| Plan Review Stops For Permit 01071404 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-09-13 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-09-13 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-09-13 00:00:00 | PROVISO:THE BASEMENT HAS BEEN REVIEWED | | | FOR SINGLE TENANT USE ONLY AND THAT | | | EXIT ACCESS WILL BE MAINTAINED TO TWO | | | INDEPENDENT EXITS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
C |
Date |
2001-08-16 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-08-16 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-08-16 00:00:00 | WHAT IS THE CURRENT USE OF THE | | | BASEMENT?PLEASE DECLARE USES AT TIME OF | | | PERMIT APPLICATION. | | | | | | SEE SBC 704.1.1 SBC 704.3 AND SBC | | | 1001.13 AND DESIGN AS NECESSARY FOR THE | | | BASEMENT AREA. | | | | | | THE PLANS COVER SHEET CITES THE 1999 | | | SBCCITHE CITY CURRENTLY INVOKES THE | | | 1997 SBCCI AS AMENDED. | | | | | | THE NORTH ARROW IS INCORRECT ON THE | | | LOCATION PLAN. | | | | | | SHEET A2.2, INSURE THAT HC ACCESS IS | | | PROVIDED TO THE CUSTOMER SERVICE AREA | | | AND COUNTERS AS REQUIRED BY THE FACBC. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-09-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-09-10 |
Time |
18:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-09-10 |
Time |
18:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-08-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-14 |
Time |
21:20 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-14 |
Time |
21:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-09-11 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-09-11 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-08-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-07 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-07 |
Time |
08:36 |
Sent To |
|
|
| Notes |
| 2001-08-07 00:00:00 | 1) FIRE ALARM NOTES INDICATES CLASS B, | | | STYLE C FIRE ALARM CIRCUITS. ONLY | | | CLASS A, STYLE D CIRCUITS ARE | | | PERMITTED. | | | 2) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER AND FIRE ALARM | | | REMODEL. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-09-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-09-11 |
Time |
14:15 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2001-09-11 |
Time |
14:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-08-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-08-15 |
Time |
10:46 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-08-15 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2001-08-15 00:00:00 | ******************PROVISO*************** | | | | | | | | | AS PER AMENDED 1997 SMC 304.2.5, A | | | MINIMUM OF 18" BETWEEN THE ROOF SURFACE | | | AND THE BOTTOM OF THE CONDENSING UNIT | | | SUPPORT RAIL. | | | | | | PLEASE PROVIDE A DETAIL AND SIZE OF DRY | | | WELL FOR AHU CONDENSATE. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-09-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-09-06 |
Time |
08:55 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-09-06 |
Time |
08:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2001-08-15 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-08-15 |
Time |
16:09 |
Rev Time |
0.75 |
| Received By |
jleech |
Date |
2001-08-15 |
Time |
16:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-09-11 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-09-11 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|