Plan Review Details - Permit 01071384
Plan Review Stops For Permit 01071384
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-05-16 Cont ID  
Sent By jwitmer Date 2002-05-16 Time 07:57 Rev Time 0.15
Received By jwitmer Date   Time   Sent To  
Notes
2002-05-16 00:00:00TYPEIII 2ND FL INTERIOR SHUTTER MOUNT
 IST FL EXTERIOR SHUTTER MOUNT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-01-10 Cont ID  
Sent By jwitmer Date 2002-01-10 Time 12:23 Rev Time 1.25
Received By jwitmer Date 2002-01-10 Time 06:57 Sent To  
Notes
2002-01-10 00:00:00BUILDING TYPE V
 MASTER: 01071384
 BUILDING PROVISO:
 NO SURVEY WITH PLANS, TABLE 600 ISSUES
 CAN NOT BE ADDRESSED (WINDOW OPENINGS VS
 PROPERTY LINE). THIS CONCERN WILL BE
 ADDRESSED ON A INDIVIDUAL BASIS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-11-28 Cont ID  
Sent By jwitmer Date 2001-11-28 Time 18:49 Rev Time 0.50
Received By jwitmer Date 2001-11-28 Time 18:40 Sent To  
Notes
2001-11-28 00:00:00BUILDING PLAN REVIEW
 PLAN REVIEW 01071384
 TYPE III MODEL "FFEEFF"
 CONT: TRANSEASTERN
 TEL: 753-5531
  
 SEE COMMENTS UNDER 010713374

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-23 Cont ID  
Sent By dpalmer Date 2001-10-23 Time 21:16 Rev Time 0.00
Received By dpalmer Date 2001-10-23 Time 21:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-21 Cont ID  
Sent By dpalmer Date 2001-08-21 Time 08:51 Rev Time 0.00
Received By dpalmer Date 2001-08-21 Time 08:51 Sent To  
Notes
2001-08-21 00:00:00****************** UNSAT ***************
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE THAT NO RATINGS SHOWN FOR
 LOAD CENTER.
  
 2) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-11-19 Cont ID  
Sent By mcarsill Date 2001-11-19 Time 11:41 Rev Time 0.00
Received By mcarsill Date 2001-11-19 Time 11:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2001-10-04 Cont ID  
Sent By mcarsill Date 2001-10-04 Time 16:47 Rev Time 0.00
Received By mcarsill Date 2001-10-04 Time 16:47 Sent To  
Notes
2001-10-04 00:00:00NOT ALL PREVIOUS PLAN REVIEW COMMENTS
 ADDRESSED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-08-07 Cont ID  
Sent By mcarsill Date 2001-08-07 Time 14:29 Rev Time 0.00
Received By mcarsill Date 2001-08-07 Time 14:29 Sent To  
Notes
2001-08-07 00:00:001) NO SITE PLAN INDICATING WHERE
 BUILDING WILL BE BUILT.
 2) NO FIRE HYDRANT LOCATION MAP. WET
 FIRE HYDRANTS ARE REQUIRED PRIOR TO,
 DURING AND AFTER CONSTRUCTION.
 3) BUILDING ADDRESSES REQUIRED.
 4) ARE THESE BUILDINGS RENTALS OR
 OWNED.
 5) TENANT SEPARATIONS TO COMPLY WITH
 BUILDING CODE REQUIREMENTS.
 6) ELECTRIC POWERED SMOKE DETECTORS
 ARE REQUIRED. WHEN ACTIVATED, THESE
 DEVICES ARE TO BE AUDIBLE IN THE
 SLEEPING ROOMS OF THAT UNIT.
 7) PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED.
 8) STORAGE NOT PERMITTED UNDER STAIRS
 UNLESS PROPERLY FIRE RATED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-12-04 Cont ID  
Sent By pkrauss Date 2001-12-04 Time 14:05 Rev Time 2.00
Received By pkrauss Date 2001-12-04 Time 13:54 Sent To Z
Notes
2001-12-04 00:00:00******************PROVISO***************
  
  
 EXHAUST DUCT FOR DRYER SHALL NOT EXCEED
 25'.THERE SHALL BE DEDUCTION OF 2
 1/2' FOR EACH 45 DEGREE BEND AND 5' FOR
 EACH 90 DEGREE BEND.THE WALL OR ROOF
 CAP SHALL BE NONSCREENED WITH A BACK
 DRAFT DAMPER.
  
 PLEASE INDICATE HOW COMBUSTIBLE LINT
 WILL BE REMOVED (CLEANOUTS).
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-10-13 Cont ID  
Sent By pkrauss Date 2001-10-13 Time 10:09 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
2001-10-13 00:00:00NO MECH PLANS SUBMITTED

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-10-13 Cont ID  
Sent By pkrauss Date 2001-10-13 Time 10:08 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
2001-10-13 00:00:00NO MECH AS PER N. DENMARK 8-23-01

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-01-11 Cont ID  
Sent By kstevens Date 2002-01-11 Time 17:30 Rev Time 0.50
Received By kstevens Date 2002-01-11 Time 17:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-11-21 Cont ID  
Sent By kstevens Date 2001-11-21 Time 21:05 Rev Time 0.50
Received By kstevens Date 2001-11-21 Time 21:05 Sent To  
Notes
2001-11-21 00:00:00DENIED
  
 1) PAGES A-3/A-10 "E" UNITS MASTER EXTRA
 LAV SHOWN ON RISER DIAGRAM, NOT ON FLOOR
 PLAN. 2ND NOTICE.
  
 2) THIRD NOTICE - APPROVED UTILITY PLAN
 REQUIRED FOR FINAL PLUMBING PLAN REVIEW.
  
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-10-29 Cont ID  
Sent By kstevens Date 2001-10-29 Time 11:23 Rev Time 0.50
Received By kstevens Date 2001-10-29 Time 11:22 Sent To  
Notes
2001-10-29 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) APPROVED UTILITY PLANS ARE REQUIRED
 FOR FINAL PLUMBING PLAN REVIEW OF BUILD-
 INGS.
  
 2) PAGES A-3/A-10 "F" UNITS M/BATH, 2
 LAVS ON FLOOR PLAN - 1 ON RISER DIAGRAM
 PLEASE CLAIRFY.
  
 3) PAGES A-3/A-10 "E" UNITS M/BATH, W/C
 TO BE SHOWN IN M/B BY LAV AND SHOWER.
 EXTRA LAV SHOWN ON RISER DIAGRAM NOT ON
 FLOOR PLAN. PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-08-16 Cont ID  
Sent By jleech Date 2001-08-16 Time 17:21 Rev Time 0.00
Received By jleech Date   Time   Sent To  
Notes
2001-08-16 00:00:00SEE PLAN REVIEW COMENTS UNDER 01071374

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2002-01-22 Cont ID  
Sent By drunnels Date 2002-01-22 Time 11:16 Rev Time 0.00
Received By drunnels Date   Time   Sent To  
Notes
2002-01-22 00:00:00SEE BUILDING REVIEWS

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-08-27 Cont ID  
Sent By hpiskura Date 2001-08-27 Time 11:31 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-08-27 00:00:00SEE NOTES ON 01071374

Review Stop Z ZONING
Rev No 1 Status P Date 2001-12-10 Cont ID  
Sent By pkrauss Date 2001-12-05 Time 10:11 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***