Plan Review Details - Permit 01071397
Plan Review Stops For Permit 01071397
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-11-22 Cont ID  
Sent By jwitmer Date 2001-11-22 Time 09:41 Rev Time 0.25
Received By jwitmer Date   Time   Sent To  
Notes
2001-11-22 00:00:00REVISION 11/16/01

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-09-21 Cont ID  
Sent By jwitmer Date 2001-09-21 Time 13:23 Rev Time 0.50
Received By jwitmer Date 2001-09-21 Time 13:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-09-11 Cont ID  
Sent By jwitmer Date 2001-09-11 Time 07:20 Rev Time 1.00
Received By jwitmer Date 2001-09-11 Time 07:20 Sent To  
Notes
2001-09-11 00:00:00BUILDING PLAN REVIEW
 01071397
 701 S ROSEMARY/ # 103
 SCHIAPPA CONST
 TEL: (954) 658-7493
  
 1 SBC 903.1 AN APPROVED FIRE SPRINKLER
 AND DEVICES SHALL BE USED IN AUTOMATIC
 FIRE SPRINKLER SYSTEMS AND THE COMPLETE
 LAYOUT OF THE SYSSTEM.
  
 2)- SBC 905.1 FIRE ALARM SYSTEM NO PLANS
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-08-14 Cont ID  
Sent By jwitmer Date 2001-08-14 Time 15:20 Rev Time 3.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-08-14 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW 01071397
 701 S ROSEMARY# 103
 SCHIAPPA CONST CORP
 TEL: 954/ 658- 7493
  
 1)- SHEET A-4 ELEVATION #2 FIXED GLASS
 IS THIS EXISTING OR IS THIS PART OF THE
 BUILD OUT? THE SAME ISSUE WITH THE FRONT
 DOORS? IF PART OF THE TENANT BUILD OUT
 PRODUCT TESTING FOR GLAZED OPENINGS WILL
 BE REQUIRED, 2 COPIES OF PRODUCT TESTING
 FOR LARGE MISSLE IMPACT RESISTANCE TEST-
 ING, SBCCI OR DADE COUNTY ACCEPTED.
  
 2)- SHEET A-2 / A-8 BACK EXIT STAIRS,
 VERTICAL ACCESSIBILITY, FL ACC CODE
 4.1.3.(9) AN ACCESIBILE MEANS OF EGRESS
 SHALL BE PROVIDED IN THE SAME NUMBER AS
 REQUIRED FOR EXITS BY LOCAL BUILDING /
 LIFE SAFETY REGULATIONS.
  
 3)- SBC 903.1 AN APPROVED FIRE SPRINKLER
 AND DEVISES SHALL BE USSED IN AUTOMATIC
 SPRINKLKER SYSTEMS AND THE COMPLETE LAY-
 OUT OF THE SYSTEM.
  
 4)- SBC 905.1FIRE ALARM SYSTEM NO PLANS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2002-01-08 Cont ID  
Sent By dpalmer Date 2002-01-08 Time 05:42 Rev Time 0.00
Received By btrobaug Date 2002-01-08 Time 05:42 Sent To M
Notes
2002-01-08 00:00:00******************* UNSAT **************
  
  
 1)NOTE: PLEASE NOTE THAT THE AIC RATINGS
 FOR MLO PANEL"H" HAS BEEN CHANGED TO
 14,000. PLEASE NOTE THAT PER AIC
 CALCULATIONS ON PLANS, 14,000 IS NOT
 ENOUGH. PLEASE NOTE THAT BRKRS IN PANEL
 NEED TO BE CHANGED OUT BACK TO THE
 22,000 AS ORIG CALCULATED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-12-18 Cont ID  
Sent By dpalmer Date 2001-12-18 Time 08:26 Rev Time 0.00
Received By dpalmer Date 2001-12-18 Time 08:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-09-24 Cont ID  
Sent By dpalmer Date 2001-09-24 Time 09:43 Rev Time 0.00
Received By dpalmer Date 2001-09-24 Time 09:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-09-10 Cont ID  
Sent By dpalmer Date 2001-09-10 Time 19:32 Rev Time 0.00
Received By dpalmer Date 2001-09-10 Time 19:16 Sent To  
Notes
2001-09-10 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT CLEARENCES FOR
 TRANSFORMER AND DISCONNECT DOES NOT
 SEEM TO MEET 110-26. PLEASE CALRIFY
  
