F Date 2002-10-21 Cont ID  
Sent By dpalmer Date 2002-10-21 Time 07:46 Rev Time 0.25
Received By dpalmer Date 2002-10-21 Time 07:46 Sent To  
Notes
2002-10-21 00:00:00*************** UNSAT ******************
  
  
 1)NOTE: PLEASE NOTE LIGHTNING PROTECTION
 SYSTEM IS TO BE PERMITTED SEPARATELY.
 PLEASE SUBMIT PLANS ALONG WITH SUBMITTAL
 -S.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND PERMIT APPLICATION. IF THERE
 ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2002-10-21 Cont ID  
Sent By dpalmer Date 2002-10-21 Time 07:46 Rev Time 4.00
Received By dpalmer Date 2002-10-21 Time 07:45 Sent To  
Notes
2002-10-21 00:00:00SUBMITTALS FOR MATERIALS ONLY.

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2002-08-13 Cont ID  
Sent By btrobaug Date 2002-08-13 Time 13:47 Rev Time 0.00
Received By btrobaug Date 2002-08-01 Time 11:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2002-05-23 Cont ID  
Sent By dpalmer Date 2002-05-23 Time 06:26 Rev Time 0.00
Received By dpalmer Date 2002-05-23 Time 06:26 Sent To  
Notes
2002-05-23 00:00:00************** /NOTE ************
  
  
 1)NOTE: PLEASE NOTE THIS IS A REVISION
 FOR ELECTRICAL AND OWES FEE.
  
 2)NOTE: PLEASE ALSO NOTE THAT THIS IS
 A SECOND REQUEST THAT THE VALUE OF JOB
 BE INCREASED TO CORRELATE WITH THE NEW
 CONTRACT VALUE. THIS WAS REQ`UESTED AT
 THE END OF MARCH AND TO DATE NOTHING
 HAS BEEN DONE.
  
 PLEASE SUBMIT THE ABOVE AS A REVISION
 AND ADDRESS NOTE #2. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
 PLEASE CALL BILL STAPLES ABOUT VALUE
 OF WORK IF THERE ARE ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 BILL STAPLES
 ASST BUILDING OFFICIAL
 561-659-8096 EXT 8315

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2002-04-01 Cont ID  
Sent By dpalmer Date 2002-04-01 Time 08:25 Rev Time 0.00
Received By dpalmer Date 2002-04-01 Time 08:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2002-03-19 Cont ID  
Sent By dpalmer Date 2002-03-19 Time 05:58 Rev Time 4.00
Received By dpalmer Date 2002-03-18 Time 17:00 Sent To  
Notes
2002-03-19 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT THE FOLLOWING
 PANEL SCHEDULES NEED TO BE SUBMITTED FOR
 REVIEW.EHP-6/EHP-7/ELP6A/ELP7A.
  
 2)NOTE: PLEASE NOTE THAT THE FOLLOWING
 ITEMS ON ONE-LINE DIAGRAM NEED TO MATCH/
 CORRELATE WITH ALL PANEL SCHEDULES.
 NEC-215-5
 DPH2, 4ITEMS.
 DPH1, MAIN
 MSB1, DISC #3
 DPH4, MAIN
 DPL4, MAIN AND 4TH BRKR
 DPL3, 4TH BRKR
 HP3,2 ITEMS
 MSB-2, PANEL S2?, EMDP-1
 HP8, 2 BRKRS
 LP8, 3 BRKRS
 EMDP1, EMCC1,ELEV, 1&5,EHP6
 MSB-3, 6 MAIN BRKRS
 MCC2, MAIN AND OTHER MAIN BRKRS
 MCC1, 4 BRKRS, AND AHU 15/16
 MCC3, 4BRKRS.
  
 PLEASE NOTE THAT MOST OF THE ABOVE HAVE
 SOME DIFFERENCES ON PANEL SCHEDULES.
 PLEASE ALSO NOTE THAT THERE MAY BE OTHER
 -S THAT WERE NOT LOCATED, PLEASE GO
 OVER PLANS.
  
 3)NOTE: PLEASE PROVIDE A LOAD SUMMARY
 FOR GENERATOR, SINCE GEN SIZE HAS BEEN
 DECREASED.
  
 4)NOTE: PLEASE HAVE PERMIT VALUATION
 INCREASED DUE TO CONTRACT INCREASES.
 PLEASE VERIFY AMOUNTS. CITY-WIDE ADMIN
 CODE.104.7.5 (1997) EDITION.
  
 5)NOTE: PLEASE SUBMIT REVISIONS FROM
 PREVIOUS REVIEW THAT WERE NOT SUBMITTED
 BACK FOR STAMPING. THE FLOOR LAYOUTS
 DID NOT HAVE ANY COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2002-02-22 Cont ID  
Sent By dpalmer Date 2002-02-22 Time 11:48 Rev Time 0.00
Received By dpalmer Date 2002-02-22 Time 11:48 Sent To  
Notes
2002-02-22 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THERE ARE ANY PANELS
 THAT THE LOADS WERE NOT REVISED WHEN
 LOADS WERE ADDED.
 PLEASE SEE;
 "EHP1"
 "EHP2"
 "EHP3"
 "LP-5
 "LP-7"
 "LP-8"
 "EHP6"
 "EMCC-1"
  
 PLEASE NOTE THAT "MCC4" ALSO DOES NOT
 HAVE ALL LOADS REVISED.
 PLEASE NOTE THAT LOAD FOR "MSB3" WAS
 NOT REVISED.
 PLEASE NOTE LOAD FOR "MCC-1" ALSO NEEDS
 TO BE REVISED.
 PLEASE NOTE THAT PANEL SCHEDULE NEED TO
 BE REVISED. PLEASE NOTE LOAD SHOWN
 ON MSB-3 ALREADY IS AT 3417AMPS.
  
 2)NOTE: PLEASE NOTE THAT ONE LINE SHOWS
 AHU#15 AT 60HP AND "MCC1" SHOWS AT 50HP
 AND LOAD FOR HP. PLEASE CORRELATE.
  
 3)NOTE: PLEASE E6.109 LP-8 25,27,29
 SHOWS 60A AND E2.202 SHOWS 30A. PLEASE
 CORRELATE.
  
 4)NOTE: PLEAS SUBMIT LINE DIAGRAM THAT
 WOULD INCLUDE LP-8.
  
  
 PLEASE REVISE AND SUBMIT ALL OF THE
 ABOVE INFORMATION FOR REVIEW. IF THERE
 ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-11-20 Cont ID  
Sent By dpalmer Date 2001-11-20 Time 08:46 Rev Time 0.00
Received By dpalmer Date 2001-11-20 Time 08:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-11-15 Cont ID  
Sent By dpalmer Date 2001-11-15 Time 09:22 Rev Time 0.00
Received By dpalmer Date 2001-11-15 Time 09:22 Sent To  
Notes
2001-11-15 00:00:00********** PASSED PENDING *************
 MINOR CHANGES TO BE NOTED ON PLANS FOR
 FIRE PUMP OCP,ATS, AND DISCONNECT.
  
 TO BE COMPLETED1PM 11/15/01.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-10-12 Cont ID  
Sent By dpalmer Date 2001-10-12 Time 05:28 Rev Time 0.00
Received By dpalmer Date 2001-10-12 Time 05:28 Sent To  
Notes
2001-10-12 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT COLOR CODING
 OF FEEDERS ON E5.101 SHOWS CONDUCTORS
 FOR 277/480 AS BLK,RED,BLUE. PLEASE
 NOTE THAT PER LOCAL AMENDMENTS THE COLOR
 -S FOR 277/480 IS BR/PURPLE/YELLOW.
 PLEASE ASLO PLACE THIS NOTE ON EACH OF
 THE ONE-LINE DIAGRAMS. ART:215
 NOTE FROM NOTE #5 ON FIRST REVIEW.
  
 2)NOTE: PLEASE NOTE, OCP IS NOW SHOWN
 ON LINE DIAGRAM FOR FIRE PUMP AS 800A`S
 ON FPL LINE. PLEASE NOTE THAT OCP THAT
 IS SHOWN COMING FROM GENERATOR IS SHOWN
 AT 200A`S.? PLEASE SEE 430-150. PLEASE
 NOTE LOAD FROM NEC IS SHOWN AT 240A`S
 AND IS THERE ANY PF CONSIDERATION?
 PLEASE CLARIFY LOADS ON 200HP MOTOR.
 3)NOTE: PLEASE CLARIFY THE LOCATION OF
 THE 800A OCP AND ATS SHOWN ON LINE DIA-
 -GRAM E5.103. PLEASE NOTE THAT ONLY
 CONTROL PANEL IS SHOWN IN FIRE PUMP ROOM
 AND ONLY THE TWO ATS`S FOR EMDP1 AND 2
 IS SHOWN IN MAIN ELECTRICAL ROOM.
  
 4)NOTE: PLEASE NOTE THAT FROM NOTE#3
 FIRST REVIEW, A NOTE WAS PLACE ON E2.102
 "ATS IN THIS ROOM FOR SHUTOFF" PLEASE
 CLARIFY NOTE ON PLANS SO THAT THE NOTE
 IS MORE SPECIFIC OF MEANS OF SHUT-OFF
 AND FOR WHAT? (GENERATOR)
  
 5)NOTE: PLEASE NOTE THAT IF USING "SCALE
 ON E4.104, PLEASE NOTE THE CLEARENCE FOR
 MAINS ON GENERATOR/CONTROL PANEL DO NOT
 SEEM TO MEET 110-26A "CONDITION 2"
 PLEASE CLARIFY.
  
 PLEASE NOTE THAT NOTES # 1 AND #5 WERE
 ADDRESSED FULLY.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL OR CALL FOR A MEETING IF
 DESIRED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-14 Cont ID  
Sent By dpalmer Date 2001-08-14 Time 13:15 Rev Time 0.00
Received By dpalmer Date 2001-08-14 Time 13:15 Sent To  
Notes
2001-08-14 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT GFI PROTECTION
 OF MAINS ARE NOT SHOWN. PER 230-95
 PLEASE SHOW ON RISER LINE DIAGRAM AND
 PANEL SCHEDULES FOR MSB`S.
  
 2)NOTE: PLEASE PROVIDE CLARIFICATION
 FOR MEANS OF DISCONNECT FOR FIRE PUMP.
 FEED IS SHOWN FROM FPL TO ATS W/ NO
 MAIN OR OCP? PLEASE CALRIFY. 695-3-A-1,
 230-2, 230-72B, 695-4-B-2
  
 3)NOTE: PLEASE SUBMIT CLARIFICATION FOR
 MEANS OF SHUTTING DOWN OF GENERATOR?
 MEANS OF DISCONNECT TO BE GROUPED W/
 MAINS PER 230-72, 230-76,230-79 AND
 MARKED PER 230-2.
  
