Plan Review Details - Permit 01071352
Plan Review Stops For Permit 01071352
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-10-09 Cont ID  
Sent By jwitmer Date 2001-10-09 Time 14:34 Rev Time 0.00
Received By jwitmer Date 2001-10-15 Time 07:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-08-28 Cont ID  
Sent By jwitmer Date 2001-08-28 Time 07:34 Rev Time 2.50
Received By jwitmer Date 2001-08-28 Time 07:34 Sent To  
Notes
2001-08-28 00:00:00BUILDING PLAN REVIEW:
  
 1)- 1997 FL ENERGY CODE 600. ENERGY CAL-
 CULATIONS INCLUDING MANUAL J.
  
 2)- SHEET A-2A DETAILS 1&2 WEDGE ANCHORS
 MISSING THE DIAMETER AND LENGTH.
  
 3)- SHEET A-2A DETAIL #2 MISSING FIRE
 STOP AT CEILING. SBC 2305.1.4.1.
  
 4)- TERMITE TREATMENT CODE: SOIL TREAT-
 MENT SECTION 103.7/2.1. ST LEAST A FULL
 6" CLEAR INSPECTION SPACE BETWEEN THE
 FOUNDATION SIDEWALL AND ANY WOOD, SIDING
 STUCCO ON WIRE LATH SHEATHINGOR FOAM
 BOARD DOWN TO THE SOD,MULCH, DECK, PORCH
 WALKWAY OR APRON.
  
 5)_ SHUTTER REPORT- SOUTHEASTERN METAL
 DETAIL SHEETS ARE ILLEGABLE, KEY PLAN
 FOR INSTALATION SHOWING FASTENERS.
  
 6)- GARAGE DOOR REPORT, THE DETAIL SHEET
 IS ALSO ILLEGABLE, THERE IS ALSO NO
 BUCK ATTACHMENT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-02-14 Cont ID  
Sent By btrobaug Date 2002-02-14 Time 11:52 Rev Time 0.30
Received By btrobaug Date 2002-02-14 Time 11:52 Sent To  
Notes
2002-02-14 00:00:00 
 PROVISO:
  
 BATH GFI TO BE ON ITS OWN CIRCUIT AS PER
 210-11C3

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-09 Cont ID  
Sent By dpalmer Date 2001-10-09 Time 11:24 Rev Time 0.00
Received By dpalmer Date 2001-10-09 Time 11:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-08-28 Cont ID  
Sent By dpalmer Date 2001-08-28 Time 09:49 Rev Time 0.00
Received By dpalmer Date 2001-08-28 Time 09:48 Sent To  
Notes
2001-08-28 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT PANEL IS SHOWN
 HAVING A MCB W/ A MAIN DISCONNECT ON THE
 OUTSIDE. PLEASE NOTE THAT PANEL MAY BE
 MLO.
  
 2) PLEASE CLARIFY EQUIPMENT GROUNDING
 METHOD BETWEEN FIRST MEANS OF DISCONNECT
 AND PANEL(S). EQUIPMENT GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
 MAY BE #6
  
 3)NOTE: PLEASE NOTE THAT PLAN SHOWS 2/0
 CONDUCTORS. MAY BE 1/0.
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 5) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 PLEASE NOTE THAT NOTES 1 AND 3 ARE JUST
 NOTES AND THOSE ITEMS MAY STAY AS THEY
 ARE IF DESIRED. PLEASE SUBMIT THE OTHERS
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 OR I CAN BE OF ANY ASSISTANCE, PLEASE
 CALL.
  
 DEWEY PALMER
 ELELCTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-02-14 Cont ID  
Sent By pkrauss Date 2002-02-14 Time 12:01 Rev Time 0.30
Received By pkrauss Date 2002-02-14 Time 12:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-08-28 Cont ID  
Sent By pkrauss Date 2001-08-28 Time 10:30 Rev Time 0.35
Received By pkrauss Date 2001-08-28 Time 10:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-08-20 Cont ID  
Sent By pkrauss Date 2001-08-20 Time 08:01 Rev Time 0.35
Received By pkrauss Date 2001-08-20 Time 08:01 Sent To  
Notes
2001-08-20 00:00:00*******************DENIED***************
  
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND PLANS WITH MECHANICAL
 PERMIT APPLICATION.
  
 PLEASE PROVIDE INFORMATION ON THE AHU
 AND CONDENSER BEING INSTALLED.PROVIDE
 MANUFACTURER, MODEL, SEER/ERR RATING,
 AND KW FOR HEAT STRIP.
  
 INDICATE CONDENSATE LINE SIZE AND
 MATERIAL TO BE USED AS WELL AS
 INSULATION.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-08-13 Cont ID  
Sent By kstevens Date 2001-08-13 Time 16:50 Rev Time 0.50
Received By kstevens Date 2001-08-13 Time 16:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2001-10-09 Cont ID  
Sent By sgraham Date 2001-10-09 Time 13:37 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2001-08-28 Cont ID  
Sent By sgraham Date 2001-07-30 Time 11:20 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-08-28 00:00:00GARAGE APT WAS TORN DOWN, NEW BLDG MUST
 MEET THE REQUIRED SETBACKS