| Plan Review Stops For Permit 01071374 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-05-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-05-16 |
Time |
07:41 |
Rev Time |
0.15 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-05-16 00:00:00 | STORM SHUTTERS 2ND FL INTERIOR MOUNT, | | | 1ST FL EXTERIOR MOUNT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-01-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-01-10 |
Time |
12:17 |
Rev Time |
1.25 |
| Received By |
jwitmer |
Date |
2002-01-09 |
Time |
18:28 |
Sent To |
|
|
| Notes |
| 2002-01-10 00:00:00 | BUILDING TYPE I (MODEL) | | | MASTER 01071374 | | | BUILDING PROVISO: | | | NO SURVEY WITH PLANS, TABLE 600 ISSUES | | | CAN NOT BE ADDRESSED (WINDOW OPENINGS VS | | | PROPERTY LINE). THIS CONCERN WILL BE | | | ADDRESSED ON A INDIVIDUAL PERMIT BASIS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-11-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-11-28 |
Time |
17:40 |
Rev Time |
1.75 |
| Received By |
jwitmer |
Date |
2001-11-28 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2001-11-28 00:00:00 | BUILDING PLAN REVIEW | | | PLAN REVIEW 01071374 | | | TYPE I MODEL "BBAABB" | | | CONT: TRANSEASTERN | | | TEL: 753-5531 | | | | | | SBC=1997 STANDARD BUILDING CODE | | | SBC*= AMENDMENTS/ STANDARD BUILDING CODE | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | PLANS SUBMITTED FOR PERMIT APPLICATION | | | AFTER JAN.1,2002 WILL BE REVIEWED UNDER | | | 2001 FLORIDA BUILDING CODE REGARDLESS | | | OF A EARLIER PLAN REVIEW UNDER 1997 SBC. | | | | | | 1)- PLANS CAN NOT BE REVIEWED FOR SBC | | | TABLE 600 ISSUES-HORIZONTAL SEPERATION, | | | UNTIL A PLOT PLAN OR SURVEY IS SUBMITTED | | | | | | 2)- NORANDEX WINDOWS REQUIRES SITE SPEC- | | | IFIC REPORT. ACHETECT MUST SIGN, SEAL& | | | DATE EACH REPORT. | | | 3)- SHEET C-1 NOTE #14, HI RIB LATH. | | | ASTM C 1063 7.10.1.1.HIRIB TO BE FASTEN- | | | ED AT EVERY RIB (4" O.C.) | | | 4)- PLANS ARE TO BE SUBMITTED TO THE | | | COUNTY FOR REVIEW OF IMPACT FEES. | | | 5)- EACH LOT (TOWNHOUSE) SHALL SUBMIT | | | FOR A PERMIT APPLICATION WITH ASSOCIATED | | | FEES. | | | 6)- THIS PROJECT MAY REQUIRE A RESIDENT | | | INSPECTOR. CONTACT DON NEELY AT 659-8096 | | | EX.8333 FOR MORE INFORMATION. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096X8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-06-18 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-06-06 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-06-06 |
Time |
10:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-10-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-23 |
Time |
20:57 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-23 |
Time |
20:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-08-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-08-21 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-08-20 |
Time |
22:36 |
Sent To |
|
|
| Notes |
| 2001-08-21 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PLEASE NOTE THAT PLANS NEED RATINGS | | | FOR MAIN BRKR/LOAD CENTER. | | | | | | 2)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | GOING TO BUILDING STEEL AND COLD WATER | | | PER 250-50. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELELCTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-11-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-19 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-19 |