 4)NOTE: PLEASE NOTE THAT OUTLET SPACING
 TO MEET LOCAL AMENDMENST PER 210-50.
 PLEASE NOTE SOME LOCATIONS MISSING
 OUTLETS. STARTING ON E2.101 (IN-21),,,,,
  
 5)NOTE: PLEASE PLACE DETAIL ON LINE
 DIAGRAM FOR COLOR CODING OF FEEDERS
 PER LOCAL COUNTY-WIDE AND CITY-WIDE
 ADMINISTRATIVE CODE. ART215
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2004-05-25 Cont ID  
Sent By mamini Date 2004-05-25 Time 09:49 Rev Time 0.50
Received By mamini Date 2004-05-25 Time 09:49 Sent To  
Notes
2004-05-25 00:00:00PASSED:
 1. REVIEWED FOR THE SOUTHWEST FIRE DEPT.
 ACCESS RAMP, REPALCED ASPHALT PAVING
 SOTH OF THE GATE WITH SOD AND IRRIGATION
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2003-10-28 Cont ID  
Sent By mamini Date 2003-10-28 Time 08:50 Rev Time 0.50
Received By mamini Date 2003-10-28 Time 08:50 Sent To  
Notes
2003-10-28 00:00:00PASSED:
 1. RVIEWED BY DEAN LAUDERMILK 10-28-03.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-10-24 Cont ID  
Sent By shernand Date 2003-07-17 Time 11:37 Rev Time 0.25
Received By dlauderm Date   Time   Sent To  
Notes
2001-10-24 00:00:00PLAN SETS DO NOT INCLUDE CIVIL,
 IRRIGATION OR LANDSCAPING.

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status P Date 2004-05-21 Cont ID  
Sent By mcarsill Date 2004-05-21 Time 11:38 Rev Time 0.00
Received By mcarsill Date 2004-05-21 Time 11:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2004-01-14 Cont ID  
Sent By nmccray Date 2004-01-14 Time 10:36 Rev Time 0.00
Received By nmccray Date 2004-01-14 Time 10:36 Sent To  
Notes
2004-01-14 00:00:00REVISION DATED 12-10-03 FOR EMERGENCY
 LIGHTING SHEETS E1.103 AND E1.104

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2002-12-04 Cont ID  
Sent By dpalmer Date 2004-01-13 Time 12:07 Rev Time 0.00
Received By nmccray Date 2002-12-04 Time 14:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status N Date 2002-05-28 Cont ID  
Sent By dpalmer Date 2002-11-25 Time 07:10 Rev Time 0.00
Received By mcarsill Date 2002-05-28 Time 10:55 Sent To  
Notes
2002-05-28 00:00:001) WHAT WILL THE SERIES 705 UL/FM
 BUTTERFLY VALVE BE USED FOR. PLEASE
 SEE PAGE 14 OF SUBMITTALS.
  
 2) THE FIRE DEPARTMENT CONNECTION SHOWN
 ON PAGE 18 IS TO BE COMPATIBLE WITH
 WEST PALM BEACH FIRE RESCUE NST
 CONNECTION.
  
 3) PLEASE INDICATE LOCATION AND USE OF
 THE GLOBE VALVES SHOWN ON PAGE 19.
  
 MIKE WENNERGREN, ACTING CAPTAIN
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2002-02-26 Cont ID  
Sent By mcarsill Date 2002-02-26 Time 12:48 Rev Time 0.00
Received By mcarsill Date 2002-02-26 Time 12:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-11-29 Cont ID  
Sent By mcarsill Date 2001-11-29 Time 17:35 Rev Time 0.00
Received By mcarsill Date 2001-11-29 Time 17:35 Sent To  
Notes
2001-11-29 00:00:00RECEIVED ORIGINAL LETTERS REGARDING
 MEMORANDUM OF UNDERSTANDING # 1 FROM
 HOWE ENGINEERS, INC.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-11-20 Cont ID  
Sent By mcarsill Date 2001-11-20 Time 15:04 Rev Time 0.00
Received By mcarsill Date 2001-11-20 Time 15:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-10-18 Cont ID  
Sent By mcarsill Date 2001-10-18 Time 09:18 Rev Time 0.00
Received By mcarsill Date 2001-10-18 Time 09:18 Sent To  
Notes
2001-10-18 00:00:001) SOME MATH ERRORS STILL EXIST IN
 OCCUPANT LOAD CHARTS 1 & 2.
 2) DO THE WALLS IN SERVICE CORRIDOR
 2N-28 CREATE HARD BARRIERS FOR EXITING
 ONCE PERSONS LEAVE THE BALLROOMS VIA
 THE EXIT DOORS.
 3) EMERGENCY LIGHTS STILL NOT CLEARLY
 IDENTIFIED IN BALLROOMS AND EXHIBIT
 HALL.
 4) THE FINAL REPORT FOR SMOKE CONTROL,
 SMOKE EXHAUST IS NOT SIGNED AND SEALED.
 ALSO THE FINAL REPORT MUST BE SUBMITTED
 TO THE BUILDING OFFICIAL FOR HIS
 REVIEW AND APPROVAL UNDER SEPARATE
 COVER. PLEASE VERIFY THAT THE REPORT
 IS THE FINAL DRAFT AND READY FOR
 SUBMITTAL. A REVIEW OF THIS DOCUMENT
 SUGGESTS SOME CORRELATION ISSUES STILL
 EXIST.
 5) COULD NOT LOCATE EXIT # 14 ON PAGE
 A1-4.1.
 6) PLEASE CLEARLY IDENTIFY THAT ALL
 PRESCRIPTIVE CODE REQUIREMENTS HAVE BEEN
 MET FOR THE RAMP BEING USED FOR
 EXITING ADJACENT TO THE LOADING DOCK.
 7) CO2 EXTINGUISHERS NOTED ON PAGE
 FP1-1.1. PLEASE EXPLAIN.
 8) ARE THE DUAL ENCLOSED STAIRS SCISSSOR
 STAIRS OR DOUBLE STAIRS.
 9) WEST WALL NOT RATED ON PAGE A1-5.1
 10) PLEASE BE ADVISED THAT CERTAIN
 RESTRICTIONS APPLY TO THE USE OF WOOD
 IN THE FIRE LIMITS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-10 Cont ID  
Sent By mcarsill Date 2001-08-10 Time 12:20 Rev Time 0.00
Received By mcarsill Date 2001-08-10 Time 12:20 Sent To  
Notes
2001-08-10 00:00:001) PLEASE BE ADVISED THAT THIS BUILDING
 IS LOCATED WITHIN THE CITY FIRE LIMITS.
 CERTAIN RESTRICTIONS APPLY.
 2) PLEASE BE ADVISED THAT CITY CODE
 SECTION 11-73 PROHIBITS THE USE OF
 OPEN FLAME DEVICES IN PUBLIC ASSEMBLY
 OCCUPANCIES.
 3) PLEASE INDICATE COMPLIANCE WITH
 PRESCRIPTIVE CODE REQUIREMENTS OF NFPA
 101, 2000 EDITION.
 4) STILL HAVE NOT RECEIVED LETTER
 REGARDING THE NON USE OF PYROTECHNICS
 WITHIN THE BUILDING.
 5) FIRE HYDRANTS NOT SHOWN ON SITE PLAN.
 ADDITIONAL FIRE HYDRANTS HAVE BEEN
 AGREED TO BY THE DESIGN TEAM.
 6) OCCUPANT LOAD CHART, LEVEL ONE ON
 PAGE A1-4.1 IS NOT CORRECT. MATH ERRORS
 EXIST.
 7) OCCUPANT LOAD CHART FOR LEVEL TWO
 HAS THE SAME PROBLEM.
 8) VOID SPACE UNDERNEATH MONUMENTAL
 STAIR ON PAGE A2-1.1, CONFIRM USE IF
 ANY.
 9) PLEASE EXPLAIN USE FOR OVERHEAD DOORS
 IN RATED FIRE WALLS. WHEN OPENED HOW
 DO THESE DOORS CLOSE AUTOMATICALLY.
 ARE SMOKE DETECTORS TIED INTO THESE
 DOORS. PRODUCT APPROVALS NEEDED FOR ALL
 OVERHEAD FIRE DOORS. DOWN ON ALL ALARMS.
 10) PLEASE EXPLAIN OPPOSING DOORS NEAR
 CHILLER PLANT.
 11) PLEASE EXPLAIN USE OF PANTRY.
 12) EXPLAIN 16'-0 HIGH SLIDING METAL
 DOORS. HOW DO THEY SLIDE WITHOUT
 INTERFERING WITH DOORS USED FOR
 EXITING.
 13) HOW DOES THE 30' HIGH OPERABLE
 PARTITION WALL WORK.
 14) PLEASE EXPLAIN ONE HOUR RATED
 CONTINOUSLY HINGED OPERABLE WALL,
 MEETING ROOM 1E-13.
 15) FRT PLYWOOD TO 6'-0 AFFF IN SERVICE
 CORRIDOR 2N-28 IS USED FOR WHAT.
 16) PROPOSED FURNITURE LAYOUT IN
 PRE-FUNCTION AREAS SHOULD BE SHOWN.
 17) STRETCHED FABRIC WALL SYSTEMS,
 SECOND FLOOR MEETING ROOM ENTRY, PLEASE
 EXPLAIN.
 18) PLEASE PROVIDE PRODUCT APPROVALS
 FOR TRANSOMS 1 1/2 HOUR LABELED
 PERFORATED METAL INFILL PANELS.
 19) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR CEILINGS,
 WALLS, AND FLOORS. ALSO FLAME SPREAD
 INFORMATION REQUIRED FOR ANY CURTAINS,
 ETC.
 20) PLEASE INDICATE TACTILE SIGNAGE FOR
 EXIT DOORS.
 21) WHY ARE THERE NO FIRE ALARM
 EQUIPMENT WITHIN TRANSFORMER ROOM.
 22) PLEASE INDICATE WHAT THE EMERGENCY
 VOICE EVACUATION MESSAGE WILL SAY.
 23) ALL HOODS USED FOR THE COOKING THAT
 PRODUCES SMOKE OR GREASE LADEN VAPORS
 ARE TO BE CONNECTED TO THE BUILDING'S
 FIRE ALARM SYSTEM.
 24) NO SPEAKER STROBES NOTED IN LOADING
 DOCK W-07.
 25) STORAGE ROOM 2E-30 HAS NO SMOKE
 DETECTOR IN IT LIKE OTHER ONES.
 26) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE INSTALLATION OF THE FIRE ALARM
 SYSTEM.
 27) GAS INSTALLATION TO COMPLY WITH
 NFPA 54. PLEASE NOTE THIS ON THE
 DRAWINGS.
 28) WHY ARE CO2 EXTINGUISHERS PLANNED
 FOR SOME SECTIONS INSTEAD OF ABC TYPES.
 29) 8" FIRE LINE SHOWN RUN UNDERFLOOR
 IS NOT ALLOWED TO BE INSTALLED IN THIS
 MANNER.
 30) PLEASE SHOW DRAFT CURTAINS AND
 CLOSELY SPACED FIRE SPRINKLER HEADS
 TO PROTECT ESCALATOR OPENINGS.
 31) NO FIRE SPRINKLER PROTECTION SHOWN
 FOR BANQUET STORAGE 2W-14.
 32) THIS OFFICE WOULD ENCOURAGE THE USE
 OF A COMPLETE WET PIPE FIRE SPRINKLER
 SYSTEM FOR THE BUILDING INSTEAD OF SOME
 AREAS HAVING PRE-ACTION SYSTEMS DUE
 TO FUTURE MAINTENANCE ISSUES.
 33) FIRE MARSHAL SPELLED INCORRECTLY
 ON SIGN DRAWINGS ON G3.1.0.
 34) PLEASE PROVIDE A TYPICAL ARRANGEMENT
 FOR THE EXHIBIT HALL.
 35) PLEASE CLEARLY IDENTIFY EMERGENCY
 LIGHT FIXTURES IN 1E-36 AND EXHIBITION
 HALL.
 36) FIRE SPRINKLER PROTECTION REQUIRED
 IN FIRE PUMP ROOM.
 37) A HOSE CABINET IS SHOWN IN STORAGE
 ROOM 1N-48.
 38) HOW DOES THE EXIT DOORS, SOUTH ENTRY
 LOBBY WORK WHEN PHASE TWO IS STARTED.
 39) ARE THERE ANY FOOD SERVICE DEVICES
 PLANNED FOR THE EXHIBITION HALL THAT
 WOULD PRODUCE SMOKE OR GREASE LADEN
 VAPORS. IF THEY DO COMPLIANCE WITH
 NFPA 96 WOULD BE REQUIRED IN THE
 CONCESSION AREAS.
 40) AFTER ANOTHER REVIEW OF THE
 EXHIBITION HALL IT WOULD APPEAR THAT
 ADDITIONAL EXIT SIGNAGE IS NEEDED ON THE
 WEST SIDE OF IT.
 41) SMOKE EVACUATION SYSTEM CALCULATION
 FOR TOTAL VOLUME IS INCORRECT. BASED
 ON INFORMATION SUPPLIED, IT SHOULD
 READ 1,975,868 INSTEAD OF 1,975,328.
 42) HOW WILL THE SMOKE EVACUATION
 SYSTEM BE IMPACTED FOR PHASE ONE, WHEN
 THE FUTURE PHASE TWO CONSTRUCTION IS
 FINISHED.
 43) PLEASE DEFINE "OPERATOR" WHO WILL
 BE CAPABLE OF OVERRIDING THE SYSTEM AND
 PLACING THE SYSTEM INTO ANY MODE AT
 ANY TIME.
 44) PLEASE EXPLAIN WHY NO MANUAL
 OPERATION WILL CAUSE THE SMOKE EXHAUST
 SYSTEM TO OPERATE.
 45) THE BUILDING MANAGEMENT SYSTEM SHALL
 NOT BE CAPABLE OF EVER OVERRIDING THE
 REQUIRED FIRE ALARM SYSTEM OR SMOKE
 EXHAUST SYSTEM FOR THE ATRIUM.
 46) RECENTLY, IT WAS EXPLAINED THAT
 EXHUAST FANS ARE PLANNED FOR THE EXHIBIT
 HALL. WILL THESE DEVICES BE ABLE TO BE
 BUMPED ON BY FIRE RESCUE TO EXHAUST
 SMOKE OR POSSIBLE PYROTECNIC RESIDUE IF
 APPROVED BY FIRE RESCUE.
 47) PLEASE INDICATE WHAT THE WARNING
 SIGNAGE FOR THE CHILLER PLANT WILL SAY
 AND WHAT LOCATIONS WILL THEY BE PLACED.
 48) NO FIRE SEPARATION SHOWN ON WALL
 BETWEEN LOADING DOCK AND WEST WALL
 OF EXHIBIT HALL. ALSO THE SECOND FLOOR
 SAME LOCATION. SOUTH WALL ALSO.
 49) PLEASE EXPLAIN SIDELIGHTS SHOWN FOR
 WALLS ON A5-1.1.
 50) HOW IS EXITING GOING TO BE DEFINED
 FROM THE ASSEMBLY TO THE LOADING DOCK
 AREA.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 64 Status N Date 2004-05-20 Cont ID  
Sent By csiegber Date 2004-05-20 Time 14:30 Rev Time 0.00
Received By csiegber Date 2004-05-20 Time 14:30 Sent To  
Notes
2004-05-20 00:00:00TO COMM BD#26