 2)NOTE: PLEASE NOTE THAT LOAD CALCULAT-
 -IONS FOR TRACK LIGHTING NOT SHOWN PER
 220-12B. PLANS SHOW 48' OF TRACK? AT
 150W PER 2', SHOULD SHOW AT 7200W.
 PLEASE CLARIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-14 Cont ID  
Sent By dpalmer Date 2001-08-14 Time 18:43 Rev Time 0.00
Received By dpalmer Date 2001-08-14 Time 18:43 Sent To  
Notes
2001-08-14 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT TRANSFORMER IS
 BEING SHOWN INSTALLED IN A STORAGE
 ROOM?PLEASE NOTE 110-26 FOR THIS SPACE
 TO BE DEDICATED ELEC.
  
 2)NOTE: PLEASE NOTE THAT THE DISCONNECT
 SHOWN ON RISER DIAGRAM IS NOT SHOWN ON
 PLANS. PLEASE NOTE 240-21 FOR 10' TAP
 RULE FOR REQ`D DISCONNECT FOR SECONDARY
 OF TRANSFORMER ALSO OCP REQ`D PER 384-16
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE SUBMIT FOR DISCONNECT FROM
 TRANSFORMER TO PANEL"A".
  
 4)NOTE: PLEASE CLARIFY BOX SHOWN AS "J"
 ON TRANSFORMER? JUNCTION BOX?
  
 5) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC) PER 215-3/230-42
  
 6)NOTE: PLEASE SHOW LOAD CALCULATIONS
 FOR TRACK LIGHTING PER 220-12B.
  
 7)NOTE: PLEASE CLARIFY GROUNDING
 ATTACH--MENT FOR TRANSFORMER PER 250-30.
  
 PLEASE SUBMIT ALL OF THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-08-15 Cont ID  
Sent By lsmith Date 2001-08-15 Time 13:27 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-09-25 Cont ID  
Sent By mcarsill Date 2001-09-25 Time 13:29 Rev Time 0.00
Received By mcarsill Date 2001-09-25 Time 13:28 Sent To  
Notes
2001-09-25 00:00:001)FIRE SPRINKLER AND FIRE ALARM PLANS
 HAVE BEEN RECIEVED.
  
 CAPTAIN MIKE CARSILLO
 659 8096 EXT 8497
 835- 2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-09-05 Cont ID  
Sent By mcarsill Date 2001-09-05 Time 10:21 Rev Time 0.00
Received By mcarsill Date 2001-09-05 Time 10:21 Sent To  
Notes
2001-09-05 00:00:001) NOT ALL PREVIOUS PLAN REVIEW
 COMMENTS ADDRESSED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-07-31 Cont ID  
Sent By mcarsill Date 2001-07-31 Time 14:54 Rev Time 0.00
Received By mcarsill Date 2001-07-31 Time 14:53 Sent To  
Notes
2001-07-31 00:00:001) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS. PLEASE PROVIDE FIRE
 SPRINKLER DRAWINGS WITH NEXT SUBMITTAL.
 2) NO FIRE ALARM EQUIPMENT SHOWN ON
 PLANS. PLEASE PROVIDE LOCATIONS OF ALL
 FIRE ALARM DEVICES WITHIN TENANT
 SPACE.
 3) PLEASE PROVIDE AN OCCUPANT LOAD
 COUNT AND LIFE SAFETY PLAN TO THIS
 OFFICE.
 4) WRONG EDITION OF THE STANDARD
 BUILDING CODE REFERENCED. SHOULD READ
 1997 EDITION.
 5) PLEASE INDICATE EXIT DISCHARGE
 LOCATIONS FOR ALL EXIT DOORS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-01-08 Cont ID  
Sent By pkrauss Date 2002-01-08 Time 12:40 Rev Time 0.30
Received By pkrauss Date 2002-01-08 Time 12:39 Sent To  
Notes
2002-01-08 00:00:00MECH PERMIT 01100107