Time |
12:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-10-04 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-04 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-04 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2001-10-04 00:00:00 | NOT ALL PREVIOUS PLAN REVIEW COMMENTS | | | ADDRESSED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-08-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-08-07 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-08-07 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2001-08-07 00:00:00 | 1) NO SITE PLAN INDICATING WHERE | | | BUILDING WILL BE BUILT. | | | 2) NO FIRE HYDRANT LOCATION MAP. WET | | | FIRE HYDRANTS ARE REQUIRED PRIOR TO, | | | DURING AND AFTER CONSTRUCTION. | | | 3) BUILDING ADDRESSES REQUIRED. | | | 4) ARE THESE BUILDINGS RENTALS OR | | | OWNED. | | | 5) TENANT SEPARATIONS TO COMPLY WITH | | | BUILDING CODE REQUIREMENTS. | | | 6) ELECTRIC POWERED SMOKE DETECTORS | | | ARE REQUIRED. WHEN ACTIVATED, THESE | | | DEVICES ARE TO BE AUDIBLE IN THE | | | SLEEPING ROOMS OF THAT UNIT. | | | 7) PORTABLE FIRE EXTINGUISHERS ARE | | | REQUIRED. | | | 8) STORAGE NOT PERMITTED UNDER STAIRS | | | UNLESS PROPERLY FIRE RATED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-12-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-05 |
Time |
09:26 |
Rev Time |
2.00 |
| Received By |
pkrauss |
Date |
2001-12-05 |
Time |
07:55 |
Sent To |
Z |
|
| Notes |
| 2001-12-05 00:00:00 | *******************PROVISO************** | | | | | | | | | EXHAUST DUCT FOR DRYER SHALL NOT EXCEED | | | 25'.THERE SHALL BE A DEDUCTIONS OF 2 | | | 1/2' FOR EACH 45 DEGREE BEND AND 5' FOR | | | EACH 90 DEGREE BEND.THE WALL OR ROOF | | | CAP SHALL BE NONSCREENED WITH ADRAFT | | | DRAFT DAMPER. | | | | | | PLEASE INDICATE HOW COMBUSTIBLE LINT | | | WILL BE REMOVED (CLEANOUTS). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-10-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-13 |
Time |
09:49 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-10-13 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2001-10-13 00:00:00 | *******************DENIED*************** | | | | | | | | | NO MECHANICAL PLANS SUBMITTED FOR | | | REVIEW. | | | | | | 1.PROVIDE EQUIPMENT INFORMATION. | | | | | | 2.ENERGY CALCULATIONS WITH MANUAL J | | | CALCS FOR EQUIPMENT SIZING. | | | | | | 3.INFORMATION ON BATHROOM EXHAUST | | | FANS. | | | | | | 4.DUCT MATERIAL, R-VALUE, SIZE, CFM | | | DISTRIBUTION AND GRILL SIZE. | | | | | | 5.INDICATE DRYER EXHAUST DUCT SIZE, | | | MATERIAL AND TERMINATION. | | | | | | 6.INDICATE LOCATION OF CONDENSER | | | UNITS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-08-23 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-08-23 |
Time |
08:51 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2001-08-23 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2001-08-23 00:00:00 | DENIED | | | 1.PLANS LACK INFORMATION ON MECHANICAL | | | SYSTEMS, INCLUDING CODE REQUIRED MINIMUM | | | VENTILATION AND EXHAUST FOR BATHROOMS. | | | 2. PROVIDE INFORMATION ON BATHROOM | | | EXHAUST, DRYER EXHAUST AND AIR | | | CONDITIONING SYSTEM TO BE INSTALLED FOR | | | REVIEW. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2002-01-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-11 |