Review Stop I INCOMING/PROCESSING
Rev No 63 Status N Date 2004-05-19 Cont ID  
Sent By mmclean Date 2004-05-20 Time 11:25 Rev Time 0.00
Received By csiegber Date 2004-05-19 Time 13:09 Sent To Z
Notes
2004-05-19 00:00:00TO ERIC SCHNEIDER VIA MM

Review Stop I INCOMING/PROCESSING
Rev No 62 Status N Date 2004-04-07 Cont ID  
Sent By csiegber Date 2004-04-07 Time 16:51 Rev Time 0.00
Received By csiegber Date 2004-04-07 Time 16:51 Sent To E
Notes
2004-04-07 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 61 Status N Date 2004-01-09 Cont ID  
Sent By csiegber Date 2004-01-09 Time 09:11 Rev Time 0.00
Received By csiegber Date 2004-01-09 Time 09:11 Sent To E
Notes
2004-01-09 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 60 Status N Date 2004-01-06 Cont ID  
Sent By mmclean Date 2004-01-08 Time 15:50 Rev Time 0.00
Received By csiegber Date 2004-01-06 Time 10:58 Sent To Z
Notes
2004-01-06 00:00:00TO ERIC SCHNEIDER/PLANNING/REV

Review Stop I INCOMING/PROCESSING
Rev No 59 Status N Date 2003-12-19 Cont ID  
Sent By csiegber Date 2003-12-19 Time 10:13 Rev Time 0.00
Received By csiegber Date 2003-12-19 Time 10:13 Sent To  
Notes
2003-12-19 00:00:00TO LM DESK

Review Stop I INCOMING/PROCESSING
Rev No 58 Status N Date 2003-12-16 Cont ID  
Sent By csiegber Date 2003-12-16 Time 09:52 Rev Time 0.00
Received By csiegber Date 2003-12-16 Time 09:52 Sent To B
Notes
2003-12-16 00:00:00TO LM DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 57 Status N Date 2003-12-10 Cont ID  
Sent By csiegber Date 2003-12-10 Time 15:57 Rev Time 0.00
Received By csiegber Date 2003-12-10 Time 15:57 Sent To B
Notes
2003-12-10 00:00:00TO LM DESK/SUBMITTAL SE CANOPY FRAMING
 HANDRAIL CALCS

Review Stop I INCOMING/PROCESSING
Rev No 56 Status N Date 2003-12-05 Cont ID  
Sent By csiegber Date 2003-12-05 Time 15:47 Rev Time 0.00
Received By csiegber Date 2003-12-05 Time 15:47 Sent To  
Notes
2003-12-05 00:00:00TO MIKE SIZEMORE

Review Stop I INCOMING/PROCESSING
Rev No 55 Status N Date 2003-12-05 Cont ID  
Sent By csiegber Date 2003-12-05 Time 08:27 Rev Time 0.00
Received By csiegber Date 2003-12-05 Time 08:27 Sent To B
Notes
2003-12-05 00:00:00TO LM DESK/RFI'S 1393-1393A

Review Stop I INCOMING/PROCESSING
Rev No 54 Status N Date 2003-11-26 Cont ID  
Sent By csiegber Date 2003-11-26 Time 09:02 Rev Time 0.00
Received By csiegber Date 2003-11-26 Time 09:02 Sent To E
Notes
2003-11-26 00:00:00TO DP/REV

Review Stop I INCOMING/PROCESSING
Rev No 53 Status N Date 2003-11-06 Cont ID  
Sent By csiegber Date 2003-11-06 Time 16:25 Rev Time 0.00
Received By csiegber Date 2003-11-06 Time 16:25 Sent To  
Notes
2003-11-06 00:00:00REC'D POLLUTION CONTROL PLAN INSPECT
 GAVE TO LM

Review Stop I INCOMING/PROCESSING
Rev No 52 Status N Date 2003-11-03 Cont ID  
Sent By csiegber Date 2003-11-03 Time 14:14 Rev Time 0.00
Received By csiegber Date 2003-11-03 Time 14:14 Sent To  
Notes
2003-11-03 00:00:00TO COMM BD#36

Review Stop I INCOMING/PROCESSING
Rev No 51 Status N Date 2003-10-22 Cont ID  
Sent By csiegber Date 2003-10-22 Time 14:14 Rev Time 0.00
Received By csiegber Date 2003-10-22 Time 14:14 Sent To B
Notes
2003-10-22 00:00:00TO LM DESK/SIGNAGE

Review Stop I INCOMING/PROCESSING
Rev No 50 Status N Date 2003-10-22 Cont ID  
Sent By csiegber Date 2003-10-22 Time 14:11 Rev Time 0.00
Received By csiegber Date 2003-10-22 Time 14:11 Sent To B
Notes
2003-10-22 00:00:00TO LM DESK SUBMITTA; - SIGN FOOTING

Review Stop I INCOMING/PROCESSING
Rev No 49 Status N Date 2003-10-22 Cont ID  
Sent By csiegber Date 2003-10-22 Time 14:10 Rev Time 0.00
Received By csiegber Date 2003-10-22 Time 14:10 Sent To B
Notes
2003-10-22 00:00:00TO LM DESK/FLAG POLE SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 48 Status N Date 2003-10-22 Cont ID  
Sent By csiegber Date 2003-10-22 Time 14:05 Rev Time 0.00
Received By csiegber Date 2003-10-22 Time 14:05 Sent To  
Notes
2003-10-22 00:00:00TO DON NEELY/SUBMITTAL-POLLUTION CONTROL
 PLAN INSP & MTNC REPT

Review Stop I INCOMING/PROCESSING
Rev No 47 Status N Date 2003-10-22 Cont ID  
Sent By csiegber Date 2003-10-22 Time 14:00 Rev Time 0.00
Received By csiegber Date 2003-10-22 Time 14:00 Sent To B
Notes
2003-10-22 00:00:00TO LM DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 46 Status N Date 2003-10-22 Cont ID  
Sent By csiegber Date 2003-10-22 Time 13:58 Rev Time 0.00
Received By csiegber Date 2003-10-22 Time 13:58 Sent To B
Notes
2003-10-22 00:00:00TO LM DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 45 Status N Date 2003-10-21 Cont ID  
Sent By csiegber Date 2003-10-21 Time 14:37 Rev Time 0.00
Received By csiegber Date 2003-10-21 Time 14:37 Sent To B
Notes
2003-10-21 00:00:00TO LM DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 44 Status N Date 2003-10-16 Cont ID  
Sent By csiegber Date 2003-10-16 Time 10:23 Rev Time 0.00
Received By csiegber Date 2003-10-16 Time 10:23 Sent To E
Notes
2003-10-16 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 43 Status N Date 2003-09-10 Cont ID  
Sent By dbaxter Date 2003-09-10 Time 15:09 Rev Time 0.00
Received By dbaxter Date 2003-09-10 Time 15:08 Sent To E
Notes
2003-09-10 00:00:00TO DPALMER DESK.

Review Stop I INCOMING/PROCESSING
Rev No 42 Status N Date 2003-09-10 Cont ID  
Sent By dbaxter Date 2003-09-10 Time 15:05 Rev Time 0.00
Received By dbaxter Date 2003-09-10 Time 15:05 Sent To B
Notes
2003-09-10 00:00:00TO LMARTINEZ DESK.