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-09-21 Cont ID  
Sent By dpalmer Date 2002-01-08 Time 05:48 Rev Time 1.00
Received By pkrauss Date 2001-09-20 Time 15:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-08-15 Cont ID  
Sent By pkrauss Date 2001-08-15 Time 11:52 Rev Time 1.00
Received By pkrauss Date 2001-08-15 Time 11:07 Sent To  
Notes
2001-08-15 00:00:00********************DENIED**************
  
  
 PLEASE INDICATE ON PLAN WHERE THE
 OVERFLOW FOR THE FCU AUXILIARY DRAIN
 PAN TERMINATES.THIS LINE SHALL
 TERMINATE AT A CONSPICUOUS POINT TO
 SERVE AS AN ALARM THAT THE REGULAR
 DRAIN IS RESTRICTED.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-09-21 Cont ID  
Sent By pschmitz Date 2001-09-21 Time 14:12 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-09-21 00:00:00MEET WITH ARCH. REX NICHOLS,PROVISO ON
 PREVIOUS COMMENTS, WITH REVISIONS TO
 FOLLOW BEFORE FINAL.PES

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-09-06 Cont ID  
Sent By pschmitz Date 2001-09-06 Time 10:55 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-09-06 00:00:00PLUMBING PLAN REVIEW, DENIED.
 PREVIOUS COMMENTS NOT ADDRESSED
 (1)SHT A-12 ELVATION DETAIL REQUIRED FOR
 BREAK RM SINK,FACBC-94 SEC 4.24 HGTH 34"
 FF, KNEE CLEARANCE, CLEAR FLR SPACE.
 (2) SHT A-2 CONFLICTS WITH SHT P-2,
 PLBG FIXTURE LEGEND CALLS FOR A HILO D/F
 SHTA-2 ONLY HAS SPACE FOR A SINGLE D/F?
 (3) SHT P-1 WATER HEATER INSTALLED ABOVE
 CEILING, SEC 501.7 W/H TO BE READLY ACCE
 SSIBLE, SHOW A DETAIL OF A WORKING PLAT
 FORM WITH A SHIPS LADDER FIXED IN PLACE.
 (4A) SHT P-2 PLBG NOTE #14 REFERENCE TO
 AIR CHAMBERS,SEC 607.8.3 TO BE ACCESSBLE
 AND RECHARGEABLE, OR DELETE NOTE.
 (B) WATER RISER DETAIL, SHOCK ARESSTORS
 ARE NOT SHOWN AS REQUIRED BY MFG FOR
 LOCATION AND PLACEMENT.
 (5) SHT A-12 MEM & WOMENS H/C REST ROOM
 STALL,SHALL COMPLY W/FACBC SEC 4.17.3&
 FIG 30E,FOR SIZE AND ARRANGMENT OF PLBG
 FIXTURES,INC INCLUDE ALL DIMENSIONS.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 561-659-8096X8233

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-09-06 Cont ID  
Sent By pschmitz Date 2001-09-06 Time 10:57 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-09-06 00:00:00SEE COMMENTS DATED 9-6-01 PES

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-09 Cont ID  
Sent By jleech Date 2001-08-09 Time 20:04 Rev Time 1.50
Received By jleech Date 2001-08-09 Time 20:04 Sent To  
Notes
2001-08-09 00:00:00DENIED;
 1.LOUNGE SINK SHALL COMPLY WITH FACBC
 4.24.2
 2.DRINKING FOUNTAIN TO COMPLY WITH 4.13
 (10) PROVISIONS SHALL BE MADE FOR
 PEOPLE WHO HAVE TROUBLE BENDING AND
 STOOPING.
 3.THE WATER HEATER SHALL BE READILY
 ACCESSIBLE. IF INSTALLED ABOVE FINISH
 FLOOR A FIXED SHIPS LADDER SHALL BE
 INSTALLED.
 4.WATER HEATER PAN DRAIN MINIMUM SIZE IS
 1" SPC SEC. 507.8.2
 5.NOTE 14. WATER HAMMER ARRESTERS SHOULD
 BE SIZED BY THE ENGINEER AND INSTALLED
 PER MANUFACTORS RECOMMENDATIONS. SEC.
 607.8.2 AND 608.8.3.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369

Review Stop Z ZONING
Rev No 1 Status N Date 2001-08-15 Cont ID  
Sent By lsmith Date 2001-08-15 Time 13:28 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***