Time |
17:34 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-01-11 |
Time |
17:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2001-11-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-21 |
Time |
21:14 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-11-21 |
Time |
21:14 |
Sent To |
|
|
| Notes |
| 2001-11-21 00:00:00 | DENIED | | | | | | THIRD NOTICE: APPROVED UTILITY PLAN RE- | | | QUIRED FOR FINAL PLUMBING PLAN REVIEW. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-10-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-29 |
Time |
11:10 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-10-29 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2001-10-29 00:00:00 | DENIED | | | REFERENCE: SPC-94 | | | | | | 1) APPROVED UTILITY PLANS ARE REQUIRED | | | FOR FINAL PLUMBING PLAN REVIEW OF BUILD- | | | INGS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-08-16 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-08-16 |
Time |
17:09 |
Rev Time |
4.00 |
| Received By |
jleech |
Date |
2001-08-16 |
Time |
17:09 |
Sent To |
|
|
| Notes |
| 2001-08-16 00:00:00 | DENIED; | | | 1."B" UNIT RISER DIAGRAM. 2" WET VENT | | | CAN HAVE A MAXIMUM OF 4 FIXTURE UNITS. | | | VENT FOR WATER CLOSET WITH LAV, TUB, | | | AND SHOWER MUST BE 3" AFTER SHOWER TO | | | PROPERLY VENT W/C SPC SEC. 911.1. | | | 2.APPROVED UTILITYS PLANS ARE REQUIRED | | | FOR FINAL PLUMBING PLAN REVIEW OF BUILD- | | | INGS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8369 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2002-01-22 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-10-26 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-26 00:00:00 | SHEET C1, FRAMING NOTES.THE ARCHITECTS | | | DISCLAIMER FOR STRUCTURAL | | | RESPONSIBILITY IS NOT ACCEPTABLE.IN | | | DELEGATING ENGINEERING RESPONSIBILITY | | | TO A SPECIALTY ENGINEER IT IS THE | | | DESIGNER OF RECORD'S DUTYTO NOTE THE | | | LOCATION, NATURE, MAGNITUDE AND | | | DIRECTION OF LOADS TO BE RESISTED.AT | | | TIME OF PERMIT APPLICATION PROVIDE | | | SIGNED AND SEALED CALCULATIONS | | | DEMONSTRATING COMPLIANCE WITH SBC 1601. | | | | | | IN THE ABSENCE OF A SURVEY AND SITE | | | PLANA COMPLETE REVIEW FOR CODE | | | COMPLIANCE IS NOT POSSIBLE. | | | | | | SHEET A10 OF THE TYPE 3 BUILDING. TERMS | | | LIKE "(STRINGER BEARING TO COMPLY W/ SBC | | | 1997)" ARE NOT ACCEPTABLE SUBSTITUTES | | | FOR SPECIFIC DESIGN INFORMATION.SEE | | | SBC104.2.SAME SHEET, THE REFERENCE | | | SFBC 2907.3 (C) IS WITHOUTSTANDING. | | | | | | WITH REGARDS TO FREE AREA OF A SOFFIT | | | SCREEN VENT, A 7" X 22" SCREEN CAN | | | PROVIDE 40% TO 60% OF FREE AREA AND NOT | | | THE SIZE OF THE ROUGH OPENING. | | | FURTHER, WHEN INSTALLED SUBSEQUENT TO | | | WIRE LATH ADDITIONAL AREA REDUCTION | | | MUST BE ALLOWED FOR. | | | | | | SEE THE 8/27/01 LIST FOR IMPACT FEES, | | | RESIDENT INSPECTOR, ETC. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2002-01-22 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-08-27 |
Time |