Review Stop I INCOMING/PROCESSING
Rev No 41 Status N Date 2003-08-29 Cont ID  
Sent By sthyng Date 2003-08-29 Time 10:47 Rev Time 0.00
Received By sthyng Date 2003-08-29 Time 10:47 Sent To B
Notes
2003-08-29 00:00:00METAL SUNSHADE TRELLIS
 TO LM DESK

Review Stop I INCOMING/PROCESSING
Rev No 40 Status N Date 2003-08-29 Cont ID  
Sent By csiegber Date 2003-08-29 Time 09:54 Rev Time 0.00
Received By csiegber Date 2003-08-29 Time 09:54 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 39 Status N Date 2003-08-25 Cont ID  
Sent By csiegber Date 2003-08-25 Time 15:29 Rev Time 0.00
Received By csiegber Date 2003-08-25 Time 15:29 Sent To B
Notes
2003-08-25 00:00:00TO LM DESK

Review Stop I INCOMING/PROCESSING
Rev No 38 Status N Date 2003-07-31 Cont ID  
Sent By alange Date 2003-07-31 Time 09:07 Rev Time 0.00
Received By alange Date 2003-07-31 Time 09:07 Sent To B
Notes
2003-07-31 00:00:00TO LM DESK 7/31/03ALANGE

Review Stop I INCOMING/PROCESSING
Rev No 37 Status N Date 2003-07-17 Cont ID  
Sent By shernand Date 2003-07-17 Time 11:38 Rev Time 0.00
Received By shernand Date 2003-07-17 Time 11:38 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 36 Status N Date 2003-07-17 Cont ID  
Sent By shernand Date 2003-07-17 Time 11:37 Rev Time 0.00
Received By shernand Date 2003-07-17 Time 11:37 Sent To ENG
Notes
2003-07-17 00:00:00SUBMITTAL, POLLUTION CONTROL PLAN

Review Stop I INCOMING/PROCESSING
Rev No 35 Status N Date 2003-07-14 Cont ID  
Sent By shernand Date 2003-07-14 Time 08:55 Rev Time 0.00
Received By shernand Date 2003-07-14 Time 08:55 Sent To B
Notes
2003-07-14 00:00:00LMARTINEZ DESK, 2 SUBMITTALS.

Review Stop I INCOMING/PROCESSING
Rev No 34 Status N Date 2003-07-11 Cont ID  
Sent By shernand Date 2003-07-11 Time 10:55 Rev Time 0.00
Received By shernand Date 2003-07-11 Time 10:55 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2003-07-07 Cont ID  
Sent By shernand Date 2003-07-07 Time 10:20 Rev Time 0.00
Received By shernand Date 2003-07-07 Time 10:20 Sent To ENG
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2003-07-01 Cont ID  
Sent By shernand Date 2003-07-01 Time 15:39 Rev Time 0.00
Received By shernand Date 2003-07-01 Time 15:39 Sent To B
Notes
2003-07-01 00:00:00LMARTINEZ

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2003-06-23 Cont ID  
Sent By shernand Date 2003-06-23 Time 10:18 Rev Time 0.00
Received By shernand Date 2003-06-23 Time 10:18 Sent To ENG
Notes
2003-06-23 00:00:003 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2003-06-10 Cont ID  
Sent By shernand Date 2003-06-10 Time 08:26 Rev Time 0.00
Received By shernand Date 2003-06-10 Time 08:26 Sent To B
Notes
2003-06-10 00:00:00LUIS MARTINEZ DESK

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2003-05-19 Cont ID  
Sent By shernand Date 2003-05-19 Time 10:08 Rev Time 0.00
Received By shernand Date 2003-05-19 Time 10:08 Sent To E
Notes
2003-05-19 00:00:00DP DESK.

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2003-05-16 Cont ID  
Sent By shernand Date 2003-05-16 Time 10:53 Rev Time 0.00
Received By shernand Date 2003-05-16 Time 10:53 Sent To ENG
Notes
2003-05-16 00:00:00SUBMITTAL.

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2003-05-15 Cont ID  
Sent By shernand Date 2003-05-15 Time 10:55 Rev Time 0.00
Received By shernand Date 2003-05-15 Time 10:55 Sent To  
Notes
2003-05-15 00:00:00COMM BOARD #64

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2003-05-13 Cont ID  
Sent By shernand Date 2003-05-13 Time 16:37 Rev Time 0.00
Received By shernand Date 2003-05-13 Time 16:37 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-04-11 Time 14:54 Rev Time 0.00
Received By shernand Date 2003-04-11 Time 14:54 Sent To E
Notes
2003-04-11 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-04-11 Time 13:51 Rev Time 0.00
Received By shernand Date 2003-04-11 Time 13:50 Sent To B
Notes
2003-04-11 00:00:00LMARTINEZ DESK

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-04-11 Time 13:50 Rev Time 0.00
Received By shernand Date 2003-04-11 Time 13:50 Sent To B
Notes
2003-04-11 00:00:00LMARTINEZ DESK

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2003-03-31 Cont ID  
Sent By sthyng Date 2003-03-31 Time 13:03 Rev Time 0.00
Received By sthyng Date 2003-03-31 Time 13:03 Sent To B
Notes
2003-03-31 00:00:00SUBMITTALS TO LM DESK
  
 1.)POLLUTION CONTROL PLAN - INSPECTION
 AND MAINT REPORT FOR WEEK ENDING 3/21/03
 2.)POLLUTION CONTROL PLAN - INSPECTION
 AND MAINT REPORT FOR 3/24 RAINFALL EVENT
 3.)POLLUTION CONTROL PLAN - INSPECTION
 AND MAINT REPORT FOR 3/27 RAINFALL EVENT
 4.)ANALYSIS OF SMOKE CONTROL/SMOKE
 EXHAUST

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2003-03-19 Cont ID  
Sent By sthyng Date 2003-03-19 Time 13:53 Rev Time 0.00
Received By sthyng Date 2003-03-19 Time 13:53 Sent To  
Notes
2003-03-19 00:00:00SUBMITTALS (6) -
  
 1.)KITCHEN EQUIPMENT SHOP DRAWINGS -
 SENT TO LM DESK
  
 2.)KITCHEN EQUIPMENT SHOP DRAWINGS -
 SENT TO LM DESK
  
 3.)THERMOSTATIC MIXING VALVE - SENT
 TO PLUMBING
  
 4.)SPLIT DX UNIT SUBMITTALS - SENT
 TO MECHANICAL
  
 5.)POLLUTION PREVENTION PLAN - SENT
 TO LM DESK
  
 6.)LIGHTING CONTROL - SENT TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2003-03-12 Cont ID  
Sent By sthyng Date 2003-03-12 Time 16:34 Rev Time 0.00
Received By sthyng Date 2003-03-12 Time 16:34 Sent To E
Notes
2003-03-12 00:00:00SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2003-03-10 Cont ID  
Sent By dpalmer Date 2003-03-10 Time 09:38 Rev Time 0.00
Received By dpalmer Date 2003-03-10 Time 09:38 Sent To B
Notes
2003-03-10 00:00:00TO LM`S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2003-03-10 Cont ID  
Sent By dpalmer Date 2003-03-10 Time 09:37 Rev Time 0.00
Received By dpalmer Date 2003-03-10 Time 09:37 Sent To B
Notes
2003-03-10 00:00:00TO LM `S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2003-03-06 Cont ID  
Sent By dpalmer Date 2003-03-06 Time 10:33 Rev Time 0.00
Received By dpalmer Date 2003-03-06 Time 10:33 Sent To B
Notes
2003-03-06 00:00:00TO LM`S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2003-03-06 Cont ID  
Sent By dpalmer Date 2003-03-06 Time 10:32 Rev Time 0.00
Received By dpalmer Date 2003-03-06 Time 10:32 Sent To B
Notes
2003-03-06 00:00:00TO LM`S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2003-02-26 Cont ID  
Sent By dpalmer Date 2003-02-26 Time 09:15 Rev Time 0.00
Received By dpalmer Date 2003-02-26 Time 09:15 Sent To B
Notes
2003-02-26 00:00:00SUBMITTAL TO LOU M.

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2003-02-10 Cont ID  
Sent By dpalmer Date 2003-02-10 Time 10:23 Rev Time 0.00
Received By dpalmer Date 2003-02-10 Time 10:23 Sent To B
Notes
2003-02-10 00:00:00TO LOU M'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2003-01-29 Cont ID  
Sent By dpalmer Date 2003-01-29 Time 16:12 Rev Time 0.00
Received By dpalmer Date 2003-01-29 Time 16:12 Sent To B
Notes
2003-01-29 00:00:00TO LM DESK.

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2003-01-27 Cont ID  
Sent By dpalmer Date 2003-01-27 Time 11:21 Rev Time 0.00
Received By dpalmer Date 2003-01-27 Time 11:21 Sent To FIRE
Notes
2003-01-27 00:00:00TO FIRE REVIEW INBOX.

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2003-01-10 Cont ID  
Sent By btrobaug Date 2003-01-10 Time 16:23 Rev Time 0.00
Received By btrobaug Date 2003-01-10 Time 16:23 Sent To B
Notes
2003-01-10 00:00:00TO LUIS M./WRT

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2003-01-10 Cont ID  
Sent By btrobaug Date 2003-01-10 Time 16:21 Rev Time 0.00
Received By btrobaug Date 2003-01-10 Time 16:21 Sent To B
Notes
2003-01-10 00:00:00TO LUIS M./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2002-12-06 Cont ID  
Sent By btrobaug Date 2002-12-06 Time 16:32 Rev Time 0.00
Received By btrobaug Date 2002-12-06 Time 16:32 Sent To B
Notes
2002-12-06 00:00:00TO HAROLD P./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2002-12-05 Cont ID  
Sent By btrobaug Date 2002-12-05 Time 17:29 Rev Time 0.00
Received By btrobaug Date 2002-12-05 Time 17:29 Sent To B
Notes
2002-12-05 00:00:00TO HAROLD P./WRT

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2002-12-04 Cont ID  
Sent By csiegber Date 2004-05-05 Time 14:08 Rev Time 0.00
Received By csiegber Date 2002-12-04 Time 17:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2002-11-27 Cont ID  
Sent By btrobaug Date 2002-11-27 Time 12:03 Rev Time 0.00
Received By btrobaug Date 2002-11-27 Time 12:03 Sent To B
Notes
2002-11-27 00:00:00TO HAROLD P./WRT

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2002-11-22 Cont ID  
Sent By btrobaug Date 2002-11-22 Time 17:33 Rev Time 0.00
Received By btrobaug Date 2002-11-22 Time 17:33 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2002-11-13 Cont ID  
Sent By dpalmer Date 2002-11-13 Time 16:30 Rev Time 0.00
Received By dpalmer Date 2002-11-13 Time 16:30 Sent To B
Notes
2002-11-13 00:00:00TO LOU MARTINEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2002-11-06 Cont ID  
Sent By btrobaug Date 2002-11-06 Time 16:42 Rev Time 0.00
Received By btrobaug Date 2002-11-06 Time 16:42 Sent To B
Notes
2002-11-06 00:00:00TO HAROLD P./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-10-31 Cont ID  
Sent By btrobaug Date 2002-10-31 Time 12:35 Rev Time 0.00
Received By btrobaug Date 2002-10-30 Time 12:33 Sent To FIRE
Notes
2002-10-31 00:00:00TO FIRE./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-29 Cont ID  
Sent By dpalmer Date 2002-10-29 Time 07:10 Rev Time 0.00
Received By dpalmer Date 2002-10-28 Time 07:09 Sent To B
Notes
2002-10-29 00:00:00SUBMITTALS, TO LOU M.

