Plan Review Details - Permit 01071404
Plan Review Stops For Permit 01071404
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-09-13 Cont ID  
Sent By hpiskura Date 2001-09-13 Time 08:15 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-09-13 00:00:00PROVISO:THE BASEMENT HAS BEEN REVIEWED
 FOR SINGLE TENANT USE ONLY AND THAT
 EXIT ACCESS WILL BE MAINTAINED TO TWO
 INDEPENDENT EXITS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status C Date 2001-08-16 Cont ID  
Sent By hpiskura Date 2001-08-16 Time 10:21 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-08-16 00:00:00WHAT IS THE CURRENT USE OF THE
 BASEMENT?PLEASE DECLARE USES AT TIME OF
 PERMIT APPLICATION.
  
 SEE SBC 704.1.1 SBC 704.3 AND SBC
 1001.13 AND DESIGN AS NECESSARY FOR THE
 BASEMENT AREA.
  
 THE PLANS COVER SHEET CITES THE 1999
 SBCCITHE CITY CURRENTLY INVOKES THE
 1997 SBCCI AS AMENDED.
  
 THE NORTH ARROW IS INCORRECT ON THE
 LOCATION PLAN.
  
 SHEET A2.2, INSURE THAT HC ACCESS IS
 PROVIDED TO THE CUSTOMER SERVICE AREA
 AND COUNTERS AS REQUIRED BY THE FACBC.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-09-10 Cont ID  
Sent By dpalmer Date 2001-09-10 Time 18:38 Rev Time 0.00
Received By dpalmer Date 2001-09-10 Time 18:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-08-14 Cont ID  
Sent By dpalmer Date 2001-08-14 Time 21:20 Rev Time 0.00
Received By dpalmer Date 2001-08-14 Time 21:19 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-09-11 Cont ID  
Sent By lsmith Date 2001-09-11 Time 08:48 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-08-07 Cont ID  
Sent By mcarsill Date 2001-08-07 Time 08:37 Rev Time 0.00
Received By mcarsill Date 2001-08-07 Time 08:36 Sent To  
Notes
2001-08-07 00:00:001) FIRE ALARM NOTES INDICATES CLASS B,
 STYLE C FIRE ALARM CIRCUITS. ONLY
 CLASS A, STYLE D CIRCUITS ARE
 PERMITTED.
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER AND FIRE ALARM
 REMODEL.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-09-11 Cont ID  
Sent By pkrauss Date 2001-09-11 Time 14:15 Rev Time 0.30
Received By pkrauss Date 2001-09-11 Time 14:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-08-15 Cont ID  
Sent By pkrauss Date 2001-08-15 Time 10:46 Rev Time 0.50
Received By pkrauss Date 2001-08-15 Time 10:33 Sent To  
Notes
2001-08-15 00:00:00******************PROVISO***************
  
  
 AS PER AMENDED 1997 SMC 304.2.5, A
 MINIMUM OF 18" BETWEEN THE ROOF SURFACE
 AND THE BOTTOM OF THE CONDENSING UNIT
 SUPPORT RAIL.
  
 PLEASE PROVIDE A DETAIL AND SIZE OF DRY
 WELL FOR AHU CONDENSATE.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-09-06 Cont ID  
Sent By kstevens Date 2001-09-06 Time 08:55 Rev Time 0.33
Received By kstevens Date 2001-09-06 Time 08:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-08-15 Cont ID  
Sent By jleech Date 2001-08-15 Time 16:09 Rev Time 0.75
Received By jleech Date 2001-08-15 Time 16:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2001-09-11 Cont ID  
Sent By lsmith Date 2001-09-11 Time 08:48 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***