07:47 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2001-08-23 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2001-08-27 00:00:00 | SHEET C1 SHOULD CITE THE 1997 SBC AS | | | THEGOVERNING DESIGN CODE AND NOT " ... | | | AS APPLICABLE ..." | | | | | | THERE WAS NO SITE PLAN OR SURVEY | | | INCLUDED WITH THE PLANS SO A COMPLETE | | | REVIEW FOR CODE COMPLIANCE WAS NOT | | | POSSIBLE. | | | | | | SOIL TREATMENT REQUIREMENTS SHOULD BE | | | ADDED TO THE FOUNDATION NOTES.SEE SBC | | | 2304.1.2 AS AMENDED. | | | | | | PLANS SUBMITTED FOR PUBLIC RECORD ARE | | | REQUIRED TO BE SIGNED, SEALED AND DATED | | | BY THE DESIGNER OF RECORD.SEE FS 471 | | | AND 481. | | | | | | SHEET C1 FRAMING NOTES, NOTE 6."THE | | | ARCHITECT ACCEPTS NO RESPONSIBILITY FOR | | | STRUCTURAL ..." A REGISTERED DESIGN | | | PROFESSIONAL MUST ASSUME RESPONSIBILITY | | | FOR THE STRUCTURAL REQUIREMENTS. | | | | | | SHEET C1 THE LOAD SCHEDULE IS NOT CLEAR | | | AS TO WHETHER ASCE 7 OR 1606.2 WAS USED | | | FOR THE WIND DESIGN. | | | | | | PROVIDE ENERGY CODE CALCULATIONS WITH | | | THE PERMIT APPLICATION. | | | | | | PROVIDE A TEST REPORT OR NOTICE OF | | | ACCEPTANCE FOR THE ROOF COVERING WITH | | | THE PERMIT APPLICATION. | | | | | | SHEET A2, PROVIDE THE SUPPORTING | | | DOCUMENTATION FOR THE "SAFE LOAD TABLE" | | | | | | SHEET A2. NOTE THE REQUIREMENT FOR | | | SAFETY GLASS IN ACCORDANCE WITH SBC | | | 2405.2 #3 FOR THE GLAZING IN THE | | | VICINITY OF THE ENTRANCE DOORS.A | | | GENERIC NOTE ON THE COVER SHEET IS | | | INSUFFICIENT. | | | | | | SHOW A CONSTRUCTION DETAIL FOR THE AREA | | | SHOWN AS "FRAMED DOWNED" ON SHEET A4. | | | | | | SHEET A9.SHOW THE STAIR STRINGER AND | | | TREAD SIZE AND MATERIAL SPECIFICATION. | | | | | | SHEET A9, STAIR DETAIL, HAS CONFLICTING | | | INFORMATION FOR THE PICKET SPACING (4 - | | | 6) AND FASTENER SIZE (#12 SCREW AND 5/8" | | | SCREW)PLEASE REVISE AS NECESSARY. | | | | | | PLEASE EXPLAIN HOW THE DETAIL SHOWN AS | | | "OPTION 1" ON SHEET A9 WILL ADEQUATELY | | | ADDRESS GRAVITY LOADS. | | | | | | THE DETAIL ON SHEET A10 CALLS FOR FRT | | | SHEATHING FROM A CENTERLINE WHILE SBC | | | 704.4.1 #2 REQUIRES FRT TO 4' FROM | | | EITHER SIDE OF THE WALL.REVISE AS | | | NECESSARY. | | | | | | PLEASE SPECIFY THE FREE AREA OF THE 6" X | | | 24" SOFFIT VENTS TO BE USED SO THAT | | | COMPLIANCE WITH SBC 2309.7 MAY BE | | | DETERMINED. | | | | | | SHOW A DETAIL FOR THE WINDOW AND DOOR | | | BUCK CONNECTIONS. | | | | | | BEFORE A PERMIT TO CONSTRUCT MAY BE | | | ISSUED IMPACT FEES MUST BE PAID TO THE | | | COUNTY AND THE PERMIT PLANS STAMPED BY | | | THEM.CALL 233-5025 FOR MORE | | | INFORMATION. | | | | | | A SEPARATE PERMIT APPLICATION IS | | | REQUIRED FOR EACH TOWNHOUSE UNIT. | | | | | | ON BUILDING TYPE 3, UNITS LABELED E MUST | | | COMPLY WITH SBC 1010.4. | | | | | | A RESIDENT INSPECTOR MAY BE REQUIRED FOR | | | THIS PROJECT.CONTACT DON NEELY AT | | | 659-8093 X 8333 FOR MORE INFORMATION. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2002-01-22 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2002-01-22 |
Time |
14:16 |
Rev Time |
0.25 |
| Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-01-22 00:00:00 | SITE PLANS APPROVED 01/22/02 MIKE SANCHE | | | Z DR |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2002-01-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-05 |
Time |
10:12 |
Rev Time |
0.25 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-12-10 00:00:00 | NO APPROVED SITE PLAN |
|
|