Review Stop M MECHANICAL (A/C)
Rev No 16 Status P Date 2003-11-04 Cont ID  
Sent By hmoser Date 2003-11-04 Time 16:56 Rev Time 0.50
Received By hmoser Date 2003-11-04 Time 16:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 15 Status P Date 2003-10-29 Cont ID  
Sent By hmoser Date 2003-10-29 Time 17:19 Rev Time 1.50
Received By hmoser Date 2003-10-29 Time 17:19 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 14 Status P Date 2003-09-15 Cont ID  
Sent By hmoser Date 2003-09-15 Time 14:34 Rev Time 0.50
Received By hmoser Date 2003-09-15 Time 14:34 Sent To  
Notes
2003-09-15 00:00:00MIKE SIZMORE AND HAROLD MOSER HAD A MEET
 ING MONDAY 9/15/03.MIKE TALKED TO NEAL
 MELICK.YOU DO NOT NEED STAMPED LETTER
 FROM SIMPLEXGRINNELL ON LOCATION OF DUCT
 MOUNTED SMOKE DETECTORS.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 13 Status F Date 2003-08-09 Cont ID  
Sent By hmoser Date 2003-08-09 Time 06:46 Rev Time 0.50
Received By hmoser Date 2003-08-09 Time 06:46 Sent To  
Notes
2003-08-09 00:00:00PLAN DENIED
 DO TO THE LETTER FROM SIMPLEXGRINNEL
 THE CITY CAN NOT DETERMIN THE ACTUAL
 PLACEMENT OF THE DUCTDETECTOR.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 12 Status P Date 2003-04-12 Cont ID  
Sent By hmoser Date 2003-04-12 Time 11:14 Rev Time 1.50
Received By hmoser Date 2003-04-12 Time 11:14 Sent To  
Notes
2003-04-12 00:00:00SUBMITHALS FOR SPLIT DXUNIOT OK

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2002-08-06 Cont ID  
Sent By dpalmer Date 2002-12-11 Time 07:30 Rev Time 0.40
Received By pkrauss Date 2002-08-06 Time 08:55 Sent To  
Notes
2002-08-06 00:00:00SUBMITTALS

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2002-05-29 Cont ID  
Sent By ndenmark Date 2002-05-29 Time 12:46 Rev Time 0.50
Received By ndenmark Date 2002-05-29 Time 12:46 Sent To  
Notes
2002-05-29 00:00:00REVISIONS REQUIRED BY THE RFI'S ARE TO
 BE SUBMITTED ON THE APPROPRIATE PLAN
 PAGES AS REQUIRED TO SHOW CHANGES ON
 DRAWINGS.
  
 NANCY DENMARK
 CHIEF MECHANICAL INSPECTOR
 (561) 659-8096 EXT. 8221

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2002-04-30 Cont ID  
Sent By ndenmark Date 2002-04-30 Time 12:49 Rev Time 0.25
Received By ndenmark Date 2002-04-30 Time 12:49 Sent To  
Notes
2002-04-30 00:00:00SKM-2 AND SKM-3 REVISEDSKM-3 REPLACES
 SKM-1

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2002-04-02 Cont ID  
Sent By pkrauss Date 2002-04-02 Time 14:58 Rev Time 0.40
Received By pkrauss Date 2002-04-02 Time 14:58 Sent To  
Notes
2002-04-02 00:00:00SUBMITTAL FOR:
  
 CHILLERS, PUMPS, SUCTION DIFFUSER, RELIE
 F VALVES, AIR SEPARATOR

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2002-03-12 Cont ID  
Sent By pkrauss Date 2002-03-12 Time 14:35 Rev Time 1.00
Received By pkrauss Date 2002-03-12 Time 14:34 Sent To  
Notes
2002-03-12 00:00:00REVISION TO PLAN SHEET M2.103, M2.104,
 M2.203, M2.204, M2.207, & M2.208.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2001-11-20 Cont ID  
Sent By ndenmark Date 2001-11-20 Time 08:43 Rev Time 0.50
Received By ndenmark Date 2001-11-20 Time 08:43 Sent To  
Notes
2001-11-20 00:00:00PROVISO:
 3 ORIGINAL SIGNED COPIES OF THE MEMO OF
 UNDERSTANDING AUTHORED BY JIM HOWE TO BE
 SET TO THIS OFFICE FOR INCLUSION IN
 THE FILE.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2001-11-14 Cont ID  
Sent By ndenmark Date 2001-11-14 Time 09:41 Rev Time 1.50
Received By ndenmark Date 2001-11-14 Time 09:41 Sent To  
Notes
2001-11-14 00:00:00THE FOLLOWING ITEMS NED TO BE CLARIFIED:
  
 1. M2.207 FIRE DAMPER REQUIRED FOR
 TRANSFER OPENING IN ELEC. RM 2E-16 WEST
 WALL BY COLUMN 16 AND S.
 2. WHAT TYPE OF FUEL SUPPLY IS TO BE
 USED FOR THE GENERATOR AND HOW MUCH ON
 SITE STORAGE?
 3. WALLS REQUIREING RATING SHALL HAVE
 OPENING PROTECTION PER 1997 SMC 610.
 4. NFPA 37 CH 5 REQUIRES RATING OF
 GEERATOR RM WALLS.
 5. PLAN SHOWS 2 HR RATING OF GENERATOR
 RM WALLS.
 6 CAN WE ACCEPT THE HOWE REPORT FOR
 SMOKE CONTROL IF NOT SIGNED/ SEALED BY
 STATE OF FLORIDA ENGINEER.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2001-10-12 Cont ID  
Sent By ndenmark Date 2001-10-12 Time 14:14 Rev Time 2.00
Received By ndenmark Date 2001-10-12 Time 14:14 Sent To  
Notes
2001-10-12 00:00:00****ATRIUM SMOKE CONTROL****************
  
 THE FOLLOWING QUESTIONS NEED TO BE
 ADDRESSED .
 1. WHY NOT USE MANUAL PULL TO INITIATE
 ATRIUM SMOKE CONTROL SYSTEM?
 2. PAGE 19 OF 57 ZONE 3 SHOWS A 6 FT
 HEIGHT FOR SMOKE FOR THE GRADE LEVEL
 AND FOR THE BALLROOM PREFUNCTION AREA.
 THIS CONFLICTS WITH PRIOR STATEMENTS TO
 MAINTAIN A 10 FOOT TENABLE HEIGHT.
 3. PAGE 30 SHOWS NO SMOKE BEING USED AND
 PAGE 34 INDICATES A SMOKE PRODUCTION
 METHOD. BE ADVISED THE ACCEPTANCE
 TEST WILL REQUIRE SMOKE TO BE USED AS
 PART OF THE CRITERIA TO ACCEPT THE
 SMOKE CONTROL SYSTEM.
 4.PROVIDE A DIAGRAM OF THE SMOKE CONTROL
 PANEL FOR REVIEW.
 5. PROVIDE A COPY OF THE FINAL APPROVED
 CITY STAMPED ANALYSIS OF SMOKE CONTROL/
 SMOKE EXHAUST PRIOR TO THE ACCEPTANCE
 TEST FOR INSPECTORS REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2001-10-12 Cont ID  
Sent By ndenmark Date 2001-10-12 Time 10:53 Rev Time 4.00
Received By ndenmark Date 2001-10-12 Time 10:53 Sent To  
Notes
2001-10-12 00:00:00*******REVIEW DOES NOT INCLUDE SMOKE
 CONTROL SYSTEM*************************
 DENIED
 1.M2.106 NO FIRE DAMPERS SHOWN IN RATED
 WALL DIFFUSER PENETRATIONS AT ALCOVE BY
 COLUMNS T AND U AND 8 AND 9.
 2. FIRE DAMPER NOT SHOWN AT RATED WALL
 PENETRATION OF 16X18 DUCT BY
 COLUMN LINE 4 AND C.8 M2.201
 3. FIRE DAMPERS NOT SHOWN M2.202 AT
 PENETRATION OF 28 X 20 DUCT BY COLUMN G
 AND ( AND ELECTRIC ROOOM 14X 8 DUCT
 PENETRATION SAME AREA
 4. M2.202 TELEPHONE ROOM 2N31 APPEARS TO
 AHVE RATED WALL PENETRATION BY 8X8
 DUCT.
 5.M2.208 NO FIRE DAMPERS SHOWN AT 2 DUCT
 PENETRATIONS BY COLUMN U AND 21 AND NO
 FIRE DAMPER SHOWN AT 18X 20 DUCT BY U
 AND 20.
 6 M2.102 TRANSFER AIR NEEDS TO BE FROM
 SATELLITE ROOM AS WELL AS IN DOOR N40-1
 7. M 2.106 FIRE DAMPER REQUIRED IN 6"
 SUPPLY TO 1N68, SHOW MANAGERS OFFICE
 8> M2.107 NO FIRE DAMPER SHOWN IN 16X6
 TRANSFER DUCT IN STORAGE RM 1E-28 EAST
 WALL
 9. PREVIOUS COMMENT ON VAULT ROOM
 OPENINGS REFER TO LOUVER OPENINGS IN
 REQUIRED RATED WALLS. THIS WOULD ALSO
 INCLUDE THE GENERATOR ROOM.
 10. PLUMBING CONNECTION OF CONDENSATE
 DRAINS TO STORM SEWER TO BE PER
 PLUMBING APPROVAL.
  
 SEE MECH REVIEW # 4 FOR SMOKE CONTROL
 COMMENTS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-08-06 Cont ID  
Sent By ndenmark Date 2001-08-06 Time 14:09 Rev Time 5.00
Received By ndenmark Date 2001-08-06 Time 14:09 Sent To  
Notes
2001-08-06 00:00:00REVIEW FOR SMOKE CONTROL SYSTEM FOR
 ATRIUM
 ***************DENIED*******************
 1. PLEASE CLARIFY MAXIMUM ATRIUM HEIGHT
 AS WE HAVE TWO DIFFERENT STATEMENTS AS
 TO HEIGHT.
 2. PROVIDE SEQUENCE OF OPERATION FOR
 DOOR OPENINGS AND ATRIUM SMOKE CONTROL
 3. DURING THE ORIGINAL MEETING ON SMOKE
 CONTROL THE BUILDING OFFICIAL REQUESTED
 IF YOU WERE USING AN ALTERNATIVE METHOD
 TO THE SBC USE THE 10 FOOT ABOVE THE
 SECOND FLOOR NOT THE 6 FOOT AS SHOWN IN
 THE REPORT.
 4. ALL ELEVATIONS OPENING TO THE ATRIUM
 ARE NOT INDICATED AS REQUESTED IN THE
 FIRST SET OF COMMENTS. PROVIDE
 INFORMATION ON THE ELEVATIONS INVOLVED,
 I,E. AREAS SHOWN AS OPEN TO BEYOND BY
 BALLROOM CONCOURSE BETWEEN COLUMNS U
 AND K.
 5. ARE ALL RESTROMS, THE ADMINISTRATIVE
 ASSISTANT (1N-49), RECEPTION AREA
 (1N-50) AND ANY OTHER AREA NOT
 SEPARATED BY RATED WALLS INCLUDED IN
 THE ATRIUM SIZE CALCULATION?
 6. AS PART OF THE SEQUENCE OF OPERATION,
 PROVIDE INFORMATION ON ALL DEVICES THAT
 WILL INITIATE THE SMOKE CONTROL SYSTEM.
 7. INDICATE IN THE SEQUENCE OF OPERATION
 HOW THE DIFFERENT FANS AND DOORS IN THE
 DIFFERENT ZONES WILL OPERATE. WILL ALL
 DOORS OPEN AND ALL FANS COME ON AR ONLY
 THOSE IN EFFECTED AREAS?
 8.SHOW FIREMANS OVERRIDE PANEL AND
 EXPLAIN FUNCTION.
 9. ON SHEET M5.103 SEQUENCE OF OPERATION
 SAYS THAT OPERATOR WILL BE ABLE TO
 OVERRIDE THE SYSTEM AT ANY TIME. DEFINE
 OPERATOR IN THIS STATEMENT.
 10. IF FANS OPERATE PRIOR TO DOOR
 OPENING, PROVIDE INFORMATION ON DOOR
 PRESURE. PROVIDE MAXIMUM DOOR PULL
 PRESSURES FOR ALL EXIT DOORS NOT OPENED
 AS PART OF THE SMOKE CONTROL SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-02 Cont ID  
Sent By ndenmark Date 2001-08-02 Time 12:01 Rev Time 14.00
Received By ndenmark Date 2001-08-02 Time 12:01 Sent To  
Notes
2001-08-02 00:00:00**************DENIED********************
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS
 PRIOR TO RESUBMITTAL OF PLANS.
 1.THE DUCT BANK DETAIL SHOWN ON A1-17
 SHOWS DUCT ON COMPACTED EARTH. !997 SMC
 607 REQUIRES MECHANICAL DUCT TO BE
 ENCLASED ON ALL SIDES WITH NOT LESS
 THAN 2" OF CONCRETE.
 2. THE LOUVER OPENING FOR GENERATOR ROOM
 SHOWN ON A2-1.3 ARE REQUIRED TO BE
 PROTECTED BY APPROVED FIRE DAMPERS TO
 MAINTAIN THE RATING OF THIS ROOM.
 PROVIDE INFORMATION ON OPENING
 PROTECTION.
 3. DOES THE PROJECTION EQUIPMENT SHOWN
 ON A3-1.6 REQUIRE ADDITIONAL
 VENTILATION OR EXHAUST? PROVIDE
 MANUFACTURES RECOMMENDATIONS ON
 EQUIPMENT REQUIREMENTS.
 4. OVERHEAD DOORS SHOWN IN RATED WALLS
 WILL BE REQUIRED TO HAVE AUTOMATIC
 CLOSURE ABILITY TO PROTECT OPENING.
 PROVIDE INFORMATION ON DOOR FUNCTION TO
 COMPLY WITH REQUIREMENTS FOR OPENING
 PROTECTION.
 5. PLAN SHOWS VEHICLE ACCESS TO SECOND
 FLOOR. WHAT REQUIREMENTS FOR ADDITONA
 OUTSIDE AIR OR MONITORING FOR CARBON
 MONOXIDE DOES THIS ADD TO THE FACILITY?
 PROVIDE CALCULATIONS SHOWING WORST CASE
 LOAD OF VEHICLES.
 6. NO INFORMATION WAS SHOWN FOR DISPOSAL
 OF CONDENSATE FROM AIR HANDLING
 EQUIPMENT. PROVIDE LOCATION AND SIZES
 OF THIS PIPING AND DISPOSAL LOCATION.
 NOTE: LOCAL ORDINACE DOES NOT PERMIT
 CONDENSATE TO GO TO THE SANITARY SYSTEM.
 7. CHILLER SPECS ON M 0.002 SHOW
 EFFIENCY RATING AS NLPV. FLORIDA ENERGY
 CODE REQUIRES RATING IN ILPV. PLEASE
 PROVIDE CHILLER RATING AS ILPV NUMBER
 COMPLYING WITH TABLE 4-5 MINIMUM
 PERFORMANCE EFFICIENCIES.
 8. ENERGY CALCS SHOW 4 SYSTEMS WITH
 VARIOUS EFFICIENCIES. NOT ALL EQUIPMENT
 APPEARS TO BE LISTED IN CALCS PROVIDED.
 SHOW ALL EQUIPMENT TO BE INSTALLED OR
 SUMMARY AS PROVIDED FOR IN FLA ENERGY
 CODE,
 9. M0.002 AIR BALANCE EXHAUST AND
 OUTSIDE AIR VALUES DO NOT ADD UP TO
 EQUIPMENT VALUES SHOWN. PROVIDE AIR
 BALANCE SCHEDULE SHOWING COMPLIANCE
 WITH 1997 SMC 501.2 AND OUTSIDE AIR
 CALCULATIONS SHOWING COMPLIANCE WITH
 ASHRAE 62.89.
 10. OUTSIDE AIR REQUIRED FOR TICKET
 OFFICE NEEDS TO BE DUCTED TO THE RETURN
 AIR OF THE UNIT SERVING THIS SPACE FOR
 BALANCING PURPOSES
 11.WOMEN'S AND MEN'S BATHROOMS AND
 LOCKER ROOMS SHOWN ON M2.101 HAVE 1400
 CFM OF EXHAUST AIR AND ONLY 200 CFM OF
 SUPPLY AIR. ANOTHER AREA HAS 600 CFM
 EXHAUST AND 100 S/A. RM 1N23+ 24 HAVE
 3050 EXHAUST AIR AND 850 SUPPLY AIR.
 PROVIDE AIR BALANCE IN COMPLIANCE WITH
 1997 SMC 501.2
 12. NO RETURN AIR IS SHOWN IN SATELLITE
 ROOM 1N53 AND IN ROOM 1N-57 S/A IS 100
 CFM AND R/A IS 10CFM.
 13. ADMIN AREA (1N64 HAS 850CFM S/A AND
 920 CFM R/A AND RMS 1N59/60 HAS 530 CFM
 EXHAUST AIR AND 100 CFM S/A.
 14. NO RETURN AIR SHOWN FOR DOCK OFFICE
 1N-39 ANY AREA WITH 350 CFM OR MORE
 NEEDS RETURN FROM ROOM.
 15. MACHINE ROOM HAS 490 CFM OF EXHAUST
 AIR AND NO PROVISION FOR MAKE UP AIR.
 SHOW COMPLIANCE WITH SMC 501.2.
 16. NO FIRE DAMPERS SHOWN AT FLOOR
 PENETRATIONS OF DUCT ON M 2.104
 17. WOMEN'S ROOM 1C 17 AND 14 HAVE 670
 CFM OF EHAUST AND 310 CFM MAKE UP AIR
 INCLUDING U/C OF DOOR.
 18. ON M 2.106 NO FIRE DAMPERS SHOWN IN
 EAST WALL OF SHOW AMANGERS
 OFFICE(1N-68)AT DUCT PENETRATION.
 19. NO PROTECTION OF WALL PENETRATIONS
 SHOWN FOR TRANSFER GRILLS, DOOR GRILLS,
 AND OVERHEAD DOORS ON WEST SIDE OF
 SERVICE CORRIDOR RATED WALL BETWEEN
 COLUMN S AND T ON M2.107
 20. NO FIRE DAMPERS SHOWN IN RATED WALL
 AT COLUMN V DUCT PENETRATIONS CLOSE TO
 AREA 7 AND 8 MATCH LINE.
 21. M2.201 MEN,S ROOM 2N-15 HAS 740 CFM
 E/A AND 485CFM MAKE UP AIR INCLUDING
 DOOR GRILL. JANITOR'S CLOSET HAS 140
 CFM E/A AND 590 CFM MAKE UP(INTO MEN'S
 ROOM).
 22. SYMBOL FOR DUCT ELEVATION CHANGE
 DIFFERS FROM LEGEND TO WHATS USED ON
 DRAWINGS.
 23. NO COMBUSTIBLES ALLOWED IN RETURN
 AIR PLENUM AREAS.
 24. M2.201 CLARIFY WHICH WALL IS RATED
 AT ELEC AND TELE RMS 2N-12 AND 10. GAP
 ON HOURLY RATED WALL PLAN A1-5.2. DUCTS
 PENETRATE SOUTH WALL W/ NO FIRE DAMPERS
 SHOWN BY COLUMNS C.8 AND 4 AT 16X18"
 DUCT PENETRATION.
 25. M2.201 NO FIRE DAMPER SHOWN BY
 COLUMN J AND 4 AT 14" DUCT PENETRATION
 26. WOMEN'S BATH AND LOCKER ROOM ON
 M2.202 HAS 500 CFM TOTAL EXHAUST AND
 250 CFM OF MAKE UP AIR
 27. NO FIRE DAMPERS SHOWN ALONG RATED
 SERVICE CORRIDOR 2N-28 X 10 PLACES ON
 M2.202. DOOR GRILLS ARE NOT SHOWN AS
 RATED. FLOOR CEILING PENETRATIONS TO BE
 PROTECTED BY 1997 SMC 610.
 28. M2.203 AND 4 NO FIRE DAMPERS
 INDICATED AT STAIR 8 RATED WALL 10X16
 DUCT PENETRATION COLUMN C.7.
 ARE MECH ROOM 2W-15, 2W-16 AND 2W-18
 WALLS RATED? PLAN SHOWS DASHED LINES
 BUT NO FIRE DAMPERS AT DUCT
 PENETRATIONS.
 29. M 2.207 ELECTRIC ROOM 2E-16 HAS 575
 CFM OF SUPPLY AIR BUT NO RETURN AIR PATH
 FROM ROOM. PROVIDE RETURN AIR PER SMC
 501.2
 30. M2.207 NO FIRE DAMPERS SHOWN AT
 RATED WALL DUCT PENETRATION 18X20 DUCT
 BY COLUMN 16 18X20 DUCT COLUMN 15 AND
 10X6 DUCT COLUMN T
 31. M2.208 NO FIRE DAMPERS SHOWN AT 6X6
 DUCT INTO STORAGE ROOM 2E-30 RATED WALL
 PENETRATION.
 32. M3.201 NO FIRE DAMPER SHOWN AT 10X6
 DUCT AND 18X20 DUCT INTO MECH ROOM.
 33. M3.202 SHOW FIRE DAMPERS AT DUCT
 PENETRATIONS IF WALLS ARE RATED.
 34. PROVIDE INFORMATION ON TYPE AND
 QUANTITY OF REFRIGERANT PER CHILLER.
 TYPE DETERMINES SETPOINT FOR
 REFRIGERANT LEAK DETECTION SYSTEM.
 35. M5.104 OUTSIDE AIR REQUIRED BY
 ASHRAE 62.89 SHALL NOT BE REDUCED BY
 CO2 SENSORS. PROVIDE INFORMATION ON
 FUNCTION OF CO2 SENSOR.
 36.DUCT SMOKE DETECTOR IN RETURN AIR
 SHALL BE PRIOR TO ANY MIXINF OF OUTSIDE
 AIR.
 37. NOTE DO NOT RUN AIR CONDITIONING
 EQUIPMENT UNTIL CONSTRUCTION IS
 FINISHED AND CITY MECHANICAL INSPECTOR
 APPROVAL IS GIVEN.
 38. MAINTAIN CLEANLINESS OF DUCT DURING
 CONSTRUCTION.
 39. CONDENSATE DRAIN LINES ARE NOT
 SHOWN.
 40. FIRE DAMPERS WILL BE REQUIRED TO
 MAINTAIN RATING OF VAULT ROOM THREE
 HOUR WALLS.
 41. CONDENSING EQUIPMENT FOR
 COOLERS/FREEZERS SHALL NOT BE IN THE
 COOL AIR STREAM OF ANOTHER UNIT. ENERGY
 EFFICIENCY REQUIREMENTS FOR FLORIDA
 407.1
 42. EXHAUST WILL BE REQUIRED IN AREA OF
 MOP SINKS SHOWN ON FS 2.1 C-32
 CONCESSION PER 1997 SMC 501.4
 THIS DOES NOT INCLUDE REVIEW COMMENTS
 FOR THE ATRIUM SMOKE CONTROL SYSTEM.
 43. CLEARLY INDICATE IF THE DAMPER IS A
 SMOKE FIRE DAMPER, FIRE DAMPER OR SMOKE
 DAMPER ON THE PLAN. THE LOCATION OF ALL
 REQUIRED DAMPERS ARE REQUIRED TO BE
 CLEARLY INDICATED ON THE PLAN BY THE
 DESIGNER BY 1997 610.6.
 44. FLOOR DRAINS INDICATED FOR THE
 CHILLER PLANT WILL NOT BE PERMITTED IF
 THEY WOULD ALLOW FOR THE SPREAD OF
 REFRIGERANT LEAK FROM ONE PART OF THE
 BUILDING TO ANOTHER.
 45. CLEARLY INDICATE ON PLAN THE
 LOCATION OF THE CHILLERS RELIEF PIPE
 TERMINATION SHOWING COMPLIANCE WITH
 1997 SMC 1105.9
 46. HORN AND STROBE FOR CHILLER ROOM
 REFRIGERANT LEAK DETECTORS SHALL BE
 LOCATED INSIDE AND OUTSIDE THE ROOM
 INAREAS WHERE THEY CAN BE SEEN AND
 HEARD.
 47. THE BREATHING APPERATUR REQUIRED
 WILL NEED TO BE LOCATED OUTSIDE OF THE
 CHILLER ROOM.
 48. THE SINGLE DOOR AT THE BACK OF THE
 CHILLER ROOM NEEDS TO HAVE SIGNS
 PROHIBITING ACCESS IN CASE OF A LEAK
 AND EXPLAINING THE DESIRED PROCEDURE.
 49. SIGNS AS REQUIRED BY SMC CH 11 AND
 ASHREA 15 WILL BE REQUIRED.
 50 ACCEPTANCE OF THE REFRIGERANT LEAK
 DETECTION WILL NEED TO BE BY TEST IN
 THE PRESENCE OF THE MECHANICAL
 INSPECTOR AND THE FIRE INSPECTOR,PRIOR
 TO LOADING OF REFIGERANT INTO THE
 CHILLERS OR IF THE CHILLERS ARE SHIPPED
 LOADED, PRIOR TO START UP.
 51. ROOF PLAN SHOWS A SF AND EF
 TOGETHER. WHAT TYPE EQUIPMENT IS THIS
 AND HOW DOES IT COMPLY WITH THE CODE
 REQUIRED TEN FOOT SEPARATION FROM EACH
 OTHER.
 52. WHAT IS THE FUNCTION OF SEF 8? IT
 APPEARS TO BE IN THE AREA OF THE
 SERVICE CORRIDOR, WHICH DOES NOT APPEAR
 TO BE PART OF THE ATRIUM.

Review Stop P PLUMBING
Rev No 15 Status P Date 2003-07-19 Cont ID  
Sent By kstevens Date 2003-07-19 Time 06:24 Rev Time 0.33
Received By kstevens Date 2003-07-19 Time 06:24 Sent To  
Notes
2003-07-19 00:00:00SUBMITTAL OK - CHAINWHEELACTIVATOR

Review Stop P PLUMBING
Rev No 14 Status N Date 2003-07-14 Cont ID  
Sent By kstevens Date 2003-07-14 Time 15:11 Rev Time 0.00
Received By kstevens Date   Time   Sent To  
Notes
2003-07-14 00:00:00THIS SUBJECT HAS BEEN ADDRESSED AT MOST
 OF THE MEETINGS HELD AT THE CONSTRUCTION
 SERVICES CONFERENCE ROOM. THE ANSWER
 GIVEN AT EACH MEETING IS THE SAME AS IT
 WILL BE NOW. THE FIRE LINE DISCHARGE
 SHALL DRAIN INTO THE SANITARY SYSTEM AND
 NOT THE STORM SYSTEM. SECTION 90-203(A)
 STATES, GENERAL PROHIBITION. EXCEPT AS
 PROVIDED IN SECTION 90-205 AND EXCEPT
 PURSUANT TO A VALID NPDES PERMIT, IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO
 DIRECTLY OR INDIRECTLY DEPOSIT, DIS-
 CHARGE, SPILL OR DUMP INTO ANY OF THE
 PUBLIC WATERS OR MUNICIPAL SEPARATE
 STORM SEWER SYSTEM WITHIN THE CITY, ANY
 SUBSTANCE OTHER THAN THAT COMPOSED
 ENTIRELY OF STORMWATER.
 I HOPE THIS WILL BE SUFFICIENT TO PUT
 AN END TO THIS MATTER. THE DISCHARGE OF
 THE FIRE LINES SHALL BE DRAINED TO THE
 CITY SANITARY SYSTEM.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 13 Status P Date 2003-03-24 Cont ID  
Sent By kstevens Date 2003-03-24 Time 13:25 Rev Time 0.50
Received By kstevens Date 2003-03-24 Time 13:24 Sent To  
Notes
2003-03-24 00:00:00SUBMITTALS OK - MIXING VALVES FOR W/H'S

Review Stop P PLUMBING
Rev No 12 Status P Date 2003-03-01 Cont ID  
Sent By kstevens Date 2003-03-01 Time 15:33 Rev Time 0.50
Received By kstevens Date 2003-03-01 Time 15:32 Sent To  
Notes
2003-03-01 00:00:00SUBMITTALS OK - ACCESS PANEL DOORS -
 EXPANSION TANKS - KITCHEN EQUIPMENT SHOP
 DRAWINGS

Review Stop P PLUMBING
Rev No 11 Status P Date 2003-01-30 Cont ID  
Sent By kstevens Date 2003-01-30 Time 17:29 Rev Time 0.10
Received By kstevens Date 2003-01-30 Time 17:28 Sent To  
Notes
2003-01-30 00:00:00SUBMITTAL OK - TRENCH DRAINS W/GALV.
 STEEL GRATES.

Review Stop P PLUMBING
Rev No 10 Status F Date 2003-01-22 Cont ID  
Sent By kstevens Date 2003-01-22 Time 13:36 Rev Time 0.10
Received By kstevens Date 2003-01-22 Time 13:36 Sent To  
Notes
2003-01-22 00:00:00SUBMITTAL DENIED - IN-LINE BOOSTER PUMB
 AND COMPRESSOR DO NOT SHOW LISTING.
 PLEASE SUBMIT LISTING ON BOTH UNITS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 9 Status P Date 2003-01-22 Cont ID  
Sent By kstevens Date 2003-01-22 Time 13:33 Rev Time 1.33
Received By kstevens Date 2003-01-22 Time 13:33 Sent To  
Notes
2003-01-22 00:00:00SUBMITTAL OK - WATER BOOSTER PUMP - U.G.
 SOIL PIPING - PIPE HANGERS - FLOOR SINKS
 DOMESTIC WATER HEATERS - SOLENOID GAS
 VALVE -

Review Stop P PLUMBING
Rev No 8 Status F Date 2003-01-13 Cont ID  
Sent By kstevens Date 2003-01-13 Time 11:23 Rev Time 3.00
Received By kstevens Date 2003-01-13 Time 11:22 Sent To  
Notes
2003-01-13 00:00:00DENIED
 REFERENCE: SPC-94-SGC-97-FACBC-97
  
 1) SHT P2-1.2 REVISION #6 NOT FOUND.
 PLEASE INDICATE REVISION BY CLOUDING.
 2) SHT P2-2.6 10" PIPE UP TO OVERFLOW
 DRAIN BEING ELIMINATED. PLEASE INDICATE
 HOW AREA OF ROOF, (19,045 SQ FT), WILL
 BE DRAINED IF PRIMARY DRAIN IS BLOCKED.
 3) ALL CHANGES FOR SANITARY, WATER, OR
 STORM SYSTEMS SHALL BE SHOWN ON RISER
 DIAGRAMS FOR EACH SYSTEM. PLEASE SUBMIT
 CHANGES FOR RISER DIAGRAMS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 7 Status P Date 2002-12-23 Cont ID  
Sent By kstevens Date 2002-12-23 Time 15:36 Rev Time 0.50
Received By kstevens Date 2002-12-23 Time 15:36 Sent To  
Notes
2002-12-23 00:00:00SUBMITTALS FOR IRRIGATION - OK

Review Stop P PLUMBING
Rev No 6 Status P Date 2002-12-03 Cont ID  
Sent By pschmitz Date 2002-12-03 Time 09:52 Rev Time 0.66
Received By pschmitz Date   Time   Sent To  
Notes
2002-12-03 00:00:00SUBMITTALS FOR ID TAGS FOR PIPING, PES

Review Stop P PLUMBING
Rev No 5 Status P Date 2002-11-09 Cont ID  
Sent By kstevens Date 2002-11-09 Time 14:42 Rev Time 0.25
Received By kstevens Date 2002-11-09 Time 14:41 Sent To  
Notes
2002-11-09 00:00:00SUBMITTAL OK - LAUNDRY TRAY

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-10-29 Cont ID  
Sent By kstevens Date 2002-10-29 Time 15:31 Rev Time 2.00
Received By kstevens Date 2002-10-29 Time 15:31 Sent To  
Notes
2002-10-29 00:00:00SUBMITTALS - PLMG FIXTURES - ANCHORS -
 SUPPORTS - GREASE TRAP - GAS BOILER -
 F.D. TRAP PRIMER - HEATER STAND - THREAD
 ANCHORS - HOSE BIBB/WALL HYDRANT - NO
 HUB COUPLINGS - SHOCK ABSORBER - CIRC.
 PUMPS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-11-15 Cont ID  
Sent By kstevens Date 2001-11-15 Time 17:26 Rev Time 2.00
Received By kstevens Date 2001-11-15 Time 17:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-10-15 Cont ID  
Sent By kstevens Date 2001-10-15 Time 13:03 Rev Time 8.00
Received By kstevens Date 2001-10-15 Time 13:03 Sent To  
Notes
2001-10-15 00:00:00DENIED
 REFERENCE: SPC-94 - SGC-97 - FACBC-97
  
 1) GREASE TRAP, TYPE AND SIZE. CONTACT
 WPB RSTP, ENVIRONMENTAL COMPLIANCE. R
 COMPO (561) 837-4074 ORD #2938-96.
 PLEASE PROVIDE SEATING CAPACITY, BALL-
 ROOM HOLDS 3904. RESPONSE NOTED, BUT NOT
 ADDRESSED FROM PREVIOUS REVIEW.
 2) SHTA1-7.1 - 7.2, PROVIDE CALCULATIONS
 FOR PRIMARY AND SECONDARY STORM DRAINS.
 SEC 1108 AND 1109 + 1/2 THE AREA OF THE
 VERTICAL WALLS, UPPER ROOFS DRAINING TO
 LOWER ROOFS TO BE INCLUDED. CALCULATIONS
 ARE REQUIRED TO CHECK PIPE SIZES.
 3) SHT P1-1.1 AHU CONDENSATE DRAIN DE-
 TAIL, COMPLY W/SEC 104.2 & 104.3 PLANS &
 SPECS., PROVIDE AN ISOMETRIC DRAWING OF
 A COMMON A/C CONDENSATE SYSTEM, CONNECT-
 ED TO STORM DRAINAGE SYSTEM OUTSIDE OF
 BUILDING WITH A OVERFLOW VENT 6" ABOVE
 GRADE AS REQUESTED IN PREVIOUS REVIEW.
 4) SHT P2-1.1 CONDENSATE TIED INTO STORM
 INSIDE BLDG AT INTERSECT. OF COLS B & 4
 VOL III.
 5) SHT P2-1.1 COMPLY W/SEC 714 MAXIMUM
 FIXTURE LOAD ON THE DWV SYSTEM. SHOW
 FIXTURE UNIT LOAD THROUGHOUT SYSTEM. SEC
 104.2 (TALK TO GEORGE HAZAU)
 6) SHT P2-1.3, CAN WASH & TRASH COMPACT-
 OR, CONNECT TO GREASE WASTE. LOCAL ORD
 #2938-96. STK DIAG. "H" SANT SHOWS CAN
 WASH STILL ON SANT. SHT P3-2.3
 7) SHT P3-2.2, STACK "D", "Q" PLBG. FIX-
 TURES FROM UPPER FLOORS SHALL NOT DIS-
 CHARGE INTO A BATTERY VENTED BRANCH.
 SHOW UPPER FLOOR DISCHARGING INTO SEPAR-
 ATE 4" LINE THAT FLOOR DRAINS ARE DRAIN-
 ING INTO.
 8) SHTP3-2.1 THRU P3-2.4 STK DIAGRAMS.
 STK "D" ISOMETRIC DOES NOT MATCH FLAT
 DRAWING, FLOOR DRAIN BY D.F. ARE ALL FD
 VENTS TYPICAL IN REST ROOMS?
 9) SHOP DRAWING SHALL BE PROVIDED FOR
 THE U/G UTILITY SERVICE BOX FROM THE
 MANUFACTURE TO SHOW HOW THERE IS NOT A
 CROSS CONNECTION OF WASTE AND POTABLE
 WATER SEC 601.5 AS REQUESTED IN PREVIOUS
 REVIEW.
 GAS PERMIT REQUIREMENTS
 10) GAS ISOMETRIC ON SHT P4-1.3 HEADER
 IN KITCHEN TO BE UNIFORM. SHOWS 4" TO 3"
 TO 2-1/2" THEN BACK TO 4". ALSO SEDIMENT
 TRAP SHALL BE UPSTREAM OF EQUIPMENT NOT
 AND END OF LINE AS SHOWN.
 11) CALCULATIONS FOR COMBUSTION AIR.
 SHOW COMBUSTION AIR FOR BOILER AND CALCS
 WATER HEATERS DIRECT VENT THRU ROOF NOT
 SHOWN.
 12) INDICATE DELIVERY PRESSURE. FPU
 DELIVERS 12" TO 14" WC - .5 PSI
 13) SUBMIT DETAIL SHOWING THE TYPE, SIZE
 LOCATION, AND TERMINATION OF GAS VENTS.
  
 REVIEW BY PAUL SCHMITZ/KEN STEVENS
 (561) 659-8096 EXT. 8233/8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-06 Cont ID  
Sent By pschmitz Date 2001-08-05 Time 13:30 Rev Time 18.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-08-05 00:00:00PLUMBING PLAN REVIEW, DENIED.
 CODE REFEREMCES,SBC-97,SGC-97 SPC-94
 FL ACCESSIBILIY CODE REVISED-98
 VOLUME (I)
 (1) FOOD SERVICE ESTABLISHMENTS,REQUIRE
 PLAN REVIEW/WITH COMMENTS PRIOR TO PLBG
 PLAN REVIEW,CONTACT DEPARTMENT OF HOTEL
 BUSINESS REGULATION, 954-958-5520.
 (2) GREASE TRAP,TYPE AND SIZE. CONTACT
 W PALM BCH RSTP,ENVIROMENTAL COMPLIANCE.
 RODNEY COMPO 561-837-4074 ORD# 2938-96.
 (3) SHT A1-7.1-7.2, PROVIDE CALCULATIONS
 FOR THE PRIMARY & SECONDARY STORM DRAINS
 SEC 1108.1,2,3,4,5,ONE HALF THE AREA OF
 VERTICAL WALLS, UPPER ROOFS DRAINING TO
 LOWER ROOFS, TO BE INCLUDED.
 (4) SHT A5-8.3 DETAIL #20, H/C,W/C FLUSH
 HANDLES TO COMPLY W/SEC 4.16.5, SHALL
 BE ON THE MOUNTING SIDE OF FIXTURE.
 (5)SHT D1-0.0,2.1 FINISH LEGEND,UNGLAZED
 FLOOR TILE, T-2,T-4,T-5,COMPLY W/SBC-97
 1204.2,NON ABSORBENT FLOOR SURFACE.
 VOLUME (II)
 (6) SHT INDEX: MINIMUM FACILITIES, SHOW
 NUMBER OF DRINKING FOUNTAINS,USE,TAB 407
 AND FACBC-98 REV,SEC 4.1.3 (A)(B).
 VOLUME (III) & (IV)
 (7) SHT P4-1.1 AHU CONDENSATE DRAIN DE-
 TAIL, COMPLY W/SEC 104.3 PLANS & SPEC'S,
 PROVIDE A ISOMETRIC DRAWING OF A COMMON
 A/C CONDENSATE SYSTEM,CONNECTED TO STORM
 DRAINAGE SYSTEM OUTSIDE OF BUILDING WITH
 A RELIEF VENT 6" ABOVE GRADE.
 (8) SHT P1-1.1, WATER HAMMER ARRETORS,TO
 BE INSTALLED AS PER MFG. INSTALLATION
 INSTRUCTIONS FOR SIZE AND PLACEMENT.
 SEC 607.8.2, INSTALLED AS PER PDI-WH201
 (9) SHT P2-1.1 COMPLY W/SEC 714 MAXIMUM
 FIXTURE LOAD ON THE DWV SYSTEM. SHOW
 FIXTURE UNIT LOAD THRU OUT SYSTEM.
 (10) SHT P4-2.2,2.4, CAN WASH AND TRASH
 COMPACTOR, CONNECT TO GREASE WASTE.
 LOCAL ORDINANCE # 2938-96.
 (11) SHT P4-2.1,2.3, STACK "D","Q",
 PLBG FIXTURES FROM UPPER FLOORS, SHALL
 NOT DISCHARGE INTO A BATTERY VENTED
 BRANCH SPC-95 SEC 914.1
 (12) SHT P4-1.1 EWH DETAIL,TO BE READILY
 ACCESSIBLE,SEC 501.7, PROVIDE A DETAIL
 OF A WORKING PLATFORM W/ A SHIPS LADDER,
 OR SET THE DWH THE ON FLOOR.
 SEC 507.8.2, MIN.SIZE PAN DRAIN, 1".
 DWH DRAINS,SEC 802,ALL I/D WASTE TO F/S.
 (13) SHT P3-1.5 ALCOVE DWV SYSTEM DESIGN
 COMLPY WITH 921.1, COMBINATION WASTE AND
 VENT SYSTEM. THIS SHOULD BE TYPICAL FOR
 CONSESSION AND FOODN SERVICE SYSTEMS.
 (14) SHT P4-2.1 THRU 2.4,STACK DIAGRAMS.
 CIRCUIT AND LOOP, BRANCH SOIL OR WASTE
 PIPE SHALL BE UNIFORM THROUGH ITS ENTIRE
 LENGTH. SEC 914.1
 (15A) SHT P2-1.1 TO 1.8, EXHIBIT HALL
 U/G DWV SYSTEM PIPING,TO COMPLY WITH SEC
 921, COMBINATION WASTE AND VENT SYSTEM.
 ONE VENT UPSTREAM, BETWEEN THE LAST TWO
 FIXTURE DRAINS, ONE VENT DOWN STREAM,
 BEFORE THE FIRST FIXTURE DRAIN.
 SEE ILLUSTRATION APPEX "J" PG.275,ALSO
 SEE DIFINITIONS CH-2 FIXTURE DRAIN AND
 FIXTURE BRANCH.
 (15B) PROVIDE SHOP DRAWINGS FOR THE U/G
 UTILITY SERVICE BOX,FROM THE MANUFACTURE
 TO SHOW HOW THERE IS NOT A CROSS CONNECT
 ION OF WASTE AND POTABLE WATER,SEC 601.5
 (16)SHT P2-1.1 THRU 4.1, SEC 104.3 PLANS
 PROVIDE ISOMETRIC DRAWINGS OF THE WATER
 PIPING SYSTEM, WITH CALCULATIONS FOR THE
 DISCHARGE FIXTURE UNIT DEMAND.
 NO MORE THAN TWO FIXTURES 0N 1/2" C/W.
 NO MORE THAN FOUR FIXTURES ON 1/2" H/W.
 MODEL CNTY WIDE AMENDMENTS, SPC-94,607.7
  
 GAS PERMITREQUIRMENTS
 CODE REFERENCES SGC-97,NFPA-54
 (17A) SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE,
 CORRESPONDING LENGTHS AND PIPE SIZES.
 (B) TYPE OF PIPING MATERIAL, ALL PIPE
 SIZES, TYPE OF GAS, BTU LOAD OF EACH
 APPLIANCE AND TOTAL BTU LOAD ON SYSTEM.
 (C) SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY,TO THE MOST REMOTE OUTLET IN
 THE BUILDING. (TOTAL DEVELOPED LGTH)
 (D) CALCULATIONS FOR COMBUSTION AIR
 (E) INDICATE DELIVERY PSI, (2# OR .5#).
 (F) SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE, TERMINATION OF GAS VENTS
 (G) SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT,TO VERIFY COMPLIANCE WITH
 LOCAL CODES.
 (H) SHOW LOCATION OF GAS METER.
 (I) SPECIFY, SIZE & TYPE OF REGULATORS.
 REQUIRED FOR THIS SYSTEM.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096 X 8233

Review Stop Z ZONING
Rev No 4 Status P Date 2004-05-20 Cont ID  
Sent By mmclean Date 2004-05-20 Time 11:25 Rev Time 0.00
Received By mmclean Date 2004-05-20 Time 11:25 Sent To I
Notes
2004-05-20 00:00:00ERIC SCHNEIDER, SENIOR PLANNER ONLY
 APPROVING, FIELD BULLETIN 44, FIELD
 BULLENTIN 52A AND LANDSCAPE SHEET L-5.
 NEEDS FIRE & ENG TO REVIEW MM

Review Stop Z ZONING
Rev No 3 Status P Date 2004-01-08 Cont ID  
Sent By mmclean Date 2004-01-08 Time 15:50 Rev Time 0.00
Received By mmclean Date 2004-01-08 Time 15:50 Sent To I
Notes
2004-01-08 00:00:00ERIC SCHNEIDER SENIOR PLANNER APPROVED

Review Stop Z ZONING
Rev No 2 Status P Date 2003-07-17 Cont ID  
Sent By sgraham Date 2003-07-17 Time 08:46 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-07-17 00:00:00APPROVED BY ESCHINEIDER, WESTERN MOST
 TREE MUST BE PLANTED WHERE BUFFER BEGINS
 TO WIDEN TO FIVE FEET

Review Stop Z ZONING
Rev No 1 Status P Date 2002-12-12 Cont ID  
Sent By btrobaug Date 2002-11-22 Time 17:33 Rev Time 1.00
Received By btrobaug Date   Time   Sent To  
Notes
2001-11-13 00:00:00 
 "PROVISO"
 -------
  
 SHEET A1-1.4 PORTION 4 -- SW FIRE
 DEPARTMENT ACCESS TO BE PERMITTED UNDER
 SEPERATE PERMIT. NOT APPROVED AS PART
 OF THIS PERMIT-ERIC SCHNEIDER 659-8031


Account Summary | Usage Policy | Privacy